Design of an Intelligent Sprinkler System with Risk-Level Analysis Based on Multi-Sensor Fire Detection

  • Hyun-Mi Kim (Dept. of Emergency Medical & Rescue Technology, Complex Disaster Emergency Rescue Education and Research Center Inje University) ;
  • Kyong-Jin Park (Dept. of Emergency Medical & Rescue Technology, Complex Disaster Emergency Rescue Training and Research Center Inje University)
  • 투고 : 2026.02.27
  • 심사 : 2026.06.02
  • 발행 : 2026.06.30

초록

This study proposes an intelligent sprinkler system that identifies fire zones according to risk levels using real-time multi-sensor detection data and dynamically controls water discharge intensity and spray patterns in a stepwise manner. Conventional sprinkler systems generally activate uniform water discharge across the entire protected area once predefined conditions are met, often resulting in unnecessary water damage and inefficient use of firefighting water resources. To address these limitations, the proposed system integrates and analyzes data from multiple sensors, including smoke, temperature, flame, and gas detectors, in real time to classify fire-affected zones into distinct risk levels and apply differentiated water discharge strategies corresponding to each level. While the system concept is based on a related patent filed by the author (Korean Patent Application No. 10-2025-0044155), the patented technology is not reproduced verbatim. Instead, the system is reinterpreted and expanded from an academic perspective to incorporate dynamic water discharge control mechanisms that account for fire spread characteristics and spatial conditions. This approach aims to enhance fire suppression efficiency while minimizing secondary damage resulting from unnecessary water discharge.

키워드

1. Introduction

Sprinkler systems are widely recognized as representative automatic fire suppression facilities that automatically discharge extinguishing water in the event of a fire, thereby suppressing fire spread and reducing losses to life and property. In particular, the determination of the design area and the operational characteristics of sprinkler heads are regarded as critical factors governing fire response performance, and extensive fundamental studies and experimental validations have been continuously conducted on these aspects [1]. For buildings with a high risk of vertical fire spread due to exterior finishing materials, the configuration and effectiveness of specialized systems, such as exterior wall protection sprinkler systems, have been proposed and evaluated [2]. Furthermore, in large-scale logistics facilities or rack-type warehouses with complex combustible storage configurations, previous studies have reported that the discharge characteristics and arrangement of in-rack sprinkler heads directly influence fire control performance [3].

Studies reflecting realistic fire conditions have demonstrated that direct water-supply sprinkler systems connected to municipal water lines can achieve a certain level of fire suppression performance even under limited water supply conditions. However, these systems have also been identified as having inherent structural limitations, as water is discharged uniformly across the entire protected area once the system is activated [4]. Meanwhile, studies focusing on residential spaces and small-scale buildings have addressed the applicability and performance reliability of simplified sprinkler systems as major areas of investigation [5].

With respect to sprinkler head activation characteristics, experimental studies have analyzed sprinkler response behavior as a function of fire growth rates [6], while other studies have reported that activation conditions may vary depending on specific fire growth scenarios [7]. These findings suggest that conventional sprinkler systems may exhibit differing levels of performance depending on fire characteristics, thereby highlighting the necessity for more precise and adaptive fire response strategies.

In the field of fire detection technology, extensive research has been conducted to address the limitations of single-sensor-based detection by adopting multi-sensor approaches aimed at achieving earlier fire detection and reducing false alarms. Studies employing UL 268 test fire scenarios have shown that CO sensors can be effectively utilized for early fire detection [8], while other research has reported on the development of testbeds for multi-information-based fire detection systems and evaluated their false alarm reduction performance [9]. Additionally, experimental studies have investigated the early detection performance of multi-sensor composite fire detectors in rack-type warehouse environments [10].

Recently, research efforts have increasingly focused on improving fire detection accuracy through the analysis of multi-sensor data using machine learning techniques. Studies have reported attempts to overcome the limitations of conventional detection methods by employing autoencoder-based fire detection models [11]. Furthermore, studies evaluating the suitability of sensor combinations for fire detection using machine learning approaches have been conducted to quantitatively verify the effectiveness of different sensor configurations [12].

From the perspective of fire suppression and protection, there has been growing emphasis on the need for response strategies that account for fire risk levels and spatial characteristics, rather than relying on uniform water discharge methods. Studies analyzing the effectiveness of water curtain systems under relaxed fire compartmentation conditions in logistics facilities have demonstrated that such systems can achieve a measurable level of effectiveness in suppressing fire spread [13]. Similarly, research on industrial buildings has reported that exterior wall water curtain systems can contribute to delaying fire propagation [14]. In addition, within smart building environments, the potential for intelligent and integrated fire response has been highlighted through the application of Internet of Things (IoT)-based fire protection and evacuation guidance systems [15].

