• 제목/요약/키워드: 다관형

검색결과 69건 처리시간 0.025초

다양한 형상의 판형 휜을 장착한 원통다관형 열교환기의 열성능 해석 (Thermal Performance Analysis of a Shell-and-Tube Heat Exchanger with Plate Fins of Various Shape)

  • 신지영;손영석
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제28권4호
    • /
    • pp.648-656
    • /
    • 2004
  • In this study, a highly efficient shell-and-tube heat exchanger with plate fins is considered to improve thermal performance of the conventional shell-and-tube heat exchanger. This type of shell-and-tube heat exchanger with plate fins of various shape is simulated three-dimensionally using a commercial thermal-fluid analysis code. CFX4.4. The effect of the shape of the plate fin on heat transfer characteristics is also investigated by the simulation. Plate fins of four different shapes. plane, plane-slit. wave. and wave-slit fins, are considered. The flow fields, pressure drop and heat transfer characteristics in the heat exchanger are calculated. It is proved that the shell-and-tube heat exchanger with plate fins is superior to the conventional shell-and-tube heat exchanger without plate fins in terms of heat transfer. The shape of the plate fin is important in the performance of a heat exchanger such as heat transfer and pressure drop.

Shell & Tube 열교환기 Shell 측 열전달 및 유동에 대한 수치해석 (NUMERICAL ANALYSIS ON THE HEAT TRANSFER AND FLOW IN THE SHELL AND TUBE HEAT EXCHANGER)

  • 이상혁;이명성;허남건
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2007년도 춘계 학술대회논문집
    • /
    • pp.149-152
    • /
    • 2007
  • The numerical simulations on the heat transfer and flow field were carried out for the improvement of the performance of the shell and tube heat exchanger. The steady incompressible 3-D Navier-Stokes solution is obtained with the actual operational condition and geometry of the heat exchanger. The present geometry of the heat exchanger causes poor heat transfer since the air inside shell dose not flow through the tube bundle, but around it. The enhancement of the heat transfer can be achieved by the variation of the design factor like the sealing strip located on the top/bottom and middle of the baffle.

  • PDF

파형관 튜브가 있는 순환유동층 원통다관형 열교환기 내의 유체유동 (Fluid Flow in the Fluidized Bed Shell and Tube Type Heat Exchanger with Corrugated Tubes)

  • 안수환;이병창;배성택
    • 설비공학논문집
    • /
    • 제15권5호
    • /
    • pp.406-412
    • /
    • 2003
  • An experimental study was carried on the characteristics of fluid flow and heat transfer in a fluidized bed shell-and-tube type heat exchanger with corrugated tubes. Seven different solid particles having same volume were circulated in the tubes. The effects of various parameters such as water flow rates, particle geometries and materials, and geometries of corrugated tubes on relative velocities and drag coefficients were investigated. The present work showed that the drag force coefficients of particles in the corrugated tubes were usually lower than those in the smooth tubes, meanwhile the relative velocities between particles and water in the corrugated tubes were little higher than those in the smooth tubes except the glass.

방향족 도입에 의한 자외선 경화형 프리즘시트의 휘도 개전 (Improvement of Brightness in UV Curing Type Prism Sheet by Using Aromatic Groups)

  • 김동열;김형일
    • 폴리머
    • /
    • 제33권5호
    • /
    • pp.413-419
    • /
    • 2009
  • 프리즘 시트의 프리즘 층 물질의 굴절률을 증가시킬수록 휘도가 향상되어 LCD 백라이트 유닛의 효율이 향상되었다. 프리즘 층의 굴절률을 증가시키기 위해서 방향족을 포함하고 있는 고굴절 물질과 다관능성 반응물을 혼합하여 자외선 경화형 수지를 제조하였다. 9,9-Bis [4-(2-acryloyloxyethoxy)phenyl] fluorene을 반응시켜 프리즘층의 도막 굴절률을 1.58까지 증가시켰고 백라이트의 휘도를 향상시킬 수 있었다. 백라이트 유닛에 사용되는 광원에 장기간 노출될 경우 프리즘 시트에 황변현상이 발생하게 되어 휘도가 감소되므로 자외선 안정제로 hindered amine light stabilizer를 사용하여 프리즘 시트의 내황변성을 크게 향상시켰다.

수직형 순환유동층 열교환기에서의 유체유동과 온도장의 수치해석 (Numerical analysis of fluid flow and thermal fields in the vertical fluidized bed heat exchanger)

  • 이병창;강호근;이명성;안수환
    • 동력기계공학회지
    • /
    • 제16권4호
    • /
    • pp.24-29
    • /
    • 2012
  • The numerical analysis by using CFX 11.0 commercial code was done for prediction of fluid flow and thermal field in the vertical heat exchanger. The present experimental studies were also conducted to investigate the effects of circulating solid particles on the fluid flow and temperatures in the fluidized bed vertical shell and tube type heat exchanger with counterflow, at which the solid particles of glasses (3 $mm{\Phi}$) were used in the fluidized bed with a smooth tube. The effect of circulation on the distance(L) of tube inlet and baffle plate was also examined. The present experimental and numerical results showed that the particles in the distance (Ds) of 15 mm showed a more efficient circulation without stacked the space and the LMTD(Log Mean Temperature Difference) in the fluidized bed type was much lower than that in the typical type shell and tube heat exchanger.

