The cause analysis of explosion on junction termination of 345kV cable (345 kV 케이블 종단접속부에서의 폭발사고 원인분석)

  • Shong, Kil-Mok;Bang, Sun-Bae;Kim, Chong-Min;Kim, Young-Seok;Choi, Myeong-Il
    • Congress of the korean instutite of fire investigation
    • /
    • 2010.12a
    • /
    • pp.63-79
    • /
    • 2010
  • It is found to the arc trace on the junction termination of 345kV cable. According to the analysis of the cable material is judged to be good. Manufacturing and design problems are not considered. In construction defects, it was estimated to the low level of insulation oil. In the majority of the arc trace appeared XLPE is found. However, there is no Soots mark, yellow band has not been confirmed, not associated with a radial arc of the spider leg is not evidence. In other opinions, void, contamination or jut are not found on the inside of XLPE. Thus, by the attachment of the impurities in surface of XLPE insulation is judged to the breakdown.