• Title/Summary/Keyword: 국소배기장치

Search Result 41, Processing Time 0.025 seconds

Change in Exposure Concentration in the Cleaning Process after Installing a Local Exhaust System (디클로로메탄 사용 세척공정의 국소배기장치 설치 후 노출농도 변화)

  • Myung Hwa Cho;Seung gi Kim;Hyun Soo Kim
    • Journal of Korean Society of Occupational and Environmental Hygiene
    • /
    • v.33 no.3
    • /
    • pp.280-283
    • /
    • 2023
  • Objectives: The purpose of this study was to examine the change in exposure concentration in the cleaning process after installing a local exhaust system. Methods: Dichloromethane measurement was conducted according to the KOSHA Guide (A-19-2019). Results: After the local exhaust device was installed, a total of three measurements were conducted, including temporary work environment measurements, and all of the measurements did not exceed the DCM exposure standard, but were more than 50% of the DCM Time Weighted Average((8-TWA) Conclusions: It is thought that the local ventilation system of a small business needs not only support for the initial installation cost, but also educational support for maintaining the performance of the local ventilation system and support for consumables (adsorbents, filters, etc.) that incur periodic costs.

A Study on Improvement of Industrial Hood in Ventilation System for Elimination of Harmful Material and Dust (유해물질 및 공업용 분진 제거를 위한 산업용 후드 개선에 관한 연구)

  • Kim, Young-Sun;Oh, Yool-Kwon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.4
    • /
    • pp.238-244
    • /
    • 2008
  • This study investigates on the improvement of inhalation effect of hood which attached new device named as "gas-guide-device" in local exhaust ventilation system for the effective elimination of harmful material and dust in manufacturing factory. The gas-guide-device having a diamond shape is composed of width (b) and two sides of a device (X, Y) and its size is selected the industrial hood under application in manufacturing factory after due consideration. In order to investigate the effect of gas-guide-device, numerical and experimental study is performed that the flow velocity is calculated and is measured by a commercial program "COMSOL $Multiphysics^{TM}$" and a hot wire type of anemometer, respectively. The numerical and experimental results are revealed is a similar pattern and flow velocity has improved to hood attached gas-guide-device. Also, the numerical method and result is also verified the dependance. Moreover, the optimum shape and size of gas-guide-device is revealed that the width (b) and the ratio of two sides of gas-guide-device (X, Y) has 125mm and 4 to 6.

A Study on Numerical Analysis and Performance Improvement of Ventilation Systems in Coating Room (코팅 룸 배기시스템 수치해석 및 성능개선에 대한 연구)

  • Lee, Ki Yeon;Kim, Kug Weon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.5
    • /
    • pp.2086-2091
    • /
    • 2013
  • One of the most important objects for the industrial ventilation is to protect worker's health from the harmful substances. Mainly in industrial ventilation, the harmful substances broken out through manufacturing process are to be quickly emitted outside. Recently the importance of the industrial ventilation increases with the recognition change of industrial ventilation from manufacturing focusing to human focusing. In this paper, the air flow simulation inside the coating room is performed. All the coating room and the ventilation system are modeled by SolidWorks program and air flow distribution and ventilation performance are analyzed by Flow simulation program. And the air flow directions and the air flow velocities inside the coating room are enhanced with the use of local ventilation.

Performance of Local Exhaust Ventilation Systems of Degreasing and Plating Workplaces (일부 탈지세척 및 도금공정 국소배기장치의 성능점검과 개선방안)

  • Han, Don-Hee
    • Journal of Korean Society of Occupational and Environmental Hygiene
    • /
    • v.8 no.2
    • /
    • pp.178-185
    • /
    • 1998
  • In order to evaluate and improve the performance of local exhaust ventilation systems for two TCE degreasing (A, B) and two electroplating (C, E) and one acid dipping & plating (D) operations located in Kimhae, the performance test was conducted with trace gases and a thermal anemometer (Kanomax 24-6111, Japan). For the inadequately designed systems, the improvement and redesigns in compliance with recommendation by ACGIH was suggested. The results of performance test for each system are as follows; 1. System of Workplace A was generally well-designed. Actual exhaust air flow rate was in excess of 68% above the recommended standard exhaust air flow rate. 2. System of Workplace B was very well-designed and completely enclosed. 3. All systems of Workplace C including hoods were poorly-designed and actual exhaust air flow rates were insufficient for open tanks. All systems should be upgraded according to ACGIH recommendations. 4. Supply and exhaust air flow rate of push-pull exhaust systems in Workplace D should be greatly increased. The width of flange of dipping tank hood should be increased with the value suggested. 5. System of Workplace E was well-designed. Actual exhaust air flow rate was in excess of 54% above the required.

