• 제목/요약/키워드: 복합 애자

검색결과 33건 처리시간 0.037초

복합 고분자 애자의 열화 진단 데이터 분석 기법 (Introduction of Data Analysis Method for Ageing Diagnosis of Polymer Insulator)

  • 최남호;이병성;조성수;한상옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1611-1613
    • /
    • 1999
  • This paper introduces the data processing method and the measurement of the leakage current flowing through polymer insulators. For ageing diagnosis of polymer insulator, data aquisition system was developed to record the leakage current of insulator being tested. Hence, we have gained information for life time from its leakage current. the DAS is protected against over-voltage which would develop in the event of a flashover of the test sample.

  • PDF

가공 배전선로 절연물의 열화와 이상 신호 특성에 관한 연구 (The Study on Electromagnetic Signal Emitted from Defected insulations on Overhead Distribution line)

  • 이병성;박용업;최선규;양정권
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.2085-2086
    • /
    • 2011
  • 전력설비의 절연물이 사용 환경 영향을 받아 열화되어 방전이 발생하게 되는데, 이 때 발생하는 방전의 크기 및 량은 절연물의 결함 형태와 환경에 영향을 받아 다양하게 나타난다. 절연물 결함에서 발생하는 신호는 열, 전자파, 초음파, 빛의 형태이며, 이들 신호가 복합적으로 방출된다. 결함을 갖는 절연물 종류에 따라 발생하는 이상 신호 패턴을 분석하여 절연성능 저하를 검출할 수 있고, 절연성능 저하 원인 규명에도 활용된다. 본 연구에서는 전력설비에 사용하고 있는 결함 또는 열화된 애자류의 이상신호 발생의 근본원인을 고찰하였으며, 이들의 신호를 검출하는 적절한 방법을 제시하였다.

  • PDF

산불 모의 실증 시험 설비 구축 (Study on the installation of Forest Fire Simulation Facility)

  • 이원교;최인혁;이상윤;노희원
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.361_362
    • /
    • 2009
  • 우리나라 송전선로의 위치는 대부분 산악지형에 포설되어 있어 산불 발생으로 인한 피해에 취약한 구조이다. 주로 산불에 의한 화염, 열, 연무 등 복합적인 환경 요인이 송전선로에 영향을 미치게 되며, 이로 인해 송전 선로를 구성하는 전선 및 애자를 포함한 금구류 등이 본래의 기능을 상실하게 되어 전력 공급에 문제가 발생하게 된다. 또한 산불 진화에 사용하는 물과 방재용 약재에 의해 발생하는 부가적인 송전 선로의 특성 변화 역시 잠재적인 사고 발생 요인으로 볼 수 있다. 본 논문은 이러한 산불 발생시 송전선로에 미치는 영향 및 특성 연구를 위해 산불의 특성을 살펴보고 특성을 모의하여 시험 할 수 있는 산불 모의 실증 시험 설비를 구축에 대해 설명한다.

  • PDF

Composite Insulator 구성 부품에 대한 최적 설계 연구 (Study on Optimum Design for constitution part of Composite Insulator)

  • 정용수;최성만;장윤기;이동원;김정배
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2008년도 추계학술대회A
    • /
    • pp.1181-1186
    • /
    • 2008
  • Insulators which are used in the domestic electrical industries are mostly depended on importation from some advance countries. Even though insulators which are made of ceramic material have been mostly used domestically, the ratio of usage on composite insulators is recently being increased because of difficulties in manufacturing and high cost regarding ceramic stuffs. In this research, we are trying to develop the composite insulators which are very efficient in insulation regardless of the matter of weight. Even though the technique of manufacturing composite insulator are quite generalized worldwide at the moment, one of the most important issue is to keep security on the know-how that an ingredient of insulated material named 'SF6 gas' is included. Therefore, The aim of this paper is to improve the bonding force and air tight property between two components of composite insulator, Flange and FRP Tube.

  • PDF

배전용 폴리머애자 열화특성 평가를 위한 복합열화 시험장치 구축 (A Combined Aging Test Facility for Evaluating an Aging Characteristics of Distribution Polymer Insulators)

  • 이병성;한재홍;김찬영;윤태상
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1948-1950
    • /
    • 2000
  • Polymeric composite insulators have been in use for outdoor insulation. However, our knowledge about their long-term performance in an outdoor environment is still very limited. Especially, these insulators are subjected to the environmental stress such as ultraviolet radiation, electrical stress, mechanical load, etc.. Hence, in this paper, we simulated the factors having influence on aging of polymer insulators using the combined aging test chamber. In order to evaluate an aging characteristics with time, we measured leakage current on these insulators to make out the degree of aging.

