• 제목/요약/키워드: 공냉

검색결과 87건 처리시간 0.028초

공냉식 응축기 관내 응축 열전달에 관한 연구 (A Study on the Condensation Heat Transfer inside Tube of an Air Cooled Condenser)

  • 정형호
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제24권3호
    • /
    • pp.13-19
    • /
    • 2000
  • In the present study, a program for predicting thermal performance of an air cooled condenser is illustrated. Heat transfer equations of single phase and two phase flow are formulated into the form that is convenient to incorporate the local analysis method. The resulting equations are solved by temperature and mass correction methods. Empirical equations for both side fluids are incorporated in the caculation procedures. In order to compare the calculation results, superheat temperature of steam are varied. The tube length of superheated zone, wall temperature, temperature profile along the tube and steam qualities are predicted.

  • PDF

디젤엔진 시동용 공냉식 고압 3단 왕복동 공기압축기의 설계 (Design of an air-cooled high-pressure 3-stage reciprocating air compressor, applied to the starting of diesel engines)

  • 이안성;김영철;정영식;왕지석
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제22권1호
    • /
    • pp.42-51
    • /
    • 1998
  • A 150 m$\^$3//hr, 30 kg/cm$\^$2/, air-cooled 3-stage reciprocating air compressor is designed to be used in starting large diesel engines of ships. A basic design procedure is presented to meet the targeted pressure and flow rate, and especially a volumetric efficiency of 80%. Temperature and stress analysis of the 1st stage cylinder are performed using axisymmetric FEM modelings. The dynamics of valve system is analyzed and stress at the 1st stage valve seat caused by valve impact is evaluated. To reduce friction loss and wear at the compressor engine system tribological design issues are reviewed and good design practices are suggested. Finally, forced-air pin-type interstage coolers are designed to dissipate generated compression heat at each stage.

  • PDF

공냉식 수직평판형 흡수기의 흡수과정에 대한 근사해법 (Approximate Solution of Absorption Process in an Air-Cooled Vertical Plate Absorber)

  • 정은수
    • 설비공학논문집
    • /
    • 제6권4호
    • /
    • pp.453-462
    • /
    • 1994
  • An unsteady quasi one-dimensional model of momentum, heat and mass transfer in a falling film of a vertical plate absorber which is cooled by air was developed using the integral method. Energy conservation of the absorber wall is considered in the model. The model can predict absorption rate, film thickness and mean velocity as well as concentration and temperature profiles. Predictions of steady state temperature and concentration profiles for LiBr/water system for constant wall temperature condition are in good agreement with the two-dimensional finite difference method solutions. Effects of operating conditions, such as convective heat transfer coefficient between the cooling air and the absorber wall, cooling air temperature and film thickness at inlet, on absorption rate of water vapor into LiBr/water solution were shown.

  • PDF

공냉식 수직 흡수기의 열전달에 미치는 계면활성제의 영향 (Influence of surfactant on heat transfer of air-cooled vertical absorber)

  • 윤정인;권오경;문춘근
    • 설비공학논문집
    • /
    • 제11권6호
    • /
    • pp.740-748
    • /
    • 1999
  • This research was concerned with the enhancement of heat transfer by surfactant added to the aqueous solution of LiBr. Different vertical tubes were tested with and without an additive of normal octyl alcohol. The test tubes were a bare inner surface, groove inner surface, corrugated inner surface and spring inserted inner surface tubes. The additive concentration was about 0.08 mass%. The heat transfer coefficient was measured as a function of film Reynolds number in the range of 20~200. Experiments were tarried out at higher cooling water temperature of $35^{\circ}C$ to simulate an air cooling condition for several kinds of absorber testing tubes. The experimental results were compared with cases without surfactant. The enhancement of heat transfer by Marangoni convection effect which was generated by addition of the surfactant is observed in each test tube. Especially, it is clarified that the tube with an inserted spring has the highest enhancement effect.

