• Title/Summary/Keyword: 보어홀 열교환기

Search Result 29, Processing Time 0.023 seconds

A Study on the Effects of Design Parameters of Vertical Ground Heat Exchanger on the Borehole Thermal Resistance (수직밀패형 지중열교환기의 설계인자가 보어홀 전열저항에 미치는 영향에 관한 연구)

  • Chang, Keun Sun;Kim, Min-Jun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.10
    • /
    • pp.128-135
    • /
    • 2018
  • Currently, vertical closed ground heat exchangers are the most widely utilized geothermal heat pump systems and the major influencing parameters on the performance of ground heat exchangers are the ground thermal conductivity(k) and borehole thermal resistance($R_b$). In this study, the borehole thermal resistance was calculated from the in-situ thermal response test data and the individual effects of design parameters (flow rate, number of pipe, grout composition) on the borehole thermal resistance were analyzed. The grout thermal resistance was also compared with the correlations in the literatures. The borehole thermal resistance of the investigated ground heat exchanger results in 0.1303 W/m.K and the grout thermal resistance (66.6% of borehole thermal resistance) is the most influencing parameter on borehole heat transfer compared to the other design parameters (pipe thermal resistance, 31.5% and convective thermal resistance, 1.9%). In addition, increasing the thermal conductivity of grout by adding silica sand to Bentonite is more effective than the other design improvements, such as an increase in circulating flowrate or number of tubes on enhancing borehole heat transfer.

Evaluation of Performance of Grouts and Pipe Sections for Closed-loop Vertical Ground Heat Exchanger by In-situ Thermal Response Test (현장 열응답 시험을 통한 수직 밀폐형 지중열교환기용 그라우트와 열교환 파이프 단면의 성능 평가)

  • Lee, Chul-Ho;Park, Moon-Seo;Min, Sun-Hong;Choi, Hang-Seok;Sohn, Byong-Hu
    • Journal of the Korean Geotechnical Society
    • /
    • v.26 no.7
    • /
    • pp.93-106
    • /
    • 2010
  • In performing a series of in-situ thermal response tests, the effective thermal conductivities of six vertical closed-loop ground heat exchangers were experimentally evaluated and compared one another, which were constructed in a test bed in Wonju. To compare thermal efficiency of the ground heat exchangers in field, the six boreholes were constructed with different construction conditions: grouting materials (cement vs. bentonite), different additives (silica sand vs. graphite) and the shape of pipe-sections (general U-loop type vs. 3 pipe-type). From the test results, it can be concluded that cement grouting has a higher effective thermal conductivity than bentonite grouting, and the efficiency of graphite better performs than silica sand as a thermally-enhancing addictive. In addition, a new 3 pipe-type heat exchanger provides less thermal interference between the inlet and outlet pipe than the conventional U-loop type heat exchanger, which results in superior thermal performance. Based on the results from the in-situ thermal response tests, a series of economic analyses have been made to show the applicability of the new addictives and 3 pipe-type heat exchanger.

Thermal Conductivity Measurement of Grouting Materials for Ground Heat Exchanger Borehole (지중 열교환기 보어홀 그라우팅 재료의 열전도도 측정)

  • Sohn, Byong-Hu;Shin, Hyun-Joon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.6
    • /
    • pp.493-500
    • /
    • 2006
  • This paper concerns the measurement of thermal conductivity of grouting materials for ground loop heat exchanger. A thermal conductivity meter, QTM-500 based on modified transient hot wire method was used to measure the thermal conductivity of neat bentonite and mixtures of bentonite and various additives. Relative to the total mixture mass, as the percent additive was increased the mixture thermal conductivity increased. For the bentonite-silica sand mixtures, the higher density of the sand particles resulted in much higher mixture thermal conductivity. The quartzite and silica sands produced the largest increases in mixture thermal conductivity, while common masonry and limestone sands produced lower thermal conductivity increases.