In summary, previous studies indicate that the intelligent enhancement of the fire detection stage, together with differentiated suppression strategies that account for fire location and risk level, represents a key future development direction for sprinkler systems. Accordingly, the objective of this study is to design and propose an intelligent sprinkler system that identifies fire occurrence zones by risk level using multi-sensor-based fire detection data and controls water discharge intensity and discharge patterns in a stepwise manner corresponding to each risk level.

2. System Configuration and Design

The proposed intelligent sprinkler system consists of four main components: sensing unit, control unit, suppression unit, and notification unit.

The sensing unit collects real-time data such as smoke concentration, temperature, flame detection, and gas concentration. The control unit processes this data and determines fire occurrence and risk level. The suppression unit controls water discharge intensity and spray patterns based on risk levels, while the notification unit provides alerts to operators.

SOOOB6_2026_v29n3_1_631_3_f0001.png 이미지

Fig. 1. Overall architecture of the intelligent sprinkler system.

2.1 Risk-Level Classification Algorithm

The sensing unit is responsible for acquiring fire-related data in real time, including smoke concentration, temperature variation, flame presence, and combustible gas concentration. By adopting a multi-sensor architecture, the proposed system is designed to mitigate errors arising from the malfunction or abnormal behavior of individual sensors, thereby enabling more reliable and robust fire detection.

2.2 Control Unit

The control unit determines the occurrence of a fire by comparing data received from the sensing unit with predefined threshold values and data trend criteria. Once a fire is confirmed, the control unit classifies the affected area into different risk levels based on the analyzed fire characteristics.

2.3 Suppression and Notification Units

The suppression unit regulates water discharge intensity and discharge patterns in accordance with commands issued by the control unit. In parallel, the notification unit provides on-site alarms and transmits alerts to facility managers or relevant personnel, thereby supporting prompt response and enhanced situational awareness.

3. Stepwise Water Discharge Control Method

The system operates through the following sequence: fire detection, fire confirmation, zone identification, risk level classification, and adaptive water discharge control.

Unlike conventional systems, the proposed method dynamically adjusts discharge intensity and spatial distribution according to real-time fire conditions.

The concept of zone-based differentiated water discharge according to the fire occurrence location is illustrated through the example shown in Fig. 3.

SOOOB6_2026_v29n3_1_631_4_f0001.png 이미지

Fig. 2. Flowchart of the stepwise water discharge control procedure.

SOOOB6_2026_v29n3_1_631_5_f0001.png 이미지

Fig. 3. Conceptual diagram of zone-based differentiated water discharge according to the fire occurrence location.

The diagram illustrates a control structure in which high-intensity water discharge is applied to the fire-affected zone, low-intensity water discharge is applied to adjacent zones, and water discharge is restricted in distant zones. Based on the magnitude of the detection data and predefined threshold criteria, the monitored area is classified into three risk levels: normal state, potential fire state, and fire occurrence state. This zone-based risk classification concept is schematically illustrated in Fig. 4, which shows the delineation of the fire-affected area according to detection data thresholds.

SOOOB6_2026_v29n3_1_631_5_f0002.png 이미지

Fig. 4. Conceptual diagram of fire zone classification according to risk levels.

4. Application Scenario Analysis

In this section, application scenarios are considered to evaluate the practical applicability of the proposed intelligent sprinkler system across different stages of fire development and varying risk levels. The operational characteristics of the system are analyzed with an emphasis on the coordinated interactions between the sensing unit, control unit, suppression unit, and notification unit. Additionally, the distinctiveness of the proposed approach is comparatively assessed against conventional uniform water discharge systems.

4.1 Initial Fire Stage(Low-Risk Level)

An initial fire scenario is assumed, in which localized smoke and a slight temperature increase are detected in Zone 1. When one or more sensing units collect smoke concentration and temperature data and transmit them to the control unit, the control unit determines that flame signals and gas concentrations remain below predefined thresholds, classifying the zone as a low-risk level. At this stage, the likelihood of fire spread is considered limited, and the suppression unit is activated using low-intensity or localized discharge modes. This approach effectively mitigates potential fire spread while minimizing water damage caused by unnecessary excessive discharge.

4.2 Fire Growth Stage(Medium-Risk Level)

In the medium-risk level scenario, a rapid increase in temperature and smoke concentration is detected over time in the same zone or in adjacent zones. The control unit analyzes trends in the multi-sensor data and determines that the likelihood of fire spread has increased, subsequently upgrading the affected zone to a medium-risk level. In response, the suppression unit gradually increases water discharge intensity and expands the discharge range to include portions of adjacent zones, thereby proactively mitigating fire spread. Simultaneously, the notification unit issues a medium-risk alert to facility managers or the monitoring system to prompt additional response measures.