  • PDF

축류송풍기 부착형 공냉식 열교환기의 진동저감 (Vibration Reduction of an Air Cooled Heat Exchanger with Axial Flow Fan)

  • 정구충;최연선
    • 한국소음진동공학회논문집
    • /
    • 제11권6호
    • /
    • pp.163-168
    • /
    • 2001
  • Vibration problems occurred in an air cooled heat exchanger with axial flow fan for a petrochemical plant were investigated. Experimental field test and theoretical verification were performed. To find the main cause of the high vibration of the fan at the air inlet of the axial fan, the frequency spectrum was measured. The natural frequency of the driving support of the heat exchanger was numerically calculated. Both of the measured and the natural frequency were approximately equal to the blade passing frequency. Because it was difficult to modify the structure of the driving support during the normal operation of the plant, the blade number of the fan was increased, which greatly reduced the vibration level of the heat exchanger.

  • PDF

전력전자 시스템의 방열판 설계 (Heatsink Design of Power Electronics System)

  • 김찬기;곽주식;우정욱;정길조
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 1999년도 전력전자학술대회 논문집
    • /
    • pp.45-49
    • /
    • 1999
  • 본 논문은 전력전자 시스템의 방열판 시스템에 대한 이론과 실제 시스템을 고찰하고 있다. 본 논문에는 공냉식과 수냉식 방열 시스템에 관한 내용이 있다.

  • PDF

H2O/LiBr+HO(CH2)3OH계 공냉형 이중효용 흡수식 냉방시스템의 사이클 해석 (Cycle Analysis of Air-Cooled Double-Effect Absorption Cooling System Using H2O/LiBr+HO(CH2)3OH)

  • 권오경;문춘근;윤정인
    • 대한기계학회논문집B
    • /
    • 제23권2호
    • /
    • pp.272-280
    • /
    • 1999
  • A cycle analysis was achieved to predict the characteristics by comprehensive modeling and simulation of an air-cooled, double-effect absorption system using a new $H_2O/LiBr+HO(CH_2)_3OH$ solution. The simulation results showed that the new working fluid may provide the crystallization limit 8% higher than the conventional $H_2O/LiBr$ solution. With a crystallization margin of 3wt%(weight%), the optimal solution distribution ratio was found in the range of 36 to 40%. Variation of cooling air Inlet temperature has a sensitive effect on the cooling COP and corrosion problem. The simulation of heat exchangers with UA value revealed that the absorber and the evaporator are relatively important for an air-cooled system compared with the condenser and the low temperature generator. The effect of cooling air flow rate, circulation weak solution flow rate and chilled water inlet temperature were also examined. The new working fluid may provide the COP approximately 5% higher than the conventional $H_2O/LiBr$ solution.

평판핀이 부착된 공냉형 암모니아 응축기의 열전달 성능에 대한 수치적 연구 (Numerical analysis of an air-cooled ammonia condenser with plate fins)

  • 김영일;강병하
    • 설비공학논문집
    • /
    • 제9권3호
    • /
    • pp.292-299
    • /
    • 1997
  • Ammonia has been used as refrigerant for more than 100 years in absorption as well as in compression systems. Due to its poisonous and inflammable properties, however, its use has been mainly on heavy industrial plants in which regular maintenance are available. For these systems, condensers are generally water-cooled. This is suitable for large systems over 20 RT but is not suitable for small systems. In order to apply ammonia for a small system, it is important to adopt an air-cooled condenser. In this study, simple numerical analysis of an air-cooled condenser for an ammonia refrigeration system has been carried out. The condenser is designed as horizontal tubes with plate fins attached at the outer surface to enhance the air-side heat transfer rate. Effects of fin shape and arrangement are studied in detail. Since the local heat transfer coefficient is highest at the leading edge, heat flux is highest at the edge and decreases along the distance. Conditions of inlet air are also varied in the study and condenser length that is required for full condensation is calculated. The results show that it is important to enhance both the air-side and internal heat transfer coefficients.

  • PDF