Pool boiling heat transfer coefficients of alternative refrigerants on low fin tubes (낮은 핀관에서 대체냉매의 풀비등 열전달계수)

  • 송길홍;이준강;정동수;김종보
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.4
    • /
    • pp.411-422
    • /
    • 1998
  • In this study, experiments were carried out to provide nucleate pool boiling heat transfer data for a plain tube and 4 different low fin tubes employing 2 refrigerant mixtures of R410A, R407C, and 12 pure fluids. Low fin tubes were machined on a 19.05mm nominal outside diameter copper block according to the manufacturer's low fin tube specifications. Cartridge heaters were used to generate uniform heat flux on the tubes. For all refrigerants, heat flux varied from 10㎾/$\m^2$ to 80㎾/$\m^2$. It is found that heat transfer coefficients(HTCs) of high vapor pressure refrigerants are usually higher than those of low pressure fluids. On the other hand, the fin effect was more prominent with low pressure refrigerants than with high pressure ones. Optimum fin density as well as the increase in heat transfer coefficient with the increase in fin density were found to be strongly fluid dependent. HTCs of Rl23, a low pressure alternative refrigerant, were similar to those of Rll while HTCs of R134a, an intermediate pressure alternative refrigerant, were roughly 20% higher than those of Rl2. Finally, HTCs of R32, R125, R143a, and R410A were all higher than those of R22 by 30~50%.

  • PDF

Pool Boiling Heat Transfer Charcteristics of Low-Fin Tubes in CFC11, HCFC123 and HCFC141b (CFC11, HCFC123, HCFC141b 풀내에서 낮은 핀관의 비등 열전달특성)

  • 김주형;곽태희;김종보
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.9
    • /
    • pp.2316-2327
    • /
    • 1995
  • Experimental results from nucleate pool boiling heat transfer with various finned tubes in CFC11, HCF123 and HCFC141b are reported. One plain tube and four low fin tubes of various fin densities were tested in an attempt to find out the optimum fin density in the heat flux range of 10-60 kW/m$^{[-992]}$ at near atmospheric pressure. The results indicated that CFC11 showed the highest heat transfer coefficients. Its alternatives, HCFC123 and HCFC141b, showed 3-5% lower heat transfer coefficients than those of CFC11 at the same heat flux. As the fin density increases, so does the heat transfer surface area. Measured heat transfer coefficients, however, do not necessarily always increase as the fin density increases. This unique phenomenon seems to be caused by the coalescence of the bubblers that prevent the cool liquid from entering into the fin valleys. For all the refrigerants tested, the optimum fin density yielding the highest performance was 28 fins per inch confirming the previous results by other researchers.

Condensation heat transfer coefficients of alternative refrigerants for CFC11, CFC12 and HCFC22 (CFC11, CFC12, HCFC22 대체냉매의 응축 열전달계수)

  • 정동수
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.28 no.5
    • /
    • pp.389-395
    • /
    • 1999
  • 냉동공조설비, 발전설비, 화학플랜트설비 등에 사용되는 응축기는 주로 증기가 관의 외부에서 응축을 하고 냉각수가 관 내부로 흐르는 쉘-튜브(shell and tube)형 태를 취하고 있다. 초기투자비용 및 운전비용을 줄이기 위해서는 응축기의 열교환 성능을 향상시키는 일이 필수적이며 이를 위해 코팅 표면(coated surfaces), 거친 표면(rough surfaces), 코일 튜브(coiled tubes), 선회 흐름장치(swirl flow), 전열면적을 넓힌 낮은 핀관과 3차원 형상을 갖는 열전달 촉진관의 사용이 제시되고 있다.

  • PDF

External Condensation Heat Transfer Coefficients of R245fa on Low Fin and Turbo-C Tubes (낮은 핀관과 Turbo-C 촉진관에서 R245fa의 외부 응축 열전달계수)

  • Shim, Yun-Bo;Park, Ki-Jung;Jung, Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.3
    • /
    • pp.167-175
    • /
    • 2009
  • In this study, condensation heat transfer coefficients(HTCs) of R22, R123, R134a and R245fa are measured on both 26fpi low fin and Turbo-C tubes. All data are taken at the vapor temperature of $39^{\circ}C$ with a wall subcooling of $3{\sim}8^{\circ}C$. Test results show that HTCs of the newly developed low vapor pressure alternative refrigerant, R245fa, are $7.8{\sim}9.2%$ and $10.3{\sim}18.6%$ higher than those of R123 for 26fpi low fin tube and Turbo-C tube respectively. For all refrigerants tested, HTCs of Turbo-C enhanced tube are higher than those of 26fpi low fin tube. For the low fin tube, Beatty and Katz's prediction equation yielded 20% deviation for all fluids. The heat transfer enhancement ratio of R245fa on the Turbo-C tube is $5.9{\sim}6.4$ while that of R123 is $5.7{\sim}5.9$. From the view point of environmental safety and condensation heat transfer, R245fa is a long term candidate to replace R123 currently used in centrifugal chillers.

