A study on heat transfer and pressure drop characteristics of plain fin-tube heat exchanger using CFD analysis (CFD 해석을 통한 Plain형 핀-튜브 열교환기의 열전달 및 압력강하 특성에 관한 연구)

  • Liu, Zhao;Yoon, Jun-Kyu
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.38 no.6
    • /
    • pp.615-624
    • /
    • 2014
  • The fin-tube heat exchanger being used for industrial boiler, radiator, refrigerator has been conducted in various studies to improve it's performance. In this study, the characteristics of heat transfer and pressure drop was theoretically analyzed according to longitudinal pitch, location of vortex generator, bump phase and number of the tube surface about the plain fin-tube heat exchanger. The boundary condition for the CFD (Computational Fluid Dynamics) analysis applied with the SST (Shear Stress Transport) turbulence model assumed as the tube surface temperature of 333 K, the inlet air temperature of 423-438 K and the inlet air velocity of 1.5~2.1 m/s. The analysis results indicated that the heat transfer coefficient is not affected highly by the longitudinal pitch, and the heat transfer characteristics was more favorable when the vortex generator was located in front of the tube. Also the bump phase of the tube surface indicated that circle type was more appropriate than serrated type and triangle type in the characteristics of heat transfer and pressure drop, and the sixteen's bump phase of circle type was most favorable.

A large scale model test to investigate the pressure drop and heat transer characteristics in the air side of two-row heat exchanger (2열 휜 튜브 열교환기의 공기측 압력강하 및 열전달 특성을 고찰하기 위한 확대 모형실험)

  • Gang, Hui-Chan;Kim, Mu-Hwan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.21 no.1
    • /
    • pp.113-124
    • /
    • 1997
  • This work is performed to investigate the pressure drop and heat transfer characteristics in the air side of finned-tube heat exchanger for air conditioner. Experimental apparatus and method are described to simulate the heat exchanger performance by using the three times enlarged model. The pressure drop and heat transfer coefficient were measured and compared for the heat exchangers with a plane fin and a commercial strip fin. The measured data for the strip fin agree well with those of prototype within a few percentages. For the plane fin, the measured data had similar trend to Gray & Webb's correlation at high air velocity, however a new correlation is needed to give more accurate prediction at low air velocity. It is found that most heat was transferred around the front row of the two-row heat exchanger, and the ratio of thermal load at the front tube row was increased for decreasing air velocity.

Data Reduction on the Air-side Heat Transfer Coefficients of Heat Exchangers under Dehumidifying Conditions (제습이 수반된 공조용 증발기 습표면의 열전달계수 데이터 리덕션)

  • Kim, Nae-Hyun;Oh, Wang-Kyu;Cho, Jin-Pyo;Park, Hwan-Young;Yoon, Baek
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.1
    • /
    • pp.73-85
    • /
    • 2003
  • Four different methods of reducing the heat transfer coefficients from experimental data under dehumidifying conditions are compared. The four methods consist of two different heat and mass transfer models and two different fin efficiency models. Data are obtained from two heat exchanger samples having plain fins or wave fins. Comparison of the data with the reduction methods revealed that the single potential heat and mass transfer model yielded the humidity independent heat transfer coefficients. Two different fin efficiency models - enthalpy model and humidity model - yielded approximately the same fin efficiencies and accordingly approximately the same heat transfer coefficients. The heat transfer coefficients under wet conditions were approximately the same as those of the dry conditions for the plain fin configuration. For the wave fin configuration, however, wet surface heat transfer coefficients were approximately 12% higher. The pressure drops of the wet surface were 10% to 45% larger than those of the dry surface.