Evaluation of Borehole Thermal Resistance in Ground Heat Exchanger (지중 열교환기의 보어홀 열저항 산정에 관한 연구)

  • Yoon, Seok;Lee, Seung-Rae;Kang, Han-Byul;Go, Gyu-Hyun;Kim, Min-Jun;Shin, Ho-Sung
    • Journal of the Korean Geotechnical Society
    • /
    • v.29 no.10
    • /
    • pp.49-56
    • /
    • 2013
  • The use of geothermal energy has been increased for economic and environmental friendly utilization. Ground thermal conductivity and borehole thermal resistance are very important parameters in the design of geothermal heat pump system. This paper presents an experimental study of heat exchange rate of U and W type ground heat exchangers (GHEs) measured by thermal performance tests (TPTs). U and W type GHEs were installed in a partially saturated dredged soil deposit, and TPTs were conducted to evaluate heat exchange rates under 100-hr continuous operation condition. The heat exchange rates were also calculated by analytical models to estimate borehole thermal resistances and were compared with experimental results. It comes out that multi-pole and equivalent diameter (EQD) models resulted in more accurate agreement than shape factor (SF) model which is currently more often used.

A Study on the Estimation of Soil Formation Thermal Conductivities and Borehole Resistances with One-Dimensional Numerical Model and In-Situ Field Tests (1차원 수치모델과 현지측정에 의한 지중열전도율 및 보어홀 전열저항 해석에 관한 연구)

  • Lee Se-Kyoun;Woo Joung-Son;Ro Jeong-Geun;Kim Dae-Ki
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.10
    • /
    • pp.783-790
    • /
    • 2006
  • A one-dimensional numerical model coupled with parameter estimation is used to predict the effective thermal conductivities of soil formations and borehole resistances from in situ field test data. In this application a new method of using initial ignoring time (IIT) obtained from error estimation is tried and turned out to be successful in determining soil thermal conductivities. This method is used for single-U and double-U borehole system. The results of this method are compared and agreed well with those of existing software (GPM) in the analysis of single-U borehole data. In the analysis of double-U borehole data this method seems to be better in predicting soil and borehole properties.

Evaluation of Ground Effective Thermal Properties and Effect of Borehole Thermal Resistance on Performance of Ground Heat Exchanger (지중 유효 열물성 산정 및 지중열교환기 성능에 대한 보어홀 열저항의 영향)

  • Sohn, Byonghu
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.8 no.4
    • /
    • pp.32-40
    • /
    • 2012
  • Geothermal heat pump(GHP) systems use vertical borehole heat exchangers to transfer heat to and from the surrounding ground via a heat carrier fluid that circulates between the borehole and the heat pump. An Important feature associated with design parameters and system performance is the local thermal resistances between the heat carrier flow channels in the borehole and the surrounding ground. This paper deals with the in-situ experimental determination of the effective thermal properties of the ground. The recorded thermal responses together with the line-source theory are used to determine the thermal conductivity and thermal diffusivity, and the steady-state borehole thermal resistance. In addition, this paper compares the experimental borehole resistance with the results from the different empirical and theoretical relations to evaluate this resistance. Further, the performance simulation of a GHP system with vertical borehole heat exchangers was conducted to analyze the effect of the borehole thermal resistance on the system performance.

A Study on the Thermal Characteristics of Jeju type Ground Heat Exchanger for Ground Source Heat Pump System applied to Jeju Island (제주도에 설치된 지열 열펌프 시스템용 제주형 지중열교환기의 열특성 연구)