Pool Boiling Heat Transfer Coefficient of R245fa on the Plain Tube and the Low Fin Tube (평활관과 낮은 핀관에서 R245fa의 풀 비등 열전달계수)

  • Park, Ki-Jung;Lee, Yo-Han;Lim, Byeong-Deok;Jung, Dong-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.23 no.3
    • /
    • pp.208-215
    • /
    • 2011
  • In this work, pool boiling heat transfer coefficients(HTCs) of R22, R123, R134a, and R245fa are measured on both horizontal plain and 26 fpi low fin tubes. The pool boiling temperature is maintained at $7^{\circ}C$ and heat flux is varied from 80 $kW/m^2$ to 10 $kW/m^2$ with an interval of 10 $kW/m^2$. Wall temperatures are measured directly by thermocouples inserted through holes of 0.5 mm diameter. Test results show that HTCs of high vapor pressure refrigerants are usually higher than those of low pressure fluids in both plain and low fin tubes. On a plain tube, HTCs of R245fa are 23.3% higher than those of R123 while on a 26 fpi low fin tube, HTCs of R245fa are 46.3% higher than those of R123. The fin effect is more prominent with low vapor pressure refrigerants than with high vapor pressure ones due to a sweeping effect.

Pool Boiling Heat Transfer Characteristics of R-l34a in Titanium Horizontal Plain and Low Finned Tubes (티타늄 평활관 및 전열촉진관에서 R-l34a의 관외측 풀비등 열전달 특성에 대한 연구)

  • Heo Jae-Hyeok;Yun Rin;Chung Jin-Taek;Moon Young-lune;Kim Yongchan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.29 no.7 s.238
    • /
    • pp.854-860
    • /
    • 2005
  • Pool boiling heat transfer characteristics of R-134a were investigated in titanium plain and low finned tubes. The diameter of test tube was 15.88 mm and the fin density was 33 fpi. Tests were conducted at saturation temperatures of $20^{\circ}C$ and $30^{\circ}C$. Heat fluxes varied from 5000 W/$m^2$ to 50,000 W/$m^2$ based on surface area of the plain tube. The pool boiling heat transfer coefficients of the titanium horizontal plain tube are lower than those of the copper plain tube by $8.2\%$. The boiling heat transfer coefficients of the low finned tube are averagely higher than those of the plain tubes by $34\%$. The average deviation of the Slipcevic correlation from the present data for the low finned tube is $20\%$.

Pool Boiling Heat Transfer Coefficients of New Refrigerants on Various Enhanced Tubes (열전달 촉진관에서 신냉매의 풀비등 열전달계수)

  • 박진석;김종곤;정동수;김영일
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.8
    • /
    • pp.710-719
    • /
    • 2001
  • Pool boiling heat transfer coefficients (HTCs) of HCFC123, HFC134a, HCFC22, HFC407C, HFC410A and HFC32 wre measured on a horizontal smooth tube, 26 fpi low fin tube, Turbo-B and Thermoexcel-E enhanced tubes. AN experimental apparatus was designed such that all tubes heated by cartridge heaters could be installed at the same time to save the refrigerant. Data were taken in the pool of $7^{\circ}C$ with the heat flux decreasing from 80 kW/$m^2\;to\;5kW/m^2$. Test results showed that HTCs of pure refrigerants and those of a azeotrope were greatly influenced by reduced pressure. HTCs of HFC407C were 21~25% lower than those of HCFC22 due to mass transfer resistance. For all refrigerants, enhanced tubes with sub-surface and sub-tunnels showed the largest heat transfer enhancement. Especially the largest heat enhancement was obtained for HCFC123 whose reduced pressure is the lowest among al the refrigerants tested. This indicates that either Turbo-B or Thermoexcel-E enhanced tube would be the best choice when used with a low vapor pressure refrigerant.