4.3 Large-Scale Fire Stage(High-Risk Level)

In the high-risk level scenario, flame sensors are activated, and high temperatures and gas concentrations exceeding predefined thresholds are detected. The control unit classifies the affected zone as high risk and directs the suppression unit to operate at maximum discharge intensity using a concentrated discharge mode. At this stage, fire suppression becomes the primary objective, and aggressive water discharge strategies are employed to prevent fire spread to adjacent zones. Concurrently, the notification unit issues an emergency alert to facilitate rapid on-site intervention by firefighting personnel.

4.4 Multi-Zone Simultaneous Fire Scenario

In scenarios where fire signals are detected simultaneously in multiple zones, the control unit independently evaluates the risk level of each zone and implements differentiated water discharge strategies accordingly. For instance, if Zone 1 is classified as high risk while Zone 2 is classified as medium risk, the suppression unit adjusts discharge intensities and patterns to match the respective risk levels. This approach enables efficient allocation of limited firefighting water resources, thereby maximizing overall system-level fire response effectiveness.

4.5 Comparative Analysis with Conventional Systems

Conventional sprinkler systems typically discharge water uniformly across the entire protected area once a single activation condition is met, often resulting in unnecessary water usage in areas not directly affected by fire. In contrast, the proposed intelligent sprinkler system maintains effective fire suppression while significantly reducing water damage and resource waste through detection-data-based risk-level classification and differentiated water discharge control. The application scenario analysis demonstrates the effectiveness of the proposed approach in overcoming the inherent limitations of conventional systems.

5. Conclusion

This study critically examined the structural limitations of conventional sprinkler systems, which rely on uniform water discharge mechanisms, and proposed an intelligent sprinkler system that implements stepwise water discharge control based on fire zone analysis. Unlike conventional systems, which operate using simple threshold-based activation and perform identical discharge without adequately accounting for key fire characteristics, such as location, scale, and spread rate, the proposed system is designed to respond more precisely to actual fire conditions. Conventional approaches may result in unnecessary water damage and inefficient use of firefighting resources, even in localized fire situations. Motivated by these limitations, this study aimed to advance sprinkler systems from basic automatic devices to intelligent fire protection systems capable of situational awareness and adaptive decision-making.

To achieve this objective, the proposed system collects multiple types of fire-related information, including smoke, temperature, flame, and combustible gas, using a multi-sensor approach and analyzes the data in real time to classify fire-affected zones according to risk levels. Specifically, fire zones are categorized into three stages: normal state, potential fire state, and fire occurrence state. Based on this classification, a stepwise water discharge control strategy is systematically implemented, applying differentiated discharge intensities and patterns corresponding to each stage. This approach clearly distinguishes the proposed system from conventional sprinkler systems by minimizing unnecessary water discharge in non-fire areas while enabling concentrated suppression in actual fire zones.

Furthermore, the proposed system incorporates a dynamic control structure that extends beyond static threshold-based operation by analyzing trends in detection data to capture fire spread dynamics. This enables proactive responses, such as upgrading the risk level of adjacent zones and progressively strengthening discharge intensity in situations where fire propagation accelerates. By simultaneously accounting for the temporal and spatial characteristics of fire, this dynamic control concept is expected to offer enhanced practical effectiveness, particularly in large-scale or structurally complex buildings.

As demonstrated through the application scenario analysis, the proposed system has the potential to minimize unnecessary discharge in unaffected areas and effectively reduce water damage in localized fire situations by concentrating suppression on the fire-affected zone. Conversely, in rapidly spreading fire scenarios, the system can help control fire propagation by progressively expanding the discharge range through dynamic risk level escalation. These features offer significant advantages for facilities where both fire response and water damage management are critical, such as logistics centers, data centers, hospitals, and smart buildings.

The academic significance of this study lies not only in proposing a novel sprinkler configuration but also in presenting an integrated control framework that encompasses fire detection, risk level assessment, and water discharge management. This framework aligns with the evolving direction of fire protection systems toward greater intelligence and sophistication and may serve as a foundational design concept for smart fire protection systems and intelligent building facilities. Although the study is based on a patented technology filed by the author (Korean Patent Application No. 10-2025-0044155), its scope extends beyond a mere reiteration of patent claims by reinterpreting and expanding the system architecture and control strategies from an academic perspective, thereby establishing its independence and scholarly contribution.

