• Title/Summary/Keyword: 루프 히트파이프

Search Result 35, Processing Time 0.026 seconds

Development of a High Performance Bubble Jet Loop Heat Pipe Using the Enhanced Nucleate Boiling Surface in Evaporating Section (핵비등 촉진 전열면 증발부를 이용한 고성능 Bubble Jet Loop Heat Pipe 개발)

  • Kim, Jong-Soo;Shin, Jong-Seok
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.39 no.4
    • /
    • pp.363-367
    • /
    • 2015
  • In this study, a high performance Bubble Jet Loop Heat Pipe (BJLHP) was developed using the enhanced nucleate boiling surfaces in an evaporating section. A sintered tube and GEWA-T(Wieland) tube were used enhance nucleate boiling. The thermal performance of these BJLHP was compared with the conventional smooth tube BJLHP with an effective thermal conductivity. This experiment was conducted under the following conditions : working fluid, charging ratio and input power of R-141b, 50%vol., 75W and 100W, respectively. As a result, the effective thermal conductivity of BJLHP with a sintered tube in the evaporating section was 300% higher than the smooth tube BJLHP.

A Study on the Operating Characteristics by Counter Flow and Parallel Flow in Separate Heat Pipe Exchanger (분리형 히트파이프식 열교환기에서 향류 및 병류유동에 따른 가동특성에 관한 연구)

  • 이기우;장기창;유성연
    • Journal of Energy Engineering
    • /
    • v.7 no.1
    • /
    • pp.44-56
    • /
    • 1998
  • Separate heat pipe exchanger is considered as the high thermal transportation equipment, because evaporator and condenser are separately positioned in the long distance. Its characteristics are that the working fluid is circulated naturally by the position height of two exchangers. But the operating characteristics are restricted by the temperature of hot and cold fluid, flow pattern and diameter of vapor line, etc. in this study, the vapor pressure and the minimum height of two exchangers are studied about the factors restricting the operating characteristics.

  • PDF

Cooling Technique for Electronic Equipments using a small scale CPL heat pipe (소형 CPL 히트파이프를 이용한 전자장치 냉각 기술)

  • Kang, Sarng-Woo;Lee, Yoon-Pyo
    • Proceedings of the KSME Conference
    • /
    • 2004.11a
    • /
    • pp.1241-1246
    • /
    • 2004
  • The heat flux on a chip is rapidly increasing with decreasing the size of one. It is necessary to properly cool the high heat flux chip. One of the promising cooling methods is to apply CPL heat pipes with porous materials, for example PVA, polyethylene, and powder sintered metal plate and with microchannels in the evaporator. A small scale CPL heat pipe with PVA as wick was designed and manufactured. Since the height difference between the evaporator and the condenser is a crucial parameter in the CPL heat pipes, the performance of the heat pipes depending on the parameter was investigated. The parameter is higher the performance is better. However, the improvement rate of the performance does not increase the increase rate of the height. In addition to, the parameter effect depending on heat input was investigated.

  • PDF

A Study on the Miniature Loop Heat Pipe with Non-inverted Meniscus type Capillary Structure (Non-inverted Meniscus식 모세관 구조물을 이용한 소형 루프히트파이프에 관한 실험적 연구)

  • Chung, Won-Bok;Park, Soo-Yong;Doctarau, Viachaslau-V.
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2142-2147
    • /
    • 2007
  • Experimental study was conducted to evaluate the performance of a miniature loop heat pipe (MLHP) with non-inverted meniscus type capillary structure. All parts of MLHP in this study were made of copper including the capillary structure and the distilled water was used as a working fluid of MLHP. The outer diameter of evaporator was 9 mm and its length was 119 mm. The effective pore size of the capillary structure was 30 micron and its porosity was 60%. The vapor transport line, the liquid transport line and the condenser were consisted of single 4.0 mm copper tube. The distance between the evaporator and the condenser region was 200 mm and the length of the loop was 969 mm. This MLHP was operated successfully at any orientation but the gravity highly influenced the thermal performance of the MLHP. The maximum thermal load was 130 watts at the bottom heat mode and the 20 watts at the top heat mode.