Analysis for Air-Side Convective Heat Transfer Characteristics in Compact Heat Exchangers (밀집형 열교환기 내 공기 측 대류열전달특성)

  • Moh, Jeong-Hah;Lee, Sang-Ho
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1443-1448
    • /
    • 2009
  • Numerical analysis has been carried out to investigate air-side convective heat transfer characteristics in compact heat exchangers with continuous plate fins. Simulation results such as air flow and temperature distributions are presented, and heat transfer characteristics are compared for various inlet conditions. Results from various turbulence models are also compared for applicability. There is large difference between the local heat transfer coefficient distributions along the cylinder wall for circular tubes. Colburn j factors from the calculated results of circular and flat tubes in the heat exchangers are compared for various Reynolds number. The predicted results in this study can be applied to the optimal design of air conditioning system. with compact heat exchanger.

  • PDF

A Study on Heat Transfer Characteristics in the Air Side of Louvered Fin Heat Exchanger (루우버핀형 열교환기의 공기측 열전달 특성에 관한 연구)

  • Kim, Sun-Jung
    • Journal of the Korean Solar Energy Society
    • /
    • v.23 no.1
    • /
    • pp.9-16
    • /
    • 2003
  • For the study of an effect that fin thickness and shape of heat exchanger have on the elevation of heat transfer efficiency, we make models of plate fin type heat exchanger and louvered fin type heat exchanger which was given a transformation of fin thickness in plate f)n type heat exchanger and louvered fin type heat exchanger which are often used now. And the effect of fin thickness on pressure drop and characteristics of heat transfer was experimented and analysed when air velocity and temperature of plate heating was a variable. The results of experiment shows below. Pressure drop shows larger in louvered fin type exchanger than in plate fin type exchanger, size of pressure drop shows like this order that fin thickness is 0.3mm, 0.2mm, 0.1mm. Mean heat transfer coefficient shows higher in louvered fin type exchanger than in plate fin type exchanger, size of mean heat transfer coefficient by fin thickness shows same in both case in louvered fin type heat exchanger and plate fin type exchanger like this order that fin thickness is 0.1mm, 0.2mm, 0.3mm.

An Experimental Study on the Airside Performance of Fin-and-Tube Heat Exchangers Having Wide Louver Fin (광폭 루버 핀이 장착된 핀-관 열교환기의 공기측 전열 성능에 관한 실험적 연구)

  • Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.5
    • /
    • pp.254-262
    • /
    • 2015
  • Heat transfer rate can be increased by increasing the heat transfer area. In this study, wide louver fin-and-tube heat exchangers with $P_t/P_l=1.03$ were tested and compared with louver fin-and-tube heat exchanger with $P_t/P_l=0.6$. Results show that heat transfer capacities of wide louver samples are larger (9.8% at one row, 13.6% at two row and 4.1% at three row) than those of conventional louver samples. Considering the area ratio of 1.78, the increase of heat transfer capacity is rather small, possibly due to the smaller heat transfer coefficient and fin efficiency of the wide louver sample. The j factor of the louver fin was 67% larger at one row, 42% larger at two row and 52% larger at three row. The f factor of the louver fin was 81% larger at one row, 63% larger at two row and 60% larger at three row. The effect of fin pitch on j and f factors are not pronounced and the j factor decreased as the number of tube row increased.

Evaluation of Air-side Pressure Drop and Heat Transfer Performance of Brazing Fin-tube Heat Exchanger (브레이징 휜-관 열교환기의 공기측 열유동 성능평가)

  • 강희찬;강민철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.11
    • /
    • pp.957-963
    • /
    • 2003
  • The present work was conducted to investigate the air-side thermal-hydraulic performance of the brazing fin-tube heat exchanger. Pressure drop and heat transfer coefficient for a plain and a louvered fin configuration were compared numerically and experimentally. It was found that the heat transfer characteristics for the plain fin were similar to the developing flow in the rectangular channel. The louver fin showed about twice better heat transfer coefficient than the plain fin. Previous empirical correlations presented by Davenport, Sunden and Svantesson, Sahnoun and Webb, Chang and Wang, Achaichia and Cowell, and Kang were compared with the present experimental data.

