• Title/Summary/Keyword: 엘리미네이터

Search Result 1, Processing Time 0.017 seconds

Pressure Drop and Refrigerant-Entrainment Characteristics of the Eliminators used in Absorption Chillers (흡수식 냉동기용 엘리미네이터의 압력손실 및 액적유입 특성)

  • 정시영;류진상;이상수;이정주
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.2
    • /
    • pp.109-115
    • /
    • 2003
  • The performance of two vertical-blade eliminators (V1, V2) and two horizontal-blade ones (H1, H2) for absorption chillers were tested in terms of pressure drop and refrigerant entrainment. The test was carried out using a wind tunnel with a cross section of 300 mm$\times$300 mm. The pressure drop of four eliminators tested was found to be in the rage of 1.0~2.7mm $H_2O$ at the face velocity of 2m/s. In the refrigerant entrainment test the vertical-blade eliminators showed much better performance than the horizontal-blade ones. The horizontal-blade eliminators showed satisfactory results at the air velocity of 2m/s but exceeded the limit value at 3 m/s. Since the cooling capacity of a machine is lowered by about 2.5% at the pressure drop of 1 m $H_2O$, more researches are required to reduce the pressure drop in the eliminator.