• 제목/요약/키워드: 로고우스키코일

검색결과 8건 처리시간 0.023초

로고우스키코일을 이용한 과도전류의 측정 (Measurement of Transient Current by using the Rogowski Coil)

  • 이복희;길경석;정승수;정상진
    • 대한전기학회논문지
    • /
    • 제43권7호
    • /
    • pp.1206-1213
    • /
    • 1994
  • This paper presents the operation principle and design rule of the Rogowski coil which can measure the transient current and describes the calibration and application experimental results for performance evaluation. It is obtained that the response curves of the Robowski coil with the turns of 300 and the passive integrator to sinusoidal input give a good linearity up to the frequency of 500 [kHz] and the current measurement system gaving the Rogowski coil is the frequency bandwidth of 40 [Hz]~700 [kHz]. As an application experiment for the fabricated modeling power transmission line, the impulse current, which limitates the direct lightning return stroke to overhead ground wire, is measured by the Rogowski coil and its fast Fourier transformation is carried out. The equivalent circuit of the Rogowski coil considering the stray capacitances is proposed, and the theoretical analysis is in good agreement with the measurement results. Also, it is found that for high frequency domain the stray capacitance such as a distributed capacitance to the shield and the capacitance between windings of coil should be considered in designing the Rogowski coils since the resonance originates from the stray capacitance and the self-inductance of the Rogowski coil.

  • PDF

전류측정감도 개선을 위한 로고우스키 코일의 설계 (Design of Rogowski coil to improve of current measurement sensitivity)

  • 박정남;이청;장용무;강성화;임기조;나동희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집 Vol.14 No.1
    • /
    • pp.609-612
    • /
    • 2001
  • Rogowski coil is made having no ferromagnetic material in a core. So the coil cannot be driven into saturation. This result in that Rogowski coils may be calibrated at relatively low currents. and used with confidence at very high currents. However the lowest level of current that can be measured is limited by the sensitivity of the voltage measuring instrument and system noise. Therefore. geometrical effects were investigated in order to measure high sensitivity of low level current and the significant source of error was examined as well. In the results, the source of error was associated with coil designs. i.e. shape and uniformity of coil and a geometrical location of current source inside and outside of the Rogowski coil.

  • PDF

저전류 영역에서 로고우스키 코일 특성 (Characteristics of Rogowski coil at Low Cutrrent Region)

  • 박정남;이강원;이청;김길수;박영국;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.47-50
    • /
    • 2001
  • Conventionally, air-cored Rogowski coil was designed for use as high alternating and transient current sensor without saturation caused by ferromagnetic material in its core. This paper investigated that Rogowski coil can be applied to low current measurement in 60Hz power line. Measured parameters R, L of coil were compared with theoretically calculated values. Output voltages crossed by Rogowski coil have shown some linearity according to input current(tens to thousands of amperes) passing through it. And also shielding effect for external noises was investigated for three cases.

  • PDF

전류측정감도 개선을 위한 로고우스키 코일의 설계 (Design of Rogowski coil to improve of current measurement sensitivity)

  • 박정남;이청;장용무;강성화;임기조;나동희
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 추계학술대회 논문집
    • /
    • pp.609-612
    • /
    • 2001
  • Rogowski coil is made having no ferromagnetic material in a core. So the coil cannot be driven into saturation. This result in that Rogowski coils may be calibrated at relatively low currents, and used with confidence at very high currents. However the lowest level of current that can be measured is limited by the sensitivity of the voltage measuring instrument and system noise. Therefore, geometrical effects were investigated in order to measure high sensitivity of low level current and the significant source of error wa examined as well. n the results, the source of error was associated with coil designs, i.e. shape and uniformity of coil and a geometrical location of current source inside and outside of the Rogowski coil.

  • PDF

외부 코로나 노이즈를 제거한 내부 부분방전 측정기법 (An internal partial discharge measurement method excepted an external corona noise)

  • 권동진;진상범;곽희로
    • 조명전기설비학회논문지
    • /
    • 제15권1호
    • /
    • pp.44-50
    • /
    • 2001
  • 현재까지 운전중인 변압기에 전기적인 부분방전 측정기법을 적용하기 위한 가장 큰 문제점은 외부 코로나 노이즈를 제거하는 것이다. 본 논문에서는 외부 코로나 노이즈를 제거하고 변압기 내부의 결함에 의한 부분방전 신호만을 측정하는 기법에 대하여 연구하였다. 현장에서 운전중인 변압기에서의 부분방전과 코로나 노이즈의 발생 형태를 모의하기 위하여 모의 변압기 내에 침-평판 전극을 이용하여 변압기 내부 부분방전을 발생시켰으며, 동시에 변압기 외부의 공기 중에 봉-구 전극을 이용하여 외부 코로나 노이즈를 발생시켰다. 변압기 접지선에 설치한 로고우스키 코일에는 변압기의 내부 결함에 의해 발생되는 부분방전 신호와 외부 코로나 노이즈가 동시에 측정되었다. 변압기 외부에 안테나 센서를 이용하여 외부 코로나 노이즈를 별도로 측정하여, 코로우스키 코일에서 측정된 신호에서 코로나 노이즈를 제거한 결과, 변압기 내부의 부분방전에 의한 신호만을 효과적으로 검출할 수 있었다.

