The Experimental Study on Uniform Distribution of Oil at the Air Conditioning System using Two Compressors (두 대의 압축기를 적용한 에어컨의 오일분배 특성에 관한 실험적 연구)

  • 김철민;황윤제;정백영
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.2
    • /
    • pp.103-108
    • /
    • 2003
  • The common accumulator was designed for solving the maldistribution problem of oil at the air conditioning system with two compressors. The oil level inside two compressors was visualized by using a common accumulator on the various operating conditions. As a result of the visualization, oil distribution inside two compressors was achieved appropriately according to the capacity of each compressor. Uniform distribution of oil was also accomplished at on and off operation condition.

The Experimental Study on Performance Improvement under frost conditions of the Heat Pump with Corrugate Shaped Fin and Two Compressors (저 착상 휜과 두 대 압축기 사이클을 이용한 히트펌프 난방성능 개선에 관한 연구)

  • Hwang Yoon-Jei;Cho Eun-Jun;Chung Baik-Young;Lee Gam-gue
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.3
    • /
    • pp.201-208
    • /
    • 2005
  • This study presents the experimental study on improvement of frost/defrost performance in an heat pump system with newly developed fin and multiple compressors. As multiple compressors system, the variable and single speed compressor combinations has been introduced and compared with single speed 1-compressor system in a view point of improvement of frost/defrost performance. Also, newly developed corrugate shaped fin has been compared with conventional louver shaped fin. The frost/defrost performance is defined and some parameters are compared to discuss the effect of each combination. From this experimental study, it is known that if the variable and single speed compressor combination system equipped with corrugate shaped fin, the system performance has greatly improved not only for heating capacity, but also for frost performance.