• Title/Summary/Keyword: 아이스슬러리 제빙기

Search Result 5, Processing Time 0.021 seconds

A Study on the Heat Transfer Characteristics of Ice Slurry Generator with Scraper (스크레이퍼형 아이스슬러리 제빙기의 열전달 특성 연구)

  • Kim, Min-Jun;Kim, Joung-Ha;Yun, Jae-Ho;Park, Il-Hwan;Cho, Hyoug-Seok;An, Seong-Kuk
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.1974-1979
    • /
    • 2007
  • In this study, Ice slurry generator heat transfer characteristics are experimentally investigated for the ice slurry generating system with scraper which is pneumatically operated. The ice slurry generator has the same shape as the vertical double tube type heat exchanger. Refrigerant is flowing in the outside tube and ethylene glycol solution in the inside tube. Refrigerant and solution water are parallel flow type which entering bottom of generator and leaving top of generator. The experimentations are conducted under the various test conditions such as compressor speed and cooling water temperature. For the above experimental conditions, heat transfer characteristics of the ice slurry generating system are evaluated in terms of the overall heat transfer coefficient and the heat transfer rate. And the experimental results show that the heat transfer rate of the system is increased as the compressor speed increases and the cooling water temperature decreases.

  • PDF

Continuous Ice Slurry Production and Control of Ice Packing Factor in a Pipe for the District Cooling (지역냉방을 위한 아이스슬러리의 연속제조 및 배관내 빙충전율 조절)

  • Kwon, Jae-Sung;Lee, Yoon-Pyo;Lee, Sang-Hoon;Yoo, Ho-Seon;Yoon, Seok-Mann
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.12
    • /
    • pp.825-832
    • /
    • 2008
  • The ice slurry maker which can produce the ice slurry well for the ice particle in-flowing condition was revised. We removed the stagnant region at the top of the ice slurry maker, and IPF 40% could be realized. The IPF controller with 6 mm diameter holes at the bottom was designed. But the IPF controller with only 6 mm diameter holes could not control IPF in a pipe. This is because the ice particles at ice slurry flow exist homogeneously not only at the upper part but also at the bottom part. We changed the hole size of IPF controller surface using fine meshes and then, IPF in a pipe was increased by 70% when the hole size was $80{\mu}m$ and less.

Ice slurry transporting and branching characteristics for the district cooling (지역냉방을 위한 아이스슬러리 시스템의 수송 및 분기 특성)

  • Lee, Sang-Hoon;Yoo, Ho-Seon;Lee, Yoon-Pyo;Lee, Chang-Jun;Kwon, Hyeok-Min
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.662-667
    • /
    • 2009
  • The research are performed to check the characteristics of the ice slurry transport system for the district cooling. The system are installed at the 1st floored building which is as large as the $1204\;m^2$ ($86\;m{\times}14\;m$), and the pumping power and branching characteristics are measured by transporting of the ice slurry. The ice slurry transporting pipe is as long as 200 m. For the same cooling load, the higher IPF is, the lower the transporting flow rate and the pumping power are. But when the IPF is higher than 15%, no less decrease of the pumping power does happen. For the branching characteristics, through the branch pipe where the flow resistance is higher, the higher IPF is measured. A little higher IPF is measured at the thermal expansion branch.

  • PDF

A Study on the Heat Transfer Characteristics of Slurry Ice Generator using Scraper (스크레퍼형 슬러리아이스 제빙기의 열전달 특성 연구)

  • Kim, Joung-Ha;Yun, Jae-Ho;Kim, Min-Jun;Kim, Kyu-Jin;Cho, Hyoug-Seok;An, Seong-Kuk
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.144-149
    • /
    • 2006
  • In this study ice making characteristics are experimentally investigated for the ice slurry generating system which is pneumatically operated. The experimentations are conducted under the various test conditions such as chilled water inlet temperature, aqueous solution concentration, flow rate of cooling water, scraper pitch and frequency of cylinder stroke. For the above experimental conditions, ice making characteristics of the slurry ice generating system are evaluated in terms of the overall heat transfer coefficient, heat transfer rate and the amount of slurry ice generation. And the experimental results show that the heat transfer rate of the system increases as the flow rate of cooling water solution increases and the concentration of ethylene glycol and inlet temperature of chilled water decreases.

  • PDF