A Study on Cooling Characteristics of Ground Source Heat Pump with Variation of Water Switching and Refrigerant Switching Methods (수절환 및 냉매절환방식에 따른 지열히트펌프의 냉방특성에 관한 연구)

  • Cha, Dong-An;Kwon, Oh-Kyung;Park, Cha-Sik
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.8
    • /
    • pp.605-611
    • /
    • 2012
  • The objective of this study is to investigate the influence of the cooling performance for a water-to-water 10 RT ground source heat pump by using the water switching and refrigerant switching method. The test of water-to-water ground source heat pump was measured by varying the compressor speed, load side inlet temperature, and ground heat source side temperature. The cooling capacity and refrigerant mass flow rate of the heat pump increased with increasing ground heat source temperature. But COP of the heat pump decreased with increasing ground heat source temperature. As a result, the water switching method with counter flow, compared to a refrigerant switching method, improves the cooling capacity and COP by approximately 6~9% in average, respectively.

A Study on Heating Characteristics of Ground Source Heat Pump with Variation of Heat Exchange Methods (열교환방식에 따른 지열히트펌프의 난방특성에 관한 연구)

  • Cha, Dong-An;Kwon, Oh-Kyung;Park, Cha-Sik
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.8 no.2
    • /
    • pp.9-15
    • /
    • 2012
  • The objective of this study is to investigate the influence on the heating performance for a water-to-water 10RT ground source heat pump by using the water switching and refrigerant switching method. The test of water-to-water ground source heat pump was measured by varying the compressor speed, load side inlet temperature, and ground heat source side temperature. The heating capacity and COP of the heat pump increased with increasing ground heat source temperature. As a result, compared to a refrigerant switching method, the water switching method with counter flow improves the heating capacity and COP by approximately 5% in average, respectively.