Seismic performance assessment and reliability verification of molded transformers based on shaking table tests

  • Sang-Moon Lee (Institute for Smart Infrastructure, Gangneung-Wonju National University) ;
  • Bub-Gyu Jeon (Seismic Research and Test Center, Pusan National University) ;
  • Woo-Young Jung (Department of Civil and Environmental Engineering, Gangneung-Wonju National University)
  • Received : 2024.07.25
  • Accepted : 2024.09.30
  • Published : 2024.11.25

Abstract

In this study, shaking table tests were conducted to assess and analyze the seismic performance of the molded transformers used in actual hydropower plants. The test method was executed by adjusting the acceleration magnitude through the generation of artificial earthquakes that comply with the seismic performance criteria outlined in the ICC-ES AC 156 procedure. Additionally, a performance assessment for earthquakes with a magnitude of 5.0 or greater, recorded domestically in recent times, was concurrently conducted to analyze the dynamic behavioral characteristics. The test results indicated that there was no functional damage to the test specimen in all shaking table test procedures. However, structural damage began to be visually confirmed through a visual inspection when the artificial seismic intensity exceeded 100%, and at 150%, cumulative deformation was measured at the lower part. This is attributed to the nonlinear behavior caused by the structural characteristics of the heavy upper structure, its high centre of gravity, and the relatively small load and high flexibility of the lower frame. The excessive relative displacement between the upper and lower parts resulting from this phenomenon is anticipated to lead to potential damage, such as collisions with surrounding equipment or impact on adjacent facilities.

Keywords

Acknowledgement

This present work was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education (2021R1A6A1A03044326 and 2022R1A6A3A01086071).

