• 제목/요약/키워드: 복수 지열정

검색결과 10건 처리시간 0.029초

지반 투수계수와 양수량 조건이 복수정 지열 히트펌프 시스템의 성능에 미치는 영향 (The Effect of Soil Permeability and Pumping Rate on Performance of Two-well Geothermal Heat Pump System)

  • 조정흠;남유진
    • 한국지열·수열에너지학회논문집
    • /
    • 제11권4호
    • /
    • pp.28-34
    • /
    • 2015
  • The groundwater heat pump (GWHP) systems have great potential for heating-cooling system which use annual constant groundwater temperature for heat source. Generally, the performance of GWHP system significantly depends on the geological and hydraulic properties such as hydraulic conductivity, thermal conductivity, soil condition so on. Therefore, in order to use GWHP systems efficiently, it is necessary to analyze the effect of design factors on the system performance. However, there are a few researches on the optimum design method for the open-loop geothermal system. In this research, the design factor in the open-loop geothermal system was analyzed quantitatively for the optimal design method by using numerical simulation. As a result, it was found that the temperature change of heat source depends on the design factor.

관정간 도수통로를 설치한 개방형 지열 시스템의 냉방성능 실험 (Performance Analysis for Open-loop Geothermal System with Spill-way technology by Real-scale Experiment)

  • 김홍교;배상무;남유진;전운;오종현;이병호
    • 설비공학논문집
    • /
    • 제30권4호
    • /
    • pp.186-194
    • /
    • 2018
  • A ground-source heat pump system (GSHP) is more energy efficient than other heat-source systems because it uses annual constant underground and water temperatures. Especially, two-well geothermal systems using groundwater as the heat source can achieve higher performance than closed-loop geothermal systems. However, performance of two-well geothermal systems is decreased by occurring overflow according to scale during long-term operations. Therefore, this study presents a two-well pairing geothermal system that controls the groundwater level of a diffusion well. In addition, a two-well pairing geothermal system and an SCW geothermal system were installed, and a comparative analysis of cooling performance depending on system operation under the same load conditions was conducted. The result was that the average heat pump coefficient of performance (COP) of the two-well pairing system was 6.5, and the entire system COP was 4.3.

지하수 부존지역에서 최적 지열에너지 활용방식 수치 모의 (Numerical Simulations for Optimal Utilization of Geothermal Energy under Groundwater-bearing Conditions)

  • 김진성;차장환;송성호;정교철
    • 지질공학
    • /
    • 제24권4호
    • /
    • pp.487-499
    • /
    • 2014
  • 최근 지열에너지 활용 증가 추세와 더불어 지하수 부존량이 풍부한 지역에서 수직개방형의 효율이 더 높다는 연구결과가 제시됨에도 불구하고, 국내 지열냉난방시스템의 열교환 방식은 수직밀폐형 방식이 주를 이루고 있다. 따라서, 본 연구에서는 지하수 부존량이 풍부한 지역에서 수직개방형 방식의 효율성을 검증하기 위하여, 수리지질 및 열적 특성을 반영한 최적의 지열에너지 활용 방식을 수치 모의하였다. 1차 모의 결과, 지하수 부존량이 풍부한 지역에서 지열냉난방시스템을 활용하는 경우 수직밀폐형보다 지하수를 직접 이용하는 수직개방형이 더욱 효과적인 것으로 분석되었으며, 수직개방형 중에서는 SCW (standing column well)형 보다는 주입정과 추출정이 분리된 복수관정형에서 지반과 열교환을 통해 얻을 수 있는 주입수와 추출수의 온도차 (${\Delta}$)가 커 더욱 효율적인 것으로 나타났다. 2차 모의에서는 수직개방형 지열에너지 공급방식인 단일관정형, SCW형, 복수관정형을 대상으로 열 이송, 이격거리 및 유량, 지하수 수리경사 등을 고려한 최적의 활용 방식을 검토하였으며, 이를 바탕으로 지열냉난방시스템의 지중 열교환 방식 선정 시 활용할 수 있는 흐름도를 제시하였다. 본 연구결과 제시된 다양한 선정 기준을 기초로 실제 선정 시에는 전체 지열냉난방 시스템에 대한 COP (coefficient of performance) 계산 및 세부적인 타당성 검토가 필요할 것으로 판단된다.

복수정을 이용한 개방형 지열 시스템의 초기투자비 회수기간 분석 (Analysis of the Initial Cost Payback Period on the Open-loop Geothermal System Using Two Wells)

  • 조정흠;남유진
    • 설비공학논문집
    • /
    • 제29권3호
    • /
    • pp.119-126
    • /
    • 2017
  • Recently, ground source heat pump systems are being used in buildings for cooling and heating to reduce greenhouse gas and save energy. However, ground source heat pump systems mainly use the vertical closed-loop geothermal system design rather than the open-loop geothermal system design. This is due to a lack of knowledge and few research feasibility studies. In this research, a dynamic thermal analysis numerical simulation based on a standard house model was conducted for an open-loop geothermal system. Based on heating load analysis results, the life cycle costs of a standard house using an open two-well geothermal system were analyzed and compared with a vertical closed-loop geothermal system, and a diesel boiler. As a result, it was found that using an open two-well geothermal system shows economic return on investment after three years.