  • PDF

Development of Basic Local Exhaust Ventilation System for Experimental Education (실험실습용 국소배기 기초실험장치의 개발)

  • Han, Don-Hee;Park, Min-Kyu
    • Journal of Environmental Health Sciences
    • /
    • v.31 no.5 s.86
    • /
    • pp.372-378
    • /
    • 2005
  • To enhance educational effect for exhaust ventilation system, more instructive educational engineering such as experimental system should be needed. This study was performed to 1) manufacture the basic experimental system for local exhaust ventilation, 2) experiment with this system and 3) develop methodology of exhaust ventilation education. With this system, three pressures (static pressure(SP), velocity pressure(VP) and total pressure(TP)) were measured and illustrated and the graphic shapes agreed to theoretical ones relatively. Entry loss factor ($F_h$) of each hood was found to be different with hood shape, duct velocity and flow rate. This result implies that precise $F_h$ should be determined case by case and a industrial hygienist should not be dependent on the existing values. Pressure loss using velocity pressure method and characteristics of air movement near hoods using fume were grasped with this system. But larger system should be recommended to produce more precise experimental results.

3-Dimensional Finite Element Analysis for Collecting Structure of Combustible Metal Dust During Explosion (가연성 금속분진 폭발시 저장 및 포집용 구조물에 대한 3차원 유한요소 해석)

  • Jang, Chang-Bong;Yong, Jong-Won;Baek, Jong-Bae;Kwon, Hyuck-Myun;Ko, Jae-Wook
    • Journal of the Korean Institute of Gas
    • /
    • v.15 no.5
    • /
    • pp.19-24
    • /
    • 2011
  • Due to the latest industrial flow comes mainly switch to high-tech industries, combustible metals as Al, Mg, Li, Zn more require to use for the aircraft, car, cell phones, electronics and others. As a result, Increasing the processing of combustible metals due to increase in amount of combustible metals giving rise dust explosions also. Most Explosions caused by combustible metal dust, occurred in air cleaning device of local exhaust ventilation to capture and store the combustible dust. Therefore, this study was conducted to present and analyze technically that deformation and rupture shape of air cleaning device structure by Finite Element Analysis(FEA) rather than a simple prediction, in case of explosion occurs in an air cleaning device.

Additional Improvement and Evaluation of Exhaust Ventilation Systems at Small and Medium Sized Enterprise (중.소규모 사업장의 국소배기장치 설치 실태와 문제점 및 개선방안)

  • Lim, Seong-Keun;Park, Doo-Yong;Kim, Won-Ki;Kim, Soo-Geun
    • Journal of Korean Society of Occupational and Environmental Hygiene
    • /
    • v.20 no.1
    • /
    • pp.1-9
    • /
    • 2010
  • Objectives : The purposes of this study were to evaluate exhaust ventilation systems(EVSs) and to suggest problems and improvements. Methods : For 50 small and medium-sized enterprises, we carried out evaluation of EVSs. We evaluated hoods with smoke tester and measurement of capture velocity. In addition, we used several indicators for performance evaluation designed in this study. Results : 1. Based on the smoke flow pattern and the criteria of occupational health and safety act, 67.8% of hoods were rated 'good' level at smoke test whereas 26.3% were rated 'good' level at measurement of capture velocity. 2. 29.3% of hoods, of which ratio of measured actual air flow at hood(Qah) to required ideal exhaust air flow at hood(Qih) was 1 or more, were rated 'good' level. 3. The % of EVS, of which ratio of measured actual air flow at stack(Qast) to total required ideal exhaust air flow at hood(Qith) was 1 or more, was 29.0%. 4. For the ratio of measured Qast to existing air flow at fan(Qfan), only 5% of EVSs were 1 or more and 26.0% were 0.8 or more but less than 1.0. 5. For the ratio of measured Qast to total measured actual exhaust air flow at hood(Qath), 74.0% were 0.8 or more but less than 1.0. 6. The percentage of EVS, of which ratio of total measured Qath to existing Qfan was 0.8 or more, was 19.0%. 7. The percentage of EVS, of which ratio of total measured Qath to total required ideal exhaust Qith was 1 or more, was 26.0%. 8. For the comprehensive evaluation indicators designed in this study, 29.0% were 0.8 or more. Conclusions : We found that few exhaust local ventilations at small and medium-sized enterprises were rated 'good' level and that most exhaust local ventilations had 'poor' design and installation. Therefore, relevant professional manpower and enterprises have to construct exhaust local ventilation where it is needed, and technical guidance and economic support are needed to improve 'poor' exhaust local ventilation after self-evaluation.

