• Title/Summary/Keyword: 마찰 댐퍼

Search Result 31, Processing Time 0.014 seconds

The Analysis of Correlation Major System Factors with the Performance of Smoke Control Systems Using Pressure Differentials (차압제연설비의 성능과 관련된 시스템 및 환경 변수와의 상관성 분석)

  • Yeo, Yong-Ju;Kim, Hak-Jung;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.97-105
    • /
    • 2010
  • The smoke control systems using pressure differentials are already well known as the most reliable method to prevent the smoke infiltration into the emergency stairs or safe spaces. However, it is true that many problems are domestically pointed out due to the insufficient understanding and technology on the smoke control systems using pressure differentials. In this regard, this work analyzed the effect of major factors for smoke control system using pressure differentials such as a duct area, opening area of air supply damper, improvement on open vestibules, stack effect and location of air supply. In conclusion, adequate pressure differentials can not be maintained in small duct because the smaller duct area have the large friction loss. Especially, It is confirmed that the major factor for deterioration of smoke control system performance is stack effect that makes pressure differentials smaller in the lower floors.