수치 시뮬레이션을 이용한 복수정(Two-Well) 개방형 지열 시스템의 열원수 온도 변화 검토 (A Study on the Characteristics of Heat Source Temperature for Two-Well Geothermal System Using Numerical Simulation)

  • 조정흠;남유진
    • 설비공학논문집
    • /
    • 제27권4호
    • /
    • pp.207-212
    • /
    • 2015
  • The use of groundwater and ground_heat is one of the ways to use natural and renewable energy, and it has been considered as a technology to reduce greenhouse gas emissions and increase energy-saving. There are a few researches on the optimum design for the open-loop geothermal system. In this study, to develop the optimal design method numerical simulation of the open-loop geothermal system with two-wells was performed by a groundwater and heat transfer model. In this paper, a study was performed to analyze the system performance according to well distance and pumping flow rate. In the result, average heat exchange rate and heat source temperature were calculated and it was found that they were dependent on the pumping rate.

지하수 열원 복수정 지열 열펌프 시스템의 성능에 관한 실험적 연구 (An Experimental Study of Ground Water Source Two Well Type Geothermal Heat Pump System)

  • 임효재;권정태;김창업;공형진;박성구
    • 설비공학논문집
    • /
    • 제21권8호
    • /
    • pp.468-474
    • /
    • 2009
  • Ground water source heat pump system is the oldest one of the ground source heat pump systems. Despite of this, little formal design information has been available until recently. The important design parameters for open system are the identification of optimum ground water flow, heat exchanger selection and well pump. In this study, the capacity of 50 RT system of two well type ground water heat pump system was used. As a result, static water level was -7 m and the level during the heating operation was -32 m, cooling operation was -40 m. The initial static water level recovered within 48 hrs. The temperature of ground water is $15.6^{\circ}C$ for heating season and $16.2^{\circ}C$ for cooling season and does not depend on the outdoor temperature. Operation efficiency of the system shows that, COP 3.1 for heating and COP 4.2 for cooling.

기계설비공사 분리발주 현황

  • 대한설비건설협회
    • 월간 기계설비
    • /
    • 8호통권205호
    • /
    • pp.28-37
    • /
    • 2007
  • 대한설비건설협회는 지난 1989년 협회 창립 이후 설비건설업계의 영역확대를 위해 분리발주를 숙원사업 중 하나로 정하고 그 동안 관계기관에 건의하는 등 끊임없는 노력을 기울여 왔다. 우리협회의 이러한 노력에 힘입어 대한주택공사를 비롯한 정보통신부, 교육인적자원부 등 주요 발주처 및 발주기관에서 분리발주를 시행하고 있다. 최근들어 기계설비공사는 단순한 기계설비에서 벗어나 쓰레기이송설비, 지열냉난방시스템 등 최첨단 기술을 접목한 다양한 시공으로 확대되고 있다. 이 과정에서 업역에 대한 확고한 규정이 없어서 설비•일반•전문건설업자간 치열한 밥그릇 싸움이 예상되고 있다. 따라서 대한설비건설협회는 이러한 신규분야가 우리 설비건설영역이 될 수 있도록 더욱 박차를 가할 계획이다. 또한 지난 5월 17일 공포된 건설산업기본법 개정(안)에는 2개 공종 이상의 소규모 단순복합공사는 전문건설업자에게 원도급을 허용하는 조항이 들어있다. 이로써 오는 2009년 7월 1일부터는 소규모 단순복합공사의 경우 전문건설업자도 전문면허를 복수로 취득하여 원도급 공사 참여 가능하게 됐으며, 분리발주와 동일한 효력을 갖는다. 본지는 앞으로 분리발주 확대를 위한 각오를 새롭게 다지기 위해 대한설비건설협회의 분리발주를 추진 과정 및 분리발주된 공사현황(10억원 이상, 2002년부터)을 살펴본다.

  • PDF

복수정 페어링 기술을 이용한 개방형 지열 시스템의 수리적 타당성 검토 (Hydraulic feasibility study on the open-loop geothermal system using a pairing technology)

  • 배상무;김홍교;김현우;남유진
    • KIEAE Journal
    • /
    • 제17권3호
    • /
    • pp.119-124
    • /
    • 2017
  • Purpose: Groundwater heat pump (GWHP) system has high coefficient of performance than conventional air-source heat pump system and closed-loop type geothermal system. However, there is problem in long-term operation that groundwater raise at the diffusion well and reduced at the supply well. Therefore, it is necessary to accurately predict the groundwater flow, groundwater movement and control the groundwater level in the wells. In this research, in consideration of hydrogeological characteristic, groundwater level and groundwater movement were conducted analysis in order to develop the optimal design method of the two-well system using the pairing pipe. Method: For the optimum design of the two-well system, this research focused on the design method of the pairing pipe in the simulation model. Especially, in order to control the groundwater level in wells, pairing pipe between the supply well and diffusion well was developed and the groundwater level during the system operation was analyzed by the numerical simulation. Result: As the result of simulation, the groundwater level increased to -2.65m even in the condition of low hydraulic conductivity and high pumping flow rate. Consequently, it was found that the developed system can be operated stably.

개방형 지열 히트펌프 시스템의 운전 특성 (Operation Characteristics of Open Type Geothermal Heat Pump)

  • 임효재;공형진;송윤석;박성구
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.701-706
    • /
    • 2006
  • Groundwater heat pump systems are the oldest of the ground-souce systems and it has various type. Standing column well type are must be located in hard rock geology site and produce sufficient water for the conventional open loop system. These system are indirect type(the building circulating loop and ground water are intercept). Existence of the exchanger the foundation protect water quality to use of open loop. The design of open loop system are concern on the power requirements. An experimental study was analysis the extremely heating operation COP of ground water heat pump system. Operation efficiency of the 50RT systems shows that, COP $2.9{\sim}5.0$ in heating operation. And generally it shows 3.4.

  • PDF