Worker Health Hazard and Risk Assessment of Formamide using in Workplaces in South Korea (작업장에서 사용하는 포름아미드(Formamide)의 근로자 건강 유해성과 위험성 평가)

  • Kim, Hyeon-Yeong
    • Journal of the Korean Institute of Gas
    • /
    • v.20 no.2
    • /
    • pp.35-42
    • /
    • 2016
  • Formamide is a colorless fluid with ammonia odor, and irritable when inhaled. It has $LD_{50}$ value of > 5,577 mg/kg in rats for acute oral toxicity and NOAEL of 113 mg/kg/day for target organ (liver) of whole body toxicity. It is also known as reproductive toxicant (1B) and TWA(Time Weighted Average) for it is 10 ppm. Workplace measurements of work places dealing with formamide showed the ppm of all 25 samples was very lower than WEL. However, the exposure concentration can change, depending on workplace condition such as the intensity of work, operating local ventilation system, and wearing protection equipment (Respirators). Therefore, considering it with the risk of whole body toxicity and reproductive toxicity, exposure quantity of each imaginary scenario was calculated at 5.16, 1.72, and $0.43mg/m^3$. The average value was calculated at 0.02-0.58, 0.02-0.66 at 90 percent of cumulative distribution, 0.02-0.69 at 95 percent of cumulative distribution. Therefore, it was generally evaluated to be safe because all values were below 1. However, caution is required to prevent health hazard because it has hepatotoxicity and reproductive toxicity and risk of a high level momentary exposure, depending on the condition of workplace.

Process Risk Assessment for a Batch Condensation Reaction of Polyester Resin using K-PSR Technique (K-PSR 기법을 활용한 회분식 폴리에스터 축합반응에서의 공정 위험성 평가 연구)

  • Park, Kyung-Min;Lee, Dong-Kyu;Lee, Haakil;Lee, Joon-Man;Ahn, Won-Sool
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.3
    • /
    • pp.35-42
    • /
    • 2019
  • Risk assessment and analysis for a medium-to-small sized chemical plant that manufactures a polyester resin by the process of batch-type condensation reaction was conducted using K-PSR technique which is one of the risk assessment methods used to implement the Process Safety Management System (PSM). K-PSR is a risk assessment technique developed by KOSHA to compensate for difficulties caused by the lack of infrastructure of medium-to-small sized chemical plants in the re-evaluation. To apply the K-PSR technique, the entire process of a selected chemical palnt was classified in two review sections, i.e., the condensation reaction process and the dilution/filtration process, and the potential risks of the process about these review sections were identified and classified based on the four guide-words (release, fire.explosion, process trouble, and injury). As the results of the research, refer to recommend of risk rating has been confirmed that non-destructive testing of old facilities and the preparation of LOTO procedures for the electrical equipments are necessary as specific measures to prevent the risk of release and fire.explosion. It was also shown that pressure gauges and thermometers should be installed on the hot-oil supply piping to minimize the process trouble, and exhausting hood should be installed to prevent potential injury.

The Consideration about Heavy Metal Contamination of Room and Worker in a Workshop (공작실에서 실내 및 작업종사자의 중금속 오염도에 관한 고찰)

  • Kim Jeong-Ho;Kim Gha-Jung;Kim Sung-Ki;Bea Suk-Hwan
    • The Journal of Korean Society for Radiation Therapy
    • /
    • v.17 no.2
    • /
    • pp.87-94
    • /
    • 2005
  • Purpose : Heavy metal use when producing the block from the workshop. At this time, production of heavy metal dust and fume gives risk in human. This like heavy metal to improve seriousness through measurement and analysis. And by the quest in solution is purpose of this thesis. Materials and Methods : Organization is Inductively Coupled Plasma Atomic Emission Spectrometer, and the object is Deajeon city 4 workshops in university hospital radiation oncology (Bismuth, Lead, Tin and cadmium). Method is the ppb the pumping it does at unit, comparison analysis. And the Calculation heavy metal standard level in air through heavy metal standard level in body and blood, so Heavy metal temporary standard set. Results : Subterranean existence room air quality the administration laws appointed Lead and Cadmium's exposure recommend that it is $3{\mu}g/m^3\;and\;2{\mu}g/m^3$. And Bismuth and Tin decides $7{\mu}g/m^3\;and\;6{\mu}g/m^3$ through standard level in air heavy metal and standard level in body and blood. Heavy metal measurement level of workshops in 4 university hospital Daejeon city compares with work existence and nonexistence. On work nonexistence almost measurement level is below the recommend level. But work existence case express high level. Also consequently in composition ratio of the block is continuous with the detection ratio. Conclusion : Worker's heavy metal contamination imbrued serious for solution founds basic part. In hospital may operation on local air exhauster and periodical efficiency check, protector offer, et al. And worker have a correct understanding part of heavy metal contamination, and have continuous interest, health control. Finally, learned society sphere administer to establishment standard level and periodical measurement. And it founds basic solution plan of periodical special health checkup.

  • PDF