분산형 소형 연료전지용 1KW급 열교환기 설계 (Heat Exchanger Design For The Individually Allocated Fuel Cell For 1kw Power generation)

  • 이택홍;박태성;김태완;노재현;강영진
    • 한국수소및신에너지학회논문집
    • /
    • 제25권1호
    • /
    • pp.39-46
    • /
    • 2014
  • Our lab designs a heat exchangers for hydrogen gas. Coolant is water, thus it is very difficult to determine heat transfer parameters in this gas-liquid system. Repeated experiments gives overdesign value 6.06%, overall heat transfer coefficient 36.32 ($kcal/m^2-hr-^{\circ}C$) for Hydrogen. Theoretically determined overall heat transfer coefficient is 38.44 ($kcal/m^2-hr-^{\circ}C$). Our lab simulated this system and overdesign 30.4% shows good match with this experiment by HTRI. These parameters are in same range with literature.

공작기계 절삭유 냉각용 오일쿨러 설계 자동화 (Oil Cooler Design Automation on the Cooling of Machine Tool Cutting Oil)

  • 권혁홍
    • 한국생산제조학회지
    • /
    • 제8권1호
    • /
    • pp.89-99
    • /
    • 1999
  • The automatic design of shell & tube type oil cooler can be used in real industrial environments. Since the automatic design system is intended to be used in small companies, it is designed to be operated well under environments of CAD package in the personal computer. It has adopted GUI in design system, and has employed DCl language. Design parameters to be considered in the design stage of shell and tube type oil cooler are type of oil cooler, outer diameter, thickness, length of tube, tube arrangement, tube pitch, flow rate, inlet and outlet temperature, physical properties, premissive pressure loss on both sides, type of baffle plate, baffle plate cutting ratio, clearance between baffle plate outer diameter and shell inner diameter and clearance between baffle plate holes. As a result, the automatic design system of shell & tube type oil cooler is constructed by the environment of CAD software using LISP. We have built database of design data for various kinds of shell & tube type oil coolers. The automatic design system have been assessed and compared with existing specification of design. Good agreement with Handbook of heat exchanger and design dta of real industrial environments has been found.

  • PDF

다관원통형 열교환기의 파울링 해석기법 개발 연구 (A Study on the Development of Fouling Analysis Technique for Shell-and-Tube Heat Exchangers)

  • 황경모;진태은
    • 대한기계학회논문집B
    • /
    • 제28권2호
    • /
    • pp.167-173
    • /
    • 2004
  • Fouling of heat exchangers is generated by water-borne deposits, commonly known as foulants including particulate matter from the air, migrated corrosion produces; silt, clays, and sand suspended in water; organic contaminants; and boron based deposits in plants. The fouling is known to interfere with normal flow characteristics and reduce thermal efficiencies of heat exchangers. This paper describes the fouling analysis technique developed in this study which can analyze the thermal performance for heat exchangers and estimate the future fouling variations. To develop the fouling analysis technique fur heat exchangers, fouling factor was introduced based on the ASME O&M codes and TEMA standards. For the purpose or verifying the fouling analysis technique, the routing analyses were performed for four heat exchangers in several nuclear power plants; two residual heat removal heat exchangers of the residual heat removal system and two component cooling water heat exchangers of the component cooling water system.

바이오가스용 소형 열교환기 연구 (Compact Heat Exchanger Design for Biogas Application)

  • 이택홍;김태완;박태성;강영진;노재현
    • 한국수소및신에너지학회논문집
    • /
    • 제25권2호
    • /
    • pp.183-190
    • /
    • 2014
  • Our lab designs a heat exchangers for air and carbondioxide gas. Coolant is water, thus it is very difficult to determine heat transfer parameters in this gas-liquid system. Repeated experiments gives overdesign value 35%, overall heat transfer coefficient $33.8(kcal/m2-hr-^{\circ}C)$ for carbondioxide. Another series of experiments determine overdesign 18.7%, overall heat transfer coefficient $21.4(kcal/m2-hr-^{\circ}C)$ for Air. These parameters are in same range of literature. Overdesign is increasing as tube length increases, also increases as wall thickness of heat exchanger increases. To get proper fluid linear velocity in heat exchanger, we change the diameter of tube and finally we can have optimum fluid linear velocity in the heat exchanger.

다관원통형 열교환기의 파울링 및 관막음 여유 평가법 (A Study on the Development of Fouling and Plugging Margin Evaluation Methods for Shell-and-Tube Heat Exchangers)

  • 황경모;진태은
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2003년도 추계학술대회
    • /
    • pp.55-60
    • /
    • 2003
  • As operating time of heat exchangers progresses, fouling generated by water-borne deposits increases and thermal performance decreases. The fouling is known to interfere with normal flow characteristics and reduce thermal efficiencies of heat exchangers. The heat exchangers of nuclear power plants have been analyzed in terms of the heat flux and heat transfer coefficient at test conditions based on the ASME OM-S/G-Part 2 as a means of heat exchanger management. It is hard to estimate the heat performance trend and to establish the future management plan. This paper describes the fouling evaluation method which can evaluate the thermal performance for heat exchangers and estimate the future fouling variations and the plugging margin evaluation method which can reflect the current fouling level developed in this study. To develop the fouling and plugging margin evaluation methods for heat exchangers, fouling factor was introduced based on the ASME O&M codes and TEMA standards. For the purpose of verifying the two evaluation methods, the fouling and plugging margin evaluations were performed for a component cooling heat exchanger in a nuclear power plant.

  • PDF