Buckling Experiment of Eccentric Seismic Bracing Devices for Branch Lines

내진설계용 편심방식 가지배관 고정장치의 좌굴 실험

  • Changsoo, Oh (Fire.Safety Engineering, Woosuk University) ;
  • Jihoon, Kim (YangSoo Metals Co.,Ltd) ;
  • Hasung Kong (Department of Fire and Disaster Prevention, Woosuk University)
  • 오창수 (우석대학교 일반대학원 소방.안전공학과) ;
  • 김지훈 ((주)양수금속) ;
  • 공하성 (우석대학교 소방방재학과)
  • Received : 2024.01.24
  • Accepted : 2024.03.18
  • Published : 2024.03.30

Abstract

Restraints of Branch Lines are used as earthquake-resistant support devices for fire-fighting pipes along with sway brace devices. The central types are aligned and fixed in a straight line with center of the pipe, but the eccentric types are fixed to on side of the pipe, so a bending moment occurs. In this study, three specimens each of central type and eccentric type were installed at an angle of 45° from the vertical and a monotonic compression load of 1340N was applied. All central type samples satisfied 17.8mm of the allowable displacement, but all eccentric type samples failed to meet the target load and buckled. Therefore, when considering the performance of eccentric type restraints, both compressive load and bending moment must be considered. Even through material mechanics calculations, the yield stress of eccentric type - 3/8 inch all threaded steel bolt - exceeds 320Mpa of the allowable stress. A experiment standards need to be established for eccentric type restraints.

Keywords

References

  1. Natinal Fire Agency(2019), Seismic Design Criteria for Fire Protection System in 2019.
  2. H. S. Byun(2021), "A Study on the Structural Analysis of Sway Brace Device." Journal of the Korean Society of Mechanical Technology, 23(4):563-568.
  3. H. S. Kim, J. H. Lee, M. J. Lee(2021), "The Case Study of Load by The Angle of Sway Brace Device for Fire Fighting Pipe." Summer Conference of SAREK, 90-92.
  4. S. U. O, H. J. Lee, S. H. Choa(2022), "Study of Structural Stability and Seismic Performances of 4-Way Sway Prevention Brace." Journal of the Society of Disaster Information, 18(3):646-659.
  5. Q. Shang, L. Qiu, T. Wang, J. Li(2022), "Experimental and analytical study on performance of seismic sway braces for suspended piping systems." Journal of Building Engineering, 57:104826.
  6. Y. J. Na, S. G. Lee(1997), "Critical Loads of Eccentrically Loaded Struts with Thin-Walled Open Sections." Journal of the Computational Structural Engineering Institute of Korea, 9(4):135-140.
  7. KFI(2023), KFI Certification Standard for Sway Brace Device.
  8. B. J. Goodno, J. M. Gere(2017), Mechanics of Materials, SI Edition, 9th Edition. Cengage Learning Korea Ltd, 952-954.
  9. NFPA13(2019), Standard for the Installation of Sprinkler Systems.
  10. UL203A(2019), Sway Brace Devices for Sprinkler System Piping.