Study on Measurement Method of Air Egress Velocity in Vestibule of Smoke Control System (특별피난계단 부속실 제연설비의 방연풍속 측정 방법에 관한 연구)

  • Lee, Su-Kyung;Hong, Dae-Hwa
    • Fire Science and Engineering
    • /
    • v.25 no.3
    • /
    • pp.85-90
    • /
    • 2011
  • This study of the vestibule of pressurizing smoke control system installed in domestic high-rise buildings for evacuation in case of fire, when the door is open to forming characteristics of the air flow was analyzed using fire dynamics simulator and analyzed of variance. Vestibule which is compartment of the design condition, air flow in the exhaust damper was formed severe turbulence confirming preceding research. The door position is in the range of formed vortex, unsteady flow of air occurs at the point that the door could be confirmed. According to the NFSC 501A, door to symmetrically separate the average of 10 points or more as measured from the average of wind speed to do is based. Under these conditions, it is difficult to measure the characteristics of the upper air flow of upper points. so measuring points are subdivided by more than 64 points method presented in TAB because severe deviation of wind speed.

The Analysis of Correlation Major System Factors with the Performance of Smoke Control Systems Using Pressure Differentials (차압제연설비의 성능과 관련된 시스템 및 환경 변수와의 상관성 분석)

  • Yeo, Yong-Ju;Kim, Hak-Jung;Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.97-105
    • /
    • 2010
  • The smoke control systems using pressure differentials are already well known as the most reliable method to prevent the smoke infiltration into the emergency stairs or safe spaces. However, it is true that many problems are domestically pointed out due to the insufficient understanding and technology on the smoke control systems using pressure differentials. In this regard, this work analyzed the effect of major factors for smoke control system using pressure differentials such as a duct area, opening area of air supply damper, improvement on open vestibules, stack effect and location of air supply. In conclusion, adequate pressure differentials can not be maintained in small duct because the smaller duct area have the large friction loss. Especially, It is confirmed that the major factor for deterioration of smoke control system performance is stack effect that makes pressure differentials smaller in the lower floors.

A Study on the State feedback with Integral Control for a Variable Air Volume Unit (가변 풍량 유닛에 대한 적분기를 가진 상태 궤환 제어에 관한 연구)

  • 박세화
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.1 no.2
    • /
    • pp.9-14
    • /
    • 2000
  • State feedback with integral control for a variable air volume(VAV) unit which is recently taken notice of for the energy efficiency and saving in the building is studied to investigate the performance of the digital control methodology for the possible practical application. The digital controller which acquires the targat zone temperature and the air flow rate of the supplied air to the zone controls the opening of the damper in the VAV unit. Simulation results are performed for the conditions including reference changes and external thermal variations. In the simulation. simplified conditioned zone and the damper actuator modelling is considered. and relationships between controller gain Parameters and the system dynamics are investigated.

  • PDF

An Analysis on the Major Parameter and the Relations of Pressure Difference Effect of Leakage Area in the Smoke-Control Zone (제연구역의 주요 매개 변수 및 누설 면적 변화를 고려한 차압 형성 관계 분석)

  • You, Woo Jun;Ko, Gwon Hyun;SaKong, Seong Ho;Nam, Jun-Seok;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.27 no.1
    • /
    • pp.20-25
    • /
    • 2013
  • This study is experimentally analyzed to extract the major parameters affecting the performance of the smoke-control system and the relations of pressure difference between vestibule and supply air pressure zone effect of supply mass flow rate and leakage area in the smoke-control zone. To obtain this, the mock-up building of three-story scale with a total of 10 compartments was constructed, and several apparatus were also installed for in-situ measurement of the ventilation flow rate, pressure difference between compartments, smoke defensive air velocity, the opening-closing force of door, etc. This article show that pressure difference in the smoke-control zone is significantly related with leakage area of vestibule in low pressure region, leakage area of supply air pressure in over pressure region and both of them in pressure control region when the pressure control range of damper is 45 Pa~55 Pa.