Experimental Study on the Airside Performance of Fin-and-Tube Heat Exchangers Having Wide Louver Fins Under Wet Conditions (광폭 루버 핀이 장착된 핀-관 열교환기의 습표면 성능에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.39 no.9
    • /
    • pp.719-726
    • /
    • 2015
  • One method of increasing the heat-transfer rate is to increase the heat-transfer area. In this study, we test a wide louver fin-and-tube heat exchanger with $P_t/P_l$ = 1.03, and we compare the results with those of a louver fin-andtube heat exchanger with $P_t/P_l$ = 0.6. The results obtained show that the heat-transfer capacities of the wide louver samples are larger (16% in one row, 29% in two rows, and 38% in three row samples) than those of the louver samples. Considering the area ratio of 2.17, the increase in the heat-transfer capacity is somewhat small. The reason for this may be due to the smaller heat-transfer coefficient and fin efficiency of the wide louver sample. The effect of the fin pitch on the j and f factors are not profounded. The j and f factors decreased as the number of tube rows increased. We compare the data obtained with existing correlations.

Research on Heat and Mass Transfer Coefficient in the Packing Layer With a Solar Desiccant Heating/Cooling System (태양열 데시컨트 냉난방시스템 중 충진층에 있어서의 열 물질전달에 관한 연구)

  • Yohana, Eflita;Choi, Kwang-Hwan;Kim, Bu-Ahn;Kim, Dong-Gyu;Paek, Ki-Dong;Kim, Ji-Won
    • Journal of the Korean Solar Energy Society
    • /
    • v.26 no.3
    • /
    • pp.17-24
    • /
    • 2006
  • 최근에 에너지절약 차원에서 종래의 공조방식을 대신할 새로운 냉난방시스템 개발이 요구되고 있는데, 본 논문에서는 태양열 집열기를 이용하는 데시컨트 시스템 중 제습역할을 실질적으로 담당하는 제습기의 충진층 부분에서의 열 및 물질전달에 관한 일련의 해석 결과를 발표하고 있다. 제습과정에서 액체흡수제는 충진층에서 열 뿐만 아니라 물질전달을 수반하게 되는데, 이 결과 건물에 냉방 및 난방효과를 가져다 준다. 따라서 이 충진층의 최적 설계가시스템의 효율을 극대화하기 위해서는 무엇보다도 중요한데, 이를 위해서는 충진층에서의 열 및 물질전달 양상을 규명하여야 한다. 따라서 금번 실험에서는 공기와 액체흡수제와의 접촉면적을 넓히기 위해서 충진재로써 3cm(직경) ${\times}$ 3cm(높이)인 시판중인 플라스틱 재질을 사용하고, 실질적으로 40cm(너비)${\sim}$40cm(깊이)${\times}$40cm(높이)의 충진층을 직접 제작하여 실험을 행하였다. 그 결과, 공기측 열 및 물질전달 계수는 공기 온도와 밀접한 관계를 갖고 있으며, 또한 물질전달계수는 열전달계수와 같은 경향을 보이고 있음을 알 수 있었다.

Numerical Analysis for the Air-Side Convective Heat Transfer Characteristics in a Compact Heat Exchanger with Circular Tubes and Continuous Plate Fins (원형관-평판휜 형상의 밀집형 열교환기 내 공기 측대류열전달특성에 대한 수치해석)

  • Moh, Jeong-Hah;Lee, Sang-Ho
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.31 no.12
    • /
    • pp.994-1001
    • /
    • 2007
  • Numerical analysis has been carried out to investigate air-side convective heat transfer characteristics in a compact heat exchanger with circular tubes and continuous plate fins. Simulation results such as air velocity and temperature distributions are presented, and heat transfer coefficients are compared with previous experimental correlations. Three models of standard and RNG $k-{\varepsilon}$, and Reynolds stress are applied for turbulence model applicability. Predicted heat transfer coefficient from the models of standard and RNG $k-{\varepsilon}$ are very close to those of the heat transfer correlations while there are relatively large difference, more than 17 percentage in the result from the Reynolds stress model. From the calculated results a correlation for Colburn j factor in the compact heat exchanger system is suggested.