  • PDF

Condensation heat transfer characteristics of alternative refrigerants for CFC-11, CFC-12 for enhanced tubes (열전달 촉진관에서 CFC-11 및 CFC-12 대체냉매의 응축 열전달 특성 연구)

  • 조성준;황수민;정동수;김종보
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.5
    • /
    • pp.569-580
    • /
    • 1998
  • In this study, condensation heat transfer coefficients(HTCs) of a plain tube, low fin tube, and Turbo-C enhanced tube for CFC-11, HCFC-123, CFC-12, HFC-l34a are measured and compared against each other. All data are taken at the vapor temperature of 39$^{\circ}C$ with a wall subcooling temperature 3~8$^{\circ}C$. Test results show that HTCs of a low vapor pressure refrigerant, HFC-123, for a plain, low fin, and Turbo-C tubes are 10.5~20.5%, 8.2~12.2%, 16.5~19.2% lower than those of CFC-11, respectively. On the other hand, HTCs of a medium vapor refrigerant, HFC-l34a, for a plain, low fin, and Turbo-C tubes are 20.6~31.8%, 0.0~8.0%, 13.2~20.9% higher than those of CFC-12, respectively. For all refrigerants tested, HTCs of Turbo-C tube are the highest among the three tubes showing almost 8 times increase in HTCs as compared to those of a plain tube. Nusselt's prediction equation for a plain tube yielded 12% deviation for all plain tube data while Realty and Katz's prediction equation for a low fin tube yielded 20% deviation for all low tube data.

  • PDF

Experimental Study on Condensation Heat Transfer Characteristics of Special Heat Transfer Tubes (응축용 특수 전열관의 열전달 특성에 관한 연구)

  • 한규일;박종운;권영철;조동현
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.9
    • /
    • pp.827-835
    • /
    • 2001
  • In this study, condensation heat transfer characteristics were conducted with special heat transfer tubes of SH-C type. Experiments were carried out the saturated vapor temperature of 334K and the wall subcooling of 1.5-4.5K. The refrigerant was R-113 and the enhanced tubes used in the present study were SH-CDR, SH-CYR and SH-CHR. The experimental results showed that the condensation heat transfer coefficients of SH-C type tubes were about 23-66% higher than those of a low integral-fin tube. It was visualized that the condensed liquid on the outer surface of SH-C type tubes flowed continuously down unlike a low integral-fin tube and a plain tube, due to a 3-D extending fin on the outer surface of SH-C type tubes. As a result, the thermal resistance of the condensed liquid decreased and the heat transfer coefficient increased. Also, the enhancement ratio of SH-CDR tube was the highest, and it was about 9-11 times as compared to that of a plain tube.

  • PDF

A Study on the Condensation Heat Transfer and Pressure Drop in Internally Grooved Tubes Used in Condenser (응축기용 낮은 핀관의 내부 나선 홈에 의한 응축 열전달 성능과 압력손실에 관한 연구)

  • Han, Kyuil;Cho, Dong-Hyun
    • Journal of the Korean Society of Fisheries and Ocean Technology
    • /
    • v.34 no.2
    • /
    • pp.212-222
    • /
    • 1998
  • Heat transfer performance improvement by fin and groovs is studied for condensation of R-11 on integral-fin tubes. Eight tubes with trapczodially shaped integral-fins having fin density from 748 to 1654fpm(fin per meter) and 10, 30 grooves are tested. A plain tube having the same diameter as the finned tubes is also used for comparison. R-11 condensates at saturation state of 32 $^{\circ}C$ on the outside tube surface coded by inside water flow. All of test data are taken at steady state. The heat transfer loop is used for testing singe long tubes and cooling is pumped from a storage tank through filters and folwmeters to the horizontal test section where it is heated by steam condensing on the outside of the tubes. The pressure drop across the test section is measured by menas pressure gauge and manometer. The results obtained in this study is as follows : 1. Based on inside diameter and nominal inside area, overall heat transfer coefficients of finned tube are enhanced up to 1.6 ~ 3.7 times that of a plain tube at a constant Reynolds number. 2. Friction factors are up to 1.6 ~ 2.1 times those of plain tubes. 3. The constant pumping power ratio for the low integral-fin tubes increase directly with the effective area to the nominal area ratio, and with the effective area diameter ratio. 4. A tube having a fin density of 1299fpm and 30 grooves has the best heat transfer performance.

  • PDF