Study of Smoke Behavior and Differential Pressure in the Refuge Safety Area According to Damper Capacity of Smoke Control (제연댐퍼 송풍량에 따른 피난 안전 구역 차압 및 연기 거동 특성 연구)

  • Lee, Jae-Bin;Moon, Joo-Hyun;Lee, Seong-Hyuk;Ryou, Hong-Sun
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.103-109
    • /
    • 2011
  • In this study, we calculated the smoke movement at the fire area of the refuge floor which has the refuge safety area in case of fire in the high rise building by using a computational fluid dynamics (CFD) code of FLUENT (ver. 13.0). The buoyancy plume was applied using the temperature and flow velocity which represent 10 MW heat release rate in order to describe the fire, and the smoke movement was predicted using a species conservation equation. The pressurization system of smoke control was adopted with smoke control damper in refuge safety area, at the result, it is confirmed that the damper capacity was enough to smoke control in which the flow rate of supply was applied 25 $m^3/s$ in the case of the door at fire area opened only, and 50 $m^3/s$ in the doors at the fire area and lobby both opened case. They were satisfied in NFSC 501-A. Even though the door of fire area closed, there were smoke leakages at the gap between the door and wall. In addition, the refugee could be isolated in the fire area when the door of fire area closed during smoke control in the case of using the high damper flow rate of supply, 50 $m^3/s$. Therefore the proper damper flow rate of supply are needed in order to prevent the damage of refugee and this study proposes the suitable condition of damper capacity according to refuge scenario.

Pressure Differentials in the Elevator Lobby Depending on the Evacuation Scenarios (피난 시나리오에 따른 승강장 부속실 차압 특성 연구)

  • Park, Yong-Hwan
    • Fire Science and Engineering
    • /
    • v.21 no.4
    • /
    • pp.38-43
    • /
    • 2007
  • The aim of this paper is to investigate the change of pressure differential and smoke propagation characteristics in the elevator lobby with the resident's evacuation scenarios using fire modelling technique. The results showed absolute pressures in the fire room and elevator lobby can significantly increase to cause fire door to the stairway unclosed once it is open. This is due to constant pressure differentials, the increasing reference pressure of fire lobby and pressure leak from elevator lobby to fire lobby. Smoke exhaust mechanism was needed to prevent the continuous pressure rise in the living room. Over 200 Pa was expected upon closing the door during pressurization, which provide difficulties in opening the door for next refugee. Opening both fire door and entrance door may induce smoke flow from fire room to elevator lobby and stairway.

Numerical Study on Air Egress Velocity in Vestibule Pressurization System : Characteristics of Air Flow in the Vestibule with Multiple Fire Doors in an Apartment Building (부속실 가압 시스템의 방연풍속에 관한 수치해석적 연구: 공동주택 부속실내에 다수 출입문의 존재시 기류특성)

  • Seo, Chanwon;Shin, Weon Gyu
    • Fire Science and Engineering
    • /
    • v.28 no.5
    • /
    • pp.30-36
    • /
    • 2014
  • The pressurized smoke control system in the vestibule is important for fire safety in buildings because it is concerned with egress time of people and the safety of fire fighters. The vestibule pressurization system can prevent smoke from entering the vestibule using differential pressure when fire doors are closed and using the egress velocity when fire doors are open. Air supplying units in the vestibule need to be arranged by taking account of the location of doors and the volume of the vestibule in order to assure the uniform air egress velocity through a fire door when it is open. In this study, computational fluid dynamics (CFD) simulations were conducted for the vestibule where multiple doors are installed and it was found that the reverse flow occurs when the damper position in vestibule is not appropriate.

Remote Monitoring Panel and Control System for Chemical, Biological and Radiological Facilities (화생방 방호시설을 위한 원격감시 패널 및 제어시스템)

  • Park, Hyoung-Keun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.1
    • /
    • pp.464-469
    • /
    • 2019
  • A remote monitoring panel and control system was developed to control various valves and access control chambers, including gas shutoff valves used in CBR(Chemical, Biological and Radiological) facilities. The remote monitoring panel consisted of a main panel installed in the NBC (Nuclear, Biological and Chemical) control room and auxiliary panel installed in the clean room, and the size was divided into pure control and control including CCTV. This system can be monitored and controlled remotely according to the situation where an explosion door and gas barrier door can occur during war and during normal times. This system is divided into normal mode and war mode. In particular, it periodically senses the operation status of various valves, sensors, and filters in the CBR facilities to determine if each apparatus and equipment is in normal operation, and remotely alerts situation workers when repair or replacement is necessary. Damage due to the abnormal operation of each device in the situation can be prevented. This enables control of the blower, supply and exhaust damper, emergency generator, and coolant pump according to the state of shutoff valve and positive pressure valve in the occurrence of NBC, and prevents damage caused by abrupt inflow of conventional weapons and nuclear explosions.