  • PDF

Operating Characteristics of a Sintered-Metal Wick/Methanol Loop Heat Pipe Having a Bypass Line (소결금속 윅과 메탄올을 사용하며 바이패스라인이 부착된 루프히트파이프의 작동 특성)

  • Boo, Joon-Hong;Jung, Eui-Guk
    • Proceedings of the KSME Conference
    • /
    • 2007.05b
    • /
    • pp.2130-2135
    • /
    • 2007
  • Operating characteristics of a loop heat pipe (LHP) having a bypass line was investigated experimentally. The LHP had a sintered metal wick as a capillary structure and methanol as a working fluid. The sintered metal wick was made of stainless steel of which the average pore size was 5 ${\mu}m$and porosity of 47%. A bypass line of a small diameter was attached between the vapor escape passage and the liquid reservoir. The dimension of the flat evaporator was $50(L){\times}40(W){\times}30(H)$ mm and that of the condenser was $50(L){\times}40(W){\times}11(H)$ mm. Wall and pipe material of the LHP was stainless steel and heating area was 35(W) mm${\times}$35(L) mm. The inner diameters of vapor and liquid transport lines were 4.0 mm and 2.0 mm, and the lengths of the two lines were both 0.5 m. The LHP was tested for three different tilt angles of horizontal, favorite tilt, and adverse tilt. The thermal load range was up to 290 W at the condenser above evaporation position. Furthermore, the effect of a bypass line on the start-up transient as well as steady-state operation was presented and discussed.

  • PDF

Thermal Performance of a Small-scale Loop Heat Pipe for Terrestrial Application (지상용 소형 루프히트파이프 성능에 관한 연구)

  • Chung, Won-Bok;Boo, Joon-Hong
    • Proceedings of the KSME Conference
    • /
    • 2004.11a
    • /
    • pp.1052-1057
    • /
    • 2004
  • A small-scale loop heat pipe with polypropylene wick was fabricated and tested for its thermal performance. The container and tubing of the system was made of stainless steel and several working fluids were used to see the difference in performance including methanol, ethanol, acetone, R134a, and water. The heating area was 35 mm ${\times}$ 35 mm and there were nine axial grooves in the evaporator to provide a vapor passage. The pore size of the polypropylene wick inside the evaporator was varied from 0.5 m to 25 m. The size of condenser was 40 mm (W) ${\times}$ 50 mm (L) in which ten coolant paths were provided. The inner diameter of liquid and vapor transport lines were 2.0 mm and 4.0 mm, respectively and the length of which were 0.5 m. The PP wick LHP was operated with methanol, acetone, and ethanol normally. R134a was not compatible with PP wick and water was unsuitable within operating limit of $100^{\circ}C$. The minimum thermal load of 10 W (0.8 W/cm2) and maximum thermal load of 80 W (6.5 W/cm2) were achieved using methanol as working fluid with the condenser temperature of $20^{\circ}C$ with horizontal position.

  • PDF

A Study on the Heat Transfer Characteristics of Loop Type Capillary Heat Pipe (루프형 세관 히트 파이프의 열전달특성에 관한 연구)

  • Yoon, Suck-Hun;Choi, Jae-Hyuck
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.3
    • /
    • pp.346-353
    • /
    • 2000
  • In this paper, heat transfer characteristics of a loop type capillary heat pipe were experimentally investigated for the effect of several fill charge ratios of working fluid and heat loads. This type of heat pipe consists of a heating section, a cooling section and an adiabatic section. The heat pipe used has a 0.002m internal diameter, a 0.34m length in one turn and consists of 19 turns. Heating and cooling sections each have a length of 70mm. Experiments were performed to measure the temperature distributions and the pressure variation of the heat pipe. Heat transfer performance, effective thermal conductivity, boiling heat transfer and condensation heat transfer coefficients were calculated for various operating conditions of heat pipe and it was found that heat transfer characteristics of this type heat pipe were very excellent. As shown by this experimental study, this type of heat pipe operates by oscillatory flow caused by pressure and temperature oscillations.

A comparative study on the flow patterns in closed loop pulsating heat pipe charged with various working fluids (다양한 작동유체로 충전된 폐쇄 루프 맥동 히트파이프 내부 유동패턴 비교)

  • Kang, Seok Gu;Kim, Seong Keun;Ahmad, Hibal;Jung, Sung Yong
    • Journal of the Korean Society of Visualization
    • /
    • v.17 no.3
    • /
    • pp.52-58
    • /
    • 2019
  • Thermal performance and flow patterns inside the closed loop pulsating heat pipe (CLPHP) were experimentally investigated. For investigating the effect of working fluids, CLPHP was filled with various working fluids including methanol, acetone and ethanol. The thermal resistance was calculated by temperatures in evaporator and condenser and flow patterns were visualized by a digital camera. The thermal resistances for all fluids were decreased as the heat increases. Flow patterns change from static slug to elongated slug flows, bulk circulation and annular flows as the heat increases. Dry-out occurs after annular flows. For reasonable comparison of thermal performances, normalized CHF, Kutateladze number (Ku), was compared. Even though ethanol has smallest CHF, Ku of ethanol is similar with that of methanol. In addition, acetone has the highest Ku that means CLPHP with acetone provides the higher thermal performance compared with CLPHP with other fluids.