  • PDF

부분방전 검출을 위한 저, 고주파용 센서 해석 및 설계 (The Design of a Sensor for Measuring Partial Discharge Signals in Rotating Machines)

  • 허창근;김용주;강동식;정현교
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 한국정보통신설비학회 2004년도 하계학술대회
    • /
    • pp.6-10
    • /
    • 2004
  • 회전기기의 운전 상태에서 on-line 부분 방전시험은 고정자 권선의 절연상태를 검사, 평가 할 수 있는 중요한 수단으로서 이러한 부분방전시험을 통하여 회전기기 시스템의 사고예방을 위한 진단을 할 수 있다. 기존의 비접촉식 센서인 SSC는 부분방전 측정을 위하여 권선의 웨지 아래에 설치하는 방식으로 개발되어 [1], 설치가 불편하고 Global VPI 방식으로 제작된 소형 회전기에는 설치할 수 없는 단점이 있다. 본 논문에서는 소형 회전기에 사용가능한 저, 고주파용 부분방전 센서를 제안하였다. 웨지 위에 설치 가능한 SSC 형태의 마이크로스트립 센서 및 전송선로 이론을 이용한 2선 평행 전송선로 센서는 값이 싸고 소형 회전기에 설치할 수 있을 정도의 크기를 지니며, 기본적으로 센서의 구조가 고주파 웨이브가이드로서 고주파용 센서로 적합하다. 또한 저주파 신호를 검출하기 위한 센서로 로고우스키 코일 형태의 U 타입 센서는 와전류를 검출하는 센서로서 슬롯 외부에 설치 되어야 한다. 이러한 U 타입 센서와 마이크로스트립 센서 또는 2선 평행 전송선로를 동시에 설치할 경우 저, 고주파를 효과적으로 검출할 수 있다.

  • PDF

몰드변압기의 보이드 결함 크기 판별 (Identification of Void Diameters for Cast-Resin Transformers)

  • 정기우;김성욱
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국정보통신학회 2022년도 추계학술대회
    • /
    • pp.570-573
    • /
    • 2022
  • 본 논문에서는 신경망 모델을 적용한 몰드변압기의 보이드 결함 크기 판별에 관한 연구를 수행하였다. PCB 기반의 로고우스키 코일형 부분방전 센서를 제작하여 부분방전 신호를 측정하였고, 보이드에 의한 부분방전 결함을 모의하기 위한 PD 전극계를 제작하였다. 또한 보이드는 원통형 모양의 알루미늄 틀을 제작하여 에폭시가 경화되는 과정에서 실린지를 삽입하고 공기를 주입하여 서로다른 직경을 가지는 4개의 시편을 제작하였다. 보이드 결함 크기 판별을 위해 부분방전 전하량, 방전 펄스 수, 위상 분포의 부분방전 특성 파라미터를 추출하여 Labview 기반의 VI (Virtual Instrument)로 역전파 알고리즘을 설계하였다. 실험 결과로부터 제작된 알고리즘은 90%이상의 판별률로 결함의 직경크기를 구분할 수 있었다. 본 연구의 결과는 현장에서 PD 측정 시 몰드변압기의 유지보수 및 절연물 교체의 근거 자료로 활용될 수 있을 것으로 판단된다.

  • PDF

가공배전선로의 전력설비 감시를 위한 유비쿼터스 센서 (Ubiquitous Sensors for Supervision of Power Facilities in Overhead Power Distribution Lines)

  • 길경석;박대원;김일권;최수연;박찬용
    • 조명전기설비학회논문지
    • /
    • 제21권10호
    • /
    • pp.59-65
    • /
    • 2007
  • 최근 유비쿼터스 센서네트워크 기술이 전력설비관리에 적용되어 오고 있다. 본 연구에서는 가공배전선로에서 전력용변압기와 피뢰기를 관리할 수 있는 유비쿼터스 센서의 설계 및 제작에 대해 기술하였다. 이 센서들은 8-[bit] 마이크로프로세서, IEEE 802.15.4기반 무선통신모듈과 주변 전자회로로 구성되어 있다. 변압기의 부하 및 서지전류 측정에는 1000[A]까지 포화되지 않고 선형성을 유지할 수 있도록 공심형 로고우스키 코일을 제작하여 적용하였다. 피뢰기를 흐르는 $50[{\mu}A]{\sim}1[mA]$의 미소누설전류를 측정하기 위하여 180[Hz]에서 $10^5$의 고투자율을 갖는 영상변류기를 사용하였으며, 피뢰기 감시모듈의 -3[dB] 주파수 대역은 12[Hz]에서 1.24[kHz]이다.