  • PDF

컴팩트형 철탑 설계에 관한 연구 (Study on the compact design for steel tower)

  • 이원교;박준호;최인혁;이동일;송홍준;변기식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.711-712
    • /
    • 2007
  • 전력수요의 지속적 증가에 따라 송전설비의 추가적인 건설은 불가피하지만 토지구입비 증대 및 님비현상 등에 따른 토지구입난 등의 건설여건의 악화에 따라 보다 더 최적화 된 송전철탑의 도입이 요구되고 있다. 고분자소재 및 성형기술의 발달로 금속의 기계적 강도를 능가하는 절연성능을 가진 고분자 복합재료의 제작이 가능하게 되면서 큰 기계적 강도가 요구되는 철탑의 암(arm)을 고강도 FRP(Fiber glass Reinforced Plastics)를 적용한 암 절연물(braced post insulator)로 대체하려는 시도가 진행되고 있다. 본 논문은 기존의 철탑에서 도체를 지지하고 고전압이 인가된 도체의 공간적 절연 유지를 위하여 사용되던 무거운 금속 암과 애자련 대신 중심부분을 전기적 특성과 내환경성이 우수한 암 절연물을 사용한 154kV급 철탑 설계 방법과 컴팩트화 방법에 대해 제시하고자 한다.

  • PDF

송전용 폴리마 런자의 장기성능을 위한 복합열화시험 (Multi-aging Test for Estimating Long Time Performance of Polymer Insulators for Transmission line)

  • 조한구;한세원;이운용;윤문수
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1999년도 추계학술대회 논문집
    • /
    • pp.640-643
    • /
    • 1999
  • This paper presents the results of multi-stress chamber experiments done to examine the tracking and erosion performance of polymer insulator. Multi-stress testing is able to demonstrate deficiencies of polymer insulator materials and designs, including the nature of interfaces in insulation design. Therefore, multi-stress testing is believed to a suitable test for evaluating the aging performance of polymer insulator designs. We have nvestigated IEC 61109 Annex C for estimating long time performance of polymer insulator.

  • PDF

폴리머 현수애자의 복합가속열화 평가기술 (Multi-Stress Aging Test Technology for Suspension Polymer Insulator)

  • 박효열;강동필;김익수;신영준
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.1
    • /
    • pp.481-484
    • /
    • 2003
  • Recently polymer insulators are being used for outdoor high voltage applications. Polymer insulators have significant advantages over porcelain and glass insulators. With the gradual improvement of their design and material, their reliability has also increased. It is however difficult to establish how they will perform after several years of service. Aging of the insulator weathershed may lead to damages such as excessive chalking and crazing, erosion and tracking which affect the insulator performance. In service insulator are subjected to aging stresses such as humidity, pollution and electrical field which act singly or in combination. There have been numerous accelerated laboratory tests developed with the intention of evaluating suitability of polymeric materials. Some of these are strictly material tests, where as, others evaluate full scale devices. Service experience plays a key role in the utility selection of polymer insulator, but is time consuming, and may not always be available. Hence there is a need for a meaningful and reliable accelerated aging test for polymer insulator. This paper describes multi-stress aging test for reliability of polymer insulator This paper presents the rule of multi-stress aging test and test chamber for polymer insulator in korea electrotechnology research institute.

  • PDF

800kV $SF_6$ 가스절연 개폐장치용 (GIS) 복합절연애자 (Composite Hollow Insulator)의 표면오손시 내전압특성 (Flashover Voltage of 800kV Class Composite Hollow Insulator for $SF_6$ Gas Insulated Switchgear (GIS))

  • 이창용;윤자홍;최병화;윤치영;고경석;반석걸;허종철
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1449-1451
    • /
    • 2002
  • A developed 800kV class composite hollow insulator for $SF_6$ Gas Insulated Switchgear (GIS) was tested as to insulation with their surfaces contaminated. The wet power frequency withstand voltage of the silicone rubber housing was about 135kV at an equivalent salt deposite density of $5kg/m^2$, to sufficiently satisfy the required performance. According to IEC 60507, the salt fog withstand voltage was measured at 565kV, and the highest measured leakage current was below 0.2mA. Therefore, it was clarified that the composite hollow insulator has sufficient insulation performance even when it is contaminated on the surface.

  • PDF

트래킹 휠과 복합열화시험에 의한 폴리머 애자의 성능 평가 (Performance Evaluation of Polymer Insulator using Tracking Wheel and Multi-Aging Test)

  • 조한구;안명상;한세원;허종철;이운용
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.119-122
    • /
    • 2000
  • Recently polymer insulators are being used for outdoor high voltage applications. Polymer insulators for transmission line have significant advantages over porcelain and glass insulators, especially for ultra-high voltage transmission lines. Their advantages are light weight, vandalism resistance and hydrophobicity. Polymer insulators are a relatively new technology, but their expected life is still unknown. Therefore these estimating technique are very important. Their life time is related to weathering and operating condition. Multi-aging test is requested because aging factor is occurred by multi-aging than unique aging. The aging test about polymer insulators have mainly carried out by IEC 61109. This paper presents multi-stress chamber experiments and tracking wheel test to examine the tracking and erosion performance of polymer insulator for transmission. Multi-stress testing is able to demonstrate deficiencies of polymer insulator materials and designs, including the nature of interfaces in insulation design. We have investigated IEC 61109 Annex C (5000h aging test) and CEA tracking wheel test as test methods of artificial accelerated aging. The aging degree of polymer insulator is estimated by leakage current, measurement of hydrophobicity degree, damage conditions of insulator surface, withstand voltage test etc.

  • PDF