• Title/Summary/Keyword: 김두현

Search Result 335, Processing Time 0.025 seconds

Development of Thermal Precursor DB for Partial Disconnection and Poor Contact on Electrical Wire (배선에서의 반단선 및 접촉불량에 대한 열적 전조 DB구축)

  • Kim, Doo-Hyun;Kim, Sung-Chul;Lee, Jong-Ho;Kang, Dong-Kyu
    • Journal of the Korean Society of Safety
    • /
    • v.24 no.2
    • /
    • pp.30-36
    • /
    • 2009
  • This paper aims at the precursor analysis and DB development of electrical fires based on thermal and current signals for partial disconnection and poor contact on electric wires through experiments and simulations. Also, DB system required for developing the precursor DB with these data was studied and designed. Firstly, in case of partial disconnection, characteristics were derived and analyzed by experiment and electrical-thermal finite element method(Flux 3D) on the model wires which consist of VCTF and IV electric wires. Based on the characteristics, About 351 partial disconnection precursor patterns were generated by the thermal analysis for electric wire according to deterioration time under normal state and 200% overload state of rated current. Secondly, in order to develop poor contact precursor patterns, temperature value and the current signal were considered. In simulating the poor contact situation on connector area of MCCB, connection torque was changed. Through the experimental analysis, about 251 poor contact precursor patterns were generated. Finally, Using thermal precursor patterns obtained by partial disconnection and poor contact, electrical fire thermal precursor DB was developed.

Analysis of Voltage, Current and Temperature Signals for Poor Connections at Electrical Connector (커넥터에서 접촉불량 발생시의 전압, 전류 및 온도 신호 특성 분석)

  • Kim, Sang-Chul;Kim, Doo Hyun;Kang, Shin Uk
    • Journal of the Korean Society of Safety
    • /
    • v.29 no.2
    • /
    • pp.12-17
    • /
    • 2014
  • This paper is aimed to analyze the characteristics of simultaneous voltage, current and temperature signals for poor connection on electrical connector. In order to attain this purpose, detected were the current and voltage signals on electric wire with series arc, named arc signals, and also monitored were the changes of RMS, instantaneous value of waveform in time domain and temperature value with video. Two states are made normal state over $5kgf{\cdot}cm$ and poor connections state below $0.5kgf{\cdot}cm$ by screw gage. In the voltage signal case, the voltage drop was increased with which the current was increased. In the current signal case, poor connections at the time interval 1~4A all showed "shoulder", as distinct difference from the normal state shown waveform pattern. In the temperature signal case, poor connections are twice at 1A and five times at 4A in the normal state. The temperature continues insulation of electrical wiring and connector can be carbonized. The results of this study will be effectively used in developing the preventive devices and system for electric fire by poor connections.

Development of Leakage Detector for Electric Equipment Failure in Fountain (분수대에서의 전기설비 고장에 대한 누전 감지 장치 개발)

  • Kim, Doo-Hyun;Kim, Sung-Chul;Park, Jong-Young
    • Journal of the Korean Society of Safety
    • /
    • v.33 no.1
    • /
    • pp.35-40
    • /
    • 2018
  • This research aimed to develop an leakage detector of analyzing the electric potential generated from the electric leakage of electric equipment of the fountain. To accomplish this goal, the potential gradient was analyzed against path 1 ~ path 4; this was done by taking the lighting of a fountain as the electric leakage point based on code analyses in Korea and other countries. Lighting 1 was taken as the electric leakage point, and the earthing point was set against lightings(2~3). It appeared that the allowable touch voltage against the 1 type(under 2.5 V) exceeded 60.0%. Therefore, the lighting of fountain turned out to be the most dangerous point, and electric shock could be formed by the electric leakage of electric equipment in underwater as well as by the lighting. An leakage detector was developed based on this risk; this detector is capable of analyzing the electric potential of a electric equipments of the fountain in underwater. Then, a verification test was carried out. This leakage detector can be used to measure electric potential in various submerged areas such as swimming pools, flooded spaces, and fountains.