References

  1. Abdelnaby, A.E. and Elnashai, A. S. (2015), "Numerical modeling and analysis of RC frames subjected to multiple earthquakes", Earthq. Struct., 9(5), 957-981. http://doi.org/10.12989/eas.2015.9.5.957
  2. Achour, N., Miyajima, M., Kitaura, M. and Price, A. (2011), "Earthquake-induced structural and nonstructural damage in hospitals", Earthq. Spectra, 27(3), 617-634. https://doi.org/10.1193/1.3604815.
  3. Bianchi, S., Ciurlanti, J., Perrone, D., Filiatrault, A., Costa, A.C., Candeias, P.X., ... and Pampanin, S. (2021), "Shake-table tests of innovative drift sensitive nonstructural elements in a low- damage structural system", Earthq. Eng. Struct. Dyn., 50(9), 2398-2420. https://doi.org/10.1002/eqe.3452.
  4. Cho, S.G. and Salman, K. (2022), "Seismic demand estimation of electrical cabinet in nuclear power plant considering equipment-anchor-interaction", Nuclear Eng. Technol., 54(4), 1382-1393. https://doi.org/10.1016/j.net.2021.10.021.
  5. Chung, W.J., Yun, C.B., Kim, N.S. and Seo, J.W. (1999), "Shaking table and pseudodynamic tests for the evaluation of the seismic performance of base-isolated structures", Eng. Struct., 21(4), 365-379. https://doi.org/10.1016/S0141-0296(97)00211-3.
  6. Cook, R.A. and Klingner, R.E. (1989), Behavior and Design of Ductile Multiple-Anchor-to-Concrete Connections, The University of Texas at Austin, Austin, TX, USA.
  7. D'Angela, D., Magliulo, G. and Cosenza, E. (2021), "Seismic damage assessment of unanchored nonstructural components taking into account the building response", Struct. Saf., 93, 102126. https://doi.org/10.1016/j.strusafe.2021.102126.
  8. Dinh, N.H., Kim, J.Y., Lee, S.J. and Choi, K.K. (2019), "Seismic vulnerability assessment of hybrid mold transformer based on dynamic analyses", Appl. Sci., 9(15), 3180. https://doi.org/10.3390/app9153180.
  9. Dinh, N.H., Lee, S.J., Kim, J.Y. and Choi, K.K. (2020), "Study on seismic performance of a mold transformer through shaking table tests", Appl. Sci., 10(1), 361. https://doi.org/10.3390/app10010361.
  10. El Sharnouby, M.M. and El Naggar, M.H. (2010), "Numerical investigation of the response of expansion anchors used to attach helical pile connectors to concrete foundations", Can. J. Civil Eng., 37(6), 866-877. https://doi.org/10.1139/L10-025.
  11. FEMA 461 (2007), Interim Testing Protocols for Determining the Seismic Performance Characteristics of Structural and Nonstructural Components, Federal Emergency Management Agency, Washington, D.C., USA.
  12. Filiatrault, A. and Sullivan, T. (2014), "Performance-based seismic design of nonstructural building components: The next frontier of earthquake engineering", Earthq. Eng. Eng. Vib., 13, 17-46. https://doi.org/10.1007/s11803-014-0238-9.
  13. Ge, Q., He, T., Xiong, F., Zhao, P., Lu, Y., Liu, Y. and Zhou, N. (2020), "Performance study of SC wall based on experiment and parametric analysis", J. Civil Eng. Manag., 26(3), 227-246. https://doi.org/10.3846/jcem.2020.12181.
  14. Hafezolghorani, M., Hejazi, F., Vaghei, R., Jaafar, M.S.B. and Karimzade, K. (2017), "Simplified damage plasticity model for concrete", Struct. Eng. Int., 27(1), 68-78. https://doi.org/10.2749/101686616X1081.
  15. Huang, B., Gunay, S. and Lu, W. (2022), "Seismic assessment of freestanding ceramic vase with shaking table testing and performance-based earthquake engineering", J. Earthq. Eng., 26(15), 7956-7978. https://doi.org/10.1080/13632469.2021.1979132.
  16. ICC-ES AC-156 (2010), Acceptance Criteria for Seismic Certification by Shake-Table Testing of Nonstructural Components, Fourth Draft, Applied Technology Council, Redwood City, CA, USA.
  17. IEC 60068-3-3 (1991), Environmental Testing-Part 3-3: Guidance-Seismic Test Methods for Equipments, International Electronic Commission, Geneva, Switzerland
  18. IEC TS 62271-210:2013 (2013), Seismic Qualification for Metal Enclosed and Solid-Insulation Enclosed Switchgear and Controlgear Assemblies for Rated Voltages above 1 kV and up to and Including 52 kV, International Electrotechnical Commission, Geneva, Switzerland.
  19. IEEE Std. 323-2003 (2003), IEEE Standard for Qualifying Class 1E Equipment for Nuclear Power Generating Stations, Institute of Electrical and Electronics Engineers, Piscataway, NJ, USA
  20. IEEE Std. 344:2004 (2004), IEEE Recommended Practice for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Station, Institute of Electrical and Electronics Engineers, Piscataway, NJ, USA.
  21. IEEE Std. 382:2006 (2006), IEEE Standard for Qualification of Safety-Related Valve Actuators, Institute of Electrical and Electronics Engineers, Piscataway, NJ, USA.