Nevertheless, this study has limitations as quantitative performance validation through real fire experiments or field implementation was not conducted, and the discussion primarily focused on system design concepts and application scenario analysis. Future research should therefore incorporate quantitative verification through scaled experiments, simulations, or limited real-environment testing to assess the accuracy of risk level classification, the appropriateness of discharge stage transitions, and the effectiveness of water damage mitigation. Moreover, the integration of artificial intelligence-based data analysis techniques to further automate risk level determination and enhance predictive accuracy represents a promising avenue for future development.

In conclusion, this study offers both academic and practical contributions by systematically analyzing the limitations of conventional sprinkler systems and proposing a design framework for an intelligent sprinkler system capable of adaptive responses to fire scenarios. The proposed system may serve as a foundational reference for the development of intelligent fire protection facilities, smart buildings, and disaster response infrastructures, and it is expected to advance the establishment of more precise and efficient fire response strategies within the field of fire safety.

참고문헌

  1. Jung, K.-S., "A Study on the Design Area of Sprinkler Systems." Journal of Korean Institute of Fire Science & Engineering, 24:3, pp.93-98, (2010).
  2. Min, S.-H., Kim, J.-H., and Lee, S.-K., "A Study on the Configuration of Exterior Wall Protection Sprinkler Systems." Journal of Korean Institute of Fire Science & Engineering, 26:1, pp.102-112, (2012). https://doi.org/10.7731/KIFSE.2012.26.1.102
  3. Kim, J.-H., Lee, H.-J., and Park, S.-Y., "Spray Characteristics of In-Rack Sprinkler Heads." Journal of Korean Institute of Fire Science & Engineering, 31:3, pp.54-62, (2017).
  4. Jung, J.-J., Kim, Y.-S., and Choi, J.-H., "Performance Evaluation of Direct Water Supply Sprinkler Systems through Real-Scale Fire Experiments." Journal of Korean Institute of Fire Science & Engineering, 25:6, pp.39-43, (2011).
  5. National Fire Protection Association, NFPA 13: Standard for the Installation of Sprinkler Systems, Quincy, MA, USA, (2025).
  6. Choi, Y.-S., and Yoon, J.-C., "An Experimental Study on the Activation Characteristics of Sprinkler Heads in Low Growth Rate Fires." Journal of Korean Institute of Fire Science & Engineering, 30:5, pp.26-35, (2016). https://doi.org/10.7731/KIFSE.2016.30.5.026
  7. Kim, S.-C., "Activation Conditions of Sprinkler Heads According to Fire Growth Scenarios." Journal of Korean Institute of Fire Science & Engineering, 34:4, pp.45-51, (2020).
  8. Lee, C.-H., Kim , J.-Y., and Park, M.-S., "Applicability of CO Sensors as Fire Detection Sensors Based on UL 268 Fire Test Scenarios." Journal of Korean Institute of Fire Science & Engineering, 28:2, pp.54-63, (2014).
  9. Lee, K.-J., Kim, H.-S., and Park, Y.-J., "Design of a Test Bed for a Multi-Information-Based System to Reduce False Fire Alarms." Journal of the Korean Institute of Gas, 16:6, pp.107-114, (2012). https://doi.org/10.7842/kigas.2012.16.6.107
  10. Gottuk, D. T., Peatross, M. J., Roby, R. J., and Beyler, C. L., "Advanced Fire Detection Using Multi-Signature Alarm Algorithms." Fire Safety Journal, 37:4, pp.381-394, (2002).
  11. Fonollosa, J., Solórzano, A., and Marco, S., "Chemical Sensor Systems and Associated Algorithms for Fire Detection: A Review." Sensors, 18:2, Article 553, (2018).
  12. Nakip, M., Güzeliş, C., and Yildiz, O., "Recurrent Trend Predictive Neural Network for MultiSensor Fire Detection." IEEE Access, 9, pp.84204-84216, (2021). https://doi.org/10.1109/ACCESS.2021.3087736
  13. Vorwerk, P., Schubert, J., and Schultze, T., "Classification in Early Fire Detection Using Multi-Sensor Data and Machine Learning Approaches." Sensors, 24:5, Article 1428, (2024).
  14. Sultan, T., Alharbi, A., and Alotaibi, F., "Deep Learning-Based Multistage Fire Detection System for Intelligent Fire Monitoring." Fire, 7:12, Article 451, (2024).
  15. Shim, S.-M., Kim, D.-H., and Lee, J.-Y., "IoT-Based Adaptive Fire Evacuation Guidance System in Smart Buildings." Journal of the Korean Institute of Communications and Information Sciences, 47:3, pp.438-452, (2022). https://doi.org/10.7840/kics.2022.47.3.438