Characterization of carbon nanofluids applicable to heat transfer fluids (열전달 유체 적용을 위한 카본 나노유체 특성 분석)

  • Kim, Doo-Hyun;Hwang, Yu-Jin;Kwon, Yeoung-Hwan;Lee, Jae-Keun;Hong, Dae-Seung;Moon, Seong-Young;Kim, Soo-H.
    • 한국전산유체공학회:학술대회논문집
    • /
    • 2008.03b
    • /
    • pp.538-541
    • /
    • 2008
  • The carbon laden suspensions in water with no surfactants have poor stability caused by the hydrophobic layer of particles. In this study, the water-based carbon nano colloide(CNC) was successfully produced using electro-chemical one-step method without agent. The properties of CNC were characterized by using various techniques such as particle size analyzer, TEM, FT-IR, turbidity meter, viscometer, and transient hot-wire method. The average size of the suspended in the CNC was 15 nm in diameter. The thermal conductivity of CNC compared with water was increased up to 14% with 4.2wt% concentration. The CNC was stable over 600hr. The enhanced colloidal stability of CNC may be caused by the chemical structures, such as, hydroxide and carboxyl groups formed in outer atomic layer of carbon, which (i) made the carbon nanofparticles hydrophilic and (ii) prevented the aggregation among nanoparticles.

  • PDF

Studies on the influence of the chemical types of insolubilizers on coated paper properties (내수화제가 도공지의 물성에 미치는 영향)

  • Kim, Sun Goo;Kim, Du Hyuen;Won, Jong Myoung;Lee, Yong Kyu
    • Journal of Korea Technical Association of The Pulp and Paper Industry
    • /
    • v.46 no.3
    • /
    • pp.73-80
    • /
    • 2014
  • In this study, in order to investigate the influence of insolubilizer on the double coating structure, we carried out basic research related to the double coating formulation with four insolubilizers having various chemical types such as amino aldehyde, glyoxal and two metallic salts. It was found that although the four insolubilizers showed similar results on optical and surface properties of the coated papers, they gave different results in the printabilities of the coated papers since coating structure was significantly influenced by different reacting mechanism of the insolubilizers. Three of the insolubilizers (glyoxal, two metallic salts) showed better results than amino aldehyde type one when they were applied to top coating formulation. Metallic salts type insolubilizers showed good results in the print gloss when it was applied to top coating formulation. It was believed that amino aldehyde type insolubilizer applied top coating formulation showed good both of dry-pick and wet-pick strength.

Assessment of Possibility on the Human Risk for the Electromagnetic Field of Unbalanced Two Coupled Three-phase Transmission Line Using Fuzzy Theory (퍼지이론을 이용한 3상 2회선 불평형 송전선로에서의 전자계에 대한 인체 위험 가능성평가)

  • Kim, Sang-Chul;Kim, Doo-Hyun
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.2 s.74
    • /
    • pp.22-28
    • /
    • 2006
  • This paper presents assessment of possibility on the human risk for the electromagnetic field of unbalanced two coupled three-phase transmission line using fuzzy theory. Three phase load flow program was developed which employed a Newton-Raphson method as a tool to analyze system unbalanced. This research presents a method of handling two coupled three phase transmission system unbalance analysis and unbalanced power demand as a function of voltages. As the results of case study, in case of 345[kV] T/L, the electric field intensity was 10.9540[kV/m], magnetic field intensity was 0.2567[G] in severest case. The results showed that the membership of a proposition fuzzy '10.9540 [kV/m] is hazardous' is 0.6349. As the analytic results using the fuzzy qualifier term, the membership in case of very false is 0.1379 and fairly false is 0.6124, respectively. In assessment of fuzzy measure possibility for the electromagnetic field, this paper used probability of fuzzy arid measure of fuzziness technique.