  22. Institute of Electrical and Electronics Engineers (IEEE) (2005), IEEE Recommended Practice for Seismic Design of Substations, Institute of Electrical and Electronics Engineers, Piscataway, NJ, USA.
  23. ISO 898-1 (2013), Mechanical Properties of Fasteners Made of Carbon Steel and Alloy Steel-Part 1: Bolts, Screws and Studs with Specified Property Classes-Coarse Thread and Fine Pitch Thread, ISO, Geneva, Switzerland
  24. Jang, H.T. and Shin, P.S. (2011), "A surge voltage distribution analysis of 2MVA cast resin transformer winding with FEM simulation", J. Korean Inst. Illuminat. Electr. Install. Eng., 25(5), 15-21. https://doi.org/10.5207/JIEIE.2011.25.5.015.
  25. Ji, X., Fenves, G.L., Kajiwara, K. and Nakashima, M. (2011), "Seismic damage detection of a full-scale shaking table test structure", J. Struct. Eng., 137(1), 14-21. https://doi.org/10.1061/(ASCE)ST.1943-541X.00002.
  26. Kai, S., Otani, A. and Kaneko, N. (2012), "Analytical study on seismic response of piping under multiple support excitations", Press. Vessels Pip. Conf., 55072, 37-43. https://doi.org/10.1115/PVP2012-78203.
  27. KDS 41 17 00 (2019), Seismic Design Code of Buildings (KDS 41 17 00:2019), Korean Design Standard, Seoul, Korea.
  28. Lee, J. and Fenves, G.L. (1998), "Plastic-damage model for cyclic loading of concrete structures", J. Eng. Mech., 124(8), 892-900. https://doi.org/10.1061/(ASCE)0733-9399(1998)124:8(892).
  29. Lee, S.M., Jeon, B.G. and Jung, W.Y. (2022), "Evaluation of vibration characteristics according to changes in the fixing conditions of the electrical cabinet in power plants under an earthquake", Earthq. Struct., 23(3), 245. https://doi.org/10.12989/eas.2022.23.3.245.
  30. Li, C.S., Lam, S.S., Zhang, M.Z. and Wong, Y.L. (2006), "Shaking table test of a 1:20 scale high-rise building with a transfer plate system", J. Struct. Eng., 132(11), 1732-1744. https://doi.org/10.1061/(ASCE)0733-9445(2006)132:11(1732).
  31. Madan, A. and Hashmi, A.K. (2008), "Analytical prediction of the seismic performance of masonry infilled reinforced concrete frames subjected to near-field earthquakes", J. Struct. Eng., 134(9), 1569-1581. https://doi.org/10.1061/(ASCE)0733-9445(2008)134:9(1569).
  32. Martinelli, P. and Filippou, F.C. (2009), "Simulation of the shaking table test of a seven-story shear wall building", Earthq. Eng. Struct. Dyn., 38(5), 587-607. https://doi.org/10.1002/eqe.897.
  33. Ministry of the Interior and Safety (MOIS) (2017), Seismic Design General Application, The Ministry of the Interior and Safety, Sejong-si, Korea.
  34. Ministry of the Interior and Safety (MOIS) (2018), 2017 Pohang Earthquake White Paper, Ministry of the Interior and Safety, Pohang-si, Korea.
  35. MTS Systems Corporation (2004), STEX Seismic Test Execution User Manual, MTS Systems Corporation, Eden Prairie, MN, USA.
  36. Perrone, D., Calvi, P.M., Nascimbene, R., Fischer, E.C. and Magliulo, G. (2019), "Seismic performance of non-structural elements during the 2016 Central Italy earthquake", Bull. Earthq. Eng., 17, 5655-5677. https://doi.org/10.1007/s10518-018-0361-5.
  37. Rustogi, S. and Gupta, A. (2004), "Modeling the dynamic behavior of electrical cabinets and control panels: experimental and analytical results", J. Struct. Eng., 130(3), 511-519. https://doi.org/10.1061/(ASCE)0733-9445(2004)130:3(511).
  38. Selvam, R.P., Gupta, Y. and Babu, D.N. (2020), "Evaluation of seismic behaviour of high voltage switchgear panel by shake table testing", Power Res. A J. CPRI, 2020, 137-141. https://doi.org/10.33686/pwj.v16i2.155817.
  39. Song, Z. and Su, C. (2017), "Computation of Rayleigh damping coefficients for the seismic analysis of a hydro-powerhouse", Shock Vib., 2017(1), 2046345. https://doi.org/10.1155/2017/2046345.
  40. Soroushian, S., Maragakis, M., Itani, A., Pekcan, G. and Zaghi, A. E. (2011), "Design of a test-bed structure for shake table simulation of the seismic performance of nonstructural systems", Struct. Congr., 2011, 1191-1202. https://doi.org/10.1061/41171(401)106.
  41. Yang, D., Pan, J. and Li, G. (2009), "Non-structure-specific intensity measure parameters and characteristic period of near-fault ground motions", Earthq. Eng. Struct. Dyn., 38(11), 1257-1280. https://doi.org/10.1002/eqe.889.
  42. Zareei, S.A., Hosseini, M. and Ghafory-Ashtiany, M. (2016), "Seismic failure probability of a 400 kV power transformer using analytical fragility curves", Eng. Fail. Anal., 70, 273-289. https://doi.org/10.1016/j.engfailanal.2016.09.007.
  43. Zhao, J.G., Liu, G.R., Huo, S.H. and Li, Z.R. (2022), "Modes and modal analysis of three-dimensional (3D) structures based on the smoothed finite element methods (S-FEMs) using automatically generatable tetrahedral meshes", Eng. Anal. Bound. Elem., 140, 262-281. https://doi.org/10.1016/j.enganabound.2022.04.013