  • Kim, Min-Jun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.21 no.2
    • /
    • pp.32-38
    • /
    • 2020
  • This study summarizes test methods and evaluation methods for examining the thermal characteristics of Jeju-type ground heat exchangers (GHXs) installed on Jeju Island, and analyzes the ground temperature and thermal characteristics of ground heat exchangers installed in various regions by using thermal response tests (TRT). Jeju Island is composed of volcanic rock layers, and the groundwater flow is well developed. A Jeju-type GHX can be installed up to 30 m from groundwater level after drilling a borehole. The ground heat exchanger has a structure in which several pipes are inserted into the borehole. In order to examine the characteristics of the Jeju-type GHX, tests were conducted on ground heat exchangers installed in four places on Jeju Island (Pyoseon, Jeju, Namwon, and Hallym). As a result of the analysis of the Jeju-type ground heat exchanger, the ground circulating water temperature stabilized according to the heat injection, depending on the installed location, and was formed within one to three hours. The ground heat exchanger capacity in Hallym was highest at 73.4 kW (cooling) and 82.8 kW (heating), and the Jeju-type calculation was lowest at 34.1 kW (cooling) and 23.3 kW (heating).

Evaluation of Ground Thermal Conductivity by Performing In-Situ Thermal Response test (TRT) and CFD Back-Analysis (현장 열응답 시험(TRT)과 CFD 역해석을 통한 지반의 열전도도 평가)

  • Park, Moonseo;Lee, Chulho;Park, Sangwoo;Sohn, Byonghu;Choi, Hangseok
    • Journal of the Korean Geotechnical Society
    • /
    • v.28 no.12
    • /
    • pp.5-15
    • /
    • 2012
  • In this study, a series of CFD (Computational Fluid Dynamics) numerical analyses were performed in order to evaluate the thermal performance of six full-scale closed-loop vertical ground heat exchangers constructed in a test bed located in Wonju. The circulation HDPE pipe, borehole and surrounding ground formation were modeled using FLUENT, a finite-volume method (FVM) program, for analyzing the heat transfer process of the system. Two user-defined functions (UDFs) accounting for the difference in the temperatures of the circulating inflow and outflow fluid and the variation of the surrounding ground temperature with depth were adopted in the FLUENT model. The relevant thermal properties of materials measured in laboratory were used in the numerical analyses to compare the thermal efficiency of various types of the heat exchangers installed in the test bed. The simulation results provide a verification for the in-situ thermal response test (TRT) data. The CFD numerical back-analysis with the ground thermal conductivity of 4 W/mK yielded better agreement with the in-situ thermal response tests than with the ground thermal conductivity of 3 W/mK.

Evaluation of Effective Thermal Conductivity of Closed-loop Vertical Ground Heat Exchanger (수직 밀폐형 지중 열교환기의 현장시공 및 유효열전도도 평가)

  • Lee, Chul-Ho;Park, Moon-Seo;Kwak, Tae-Hoon;Choi, Hang-Seok
    • 한국방재학회:학술대회논문집
    • /
    • 2010.02a
    • /
    • pp.91.1-91.1
    • /
    • 2010
  • 본 연구에서는 수직 밀폐형 지중 열교환기를 현장 시험시공하고 현장 열응답 시험을 수행하여 보어홀과 지반의 유효열전도도를 측정하였다. 뒤채움용 그라우트재는 벤토나이트와 시멘트가 고려되었으며 첨가제로는 천연규사와 흑연을 사용하고, 지중 열교환기 파이프 단면은 일반적으로 시공되는 U-loop 파이프 단면과 파이프 사이의 열간섭 효과를 최소화 한 3공형 파이프 단면이 착용되었다. 시멘트-천연규사 그라우트재가 벤토나이트-천연규사 그라우트재 보다 큰 유효열전도도를 보이고 흑연을 첨가한 그라우트는 시멘트와 벤토나이트 모두에서 천연규사만 첨가하였을 때 보다 유효열전도도가 높게 나타났다. 3공형 파이프 단면의 경우 단면에 따른 영향을 비교하기 위해 그라우트는 시멘트-천연규사와 벤토나이트-천연규사를 사용하였으며 유효 열전도도 측정결과 각각 3.65 W/mK, 3.40 W/mK으로 일반 U-loop 파이프 단면을 사용하였을 때 보다 높게 나타났다.

  • PDF