Analysis of Current Characteristics Determined by Doping Profiles in 3-Dimensional Devices (3차원 구조 소자에서의 doping profile에 따른 전류 특성 분석)

  • Cho, Seong-Jae;Yun, Jang-Gn;Park, Il-Han;Lee, Jung-Hoon;Kim, Doo-Hyun;Lee, Gil-Seong;Lee, Jong-Duk;Park, Byung-Gook
    • Proceedings of the IEEK Conference
    • /
    • 2006.06a
    • /
    • pp.475-476
    • /
    • 2006
  • Recently, the demand for high density MOSFET arrays are increasing. In implementing 3-D devices to this end, it is inevitable to ion-implant vertically in order to avoid screening effects caused by high silicon fins. In this study, the dependency of drain current characteristics on doping profiles is investigated by 3-D numerical analysis. The position of concentration peak (PCP) and the doping gradient are varied to look into the effects on primary current characteristics. Through these analyses, criteria of ion-implantation for 3-D devices are established.

  • PDF

An Assessment of Electric Shock Hazard by Safety Criteria Using Graphical Method (그래프법을 이용한 안전기준에 의한 감전위험성 평가)

  • 김두현;강동규
    • Journal of the Korean Society of Safety
    • /
    • v.16 no.3
    • /
    • pp.53-60
    • /
    • 2001
  • This paper presents a graphical method for hazard assessment of electric shock by safety criteria. For the human body to be safety actual body current should not exceed safety criteria, i.e. allowable body current. The assessment method presented in this paper is based m the safety criteria of the IEEE Standard 80 as well as the IEC 479-1. The hazard can be assessed in terms of alterable touch voltages instead of alterable body current. Thus, the hazard assessment of given electric shock condition is referred to a procedure by which the actual touch voltages are compared with the allowable (safe) touch voltages. Since the IEC 479-1 safety criteria are nonlinear, the graphical method is presented for the hazard assessment. Body current and body voltage are calculated with the allowable touch voltage. A comparison of the safety criteria of two widely accepted standards, i.e. the IEEE Std 80 End the IEC 479-1 is proposed. Also Thevenin equivalent resistance is obtained from electric shock model expressed by two-port earth-grid-foot system. On the basis of calculated results, the allowable touch voltage, the body current and the body voltage we can conduct the hazard or safety assessment and estimate the severity of electric shock.

  • PDF

Analysis of Current Signals for Overcurrent and Series Arc in Traditional Market Shops (재래시장 상가에서 과전류 및 직렬아크의 전류 신호에 대한 분석)

  • Kim, Doo-Hyun;Hwang, Dong-Kyu;Kim, Sung-Chul;Kim, Sang-Ryull;Lee, Jong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.3
    • /
    • pp.42-48
    • /
    • 2012
  • This paper is aimed to analysis of electrical fire risk by overcurrent and series arc signals in traditional market shops Firstly, the field state investigation was conducted for shops at the traditional market (30 shops). At each shop in the traditional market, load characteristics were investigated and thermal characteristics in Panel were analyzed. Thermal characteristics in Panel is an indicator that can determine the impact of overcurrent. Results of the field state investigation found out four shops which showed abnormal thermal characteristics in Panel. Electrical load characteristics of these 4 shops were simulated by experimental setup consists of generator, motor and heater. In order to verify the electrical fire risk by electrical loads of 4 shops, arc and overcurrent experiments were conducted. The waveshapes of arc and overcurrent are investigated in both the time and frequency domains to find signal characteristics. The results obtained in this paper will be very helpful for the prevention of electrical fires occurred at the shops in the traditional market.

Electrical Fire Detection System using Temperature and Current Detectors (열.전류 감지기를 이용한 전기화재감지시스템)

  • Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.22 no.3 s.81
    • /
    • pp.7-12
    • /
    • 2007
  • This paper presents the development of an electrical fire detection system using digital temperature and current detectors in order to sound for electrical fire in advance. As the demand for electricity is increasing and industrial facilities are getting more complex and larger in size, the losses of human life and property are on the increase by electrical fires. In order to prevent electrical fires, it is required to find out fire signatures, or electric signal of the overcurrent and overheating. Therefore, in this paper, developed is an electrical fire detection system based on the detection of signal for overcurrent and overheating to prevent electrical accidents in advance that happen in electrical wires. The developed system gives an alarm by computer monitor, speaker system and mobile phone before electrical fires occur and give severe damages to human beings and properties, and the system can be implemented and supplied for business and residental buildings at a low price. The usefulness and validity of the system, also, verified in this paper by case study and experiments.