DOI QR코드

DOI QR Code

Experimental Capacity of Suspended Piping Trapeze Restraint Installations under Cyclic Loadings

반복하중을 받는 경량 배관 서포트 시스템에 대한 실험적 성능 평가

  • Jeong, Sang-Deock (Division of Architecture and Fire Protection Engineering, Pukyong National University) ;
  • Oh, Chang-Soo (Yang Soo Metals Co., Ltd.) ;
  • Park, Min Jae (Department of Architectural Engineering, Pukyong National University) ;
  • Lee, Chang-Hwan (Department of Architectural Engineering, Pukyong National University)
  • Received : 2023.07.27
  • Accepted : 2023.08.11
  • Published : 2023.09.15

Abstract

Damage to gas and fire protection piping systems can lead to secondary disasters after an earthquake, so their seismic design is crucial. Accordingly, various types of seismic restraint installations are being devised, and a new suspended piping trapeze restraint installation has also recently been developed in Korea. In this study, a cyclic loading test was performed on the developed trapeze support system, and its performance was evaluated according to ASHRAE 171, the standard for seismic and wind restraint design established by the American Society of Refrigeration and Air Conditioning Engineers (ASHRAE). The three support system specimens did not break or fracture, causing only insignificant deformations until the end of the experiment. Based on the experimentally rated strength and displacement performance, this trapeze support system is expected to control the seismic movement of piping during an earthquake.

Keywords

Acknowledgement

본 성과물은 중소벤처기업부에서 지원하는 2021년도 산학연 Collabo R&D사업(No. S3103759)의 연구수행으로 인한 결과물임을 밝힙니다.

References

  1. Filiatrault, A., Perrone, D., Merino, R. J., & Calvi, G. M., "Performance-based seismic design of nonstructural building elements", Journal of Earthquake Engineering, Vol.25, No.2, pp.237~269, 2021. DOI:https://doi.org/10.1080/13632469.2018.1512910
  2. Hong, H. Y., "Seismic design codes and provisions in the U.S. (미국의 내진설계 법규 및 규정)", Magazine of the SAREK, Vol.48, No.7, pp.40~47, 2019.
  3. Baek, G. J., "Seismic design of nonstructural elements in overseas cases (비구조 요소의 해외 내진설계 사례)", Magazine of the SAREK, Vol.48, No.7, pp.52~57, 2019.
  4. Hoehler, M. S., Lutz, C., & Schulze, P., "Testing passive fire-resistance systems for fire following earthquakes", In Proceedings of Structures Congress 2012, Chicago, Illinois, 2012. DOI:https://doi.org/10.1061/9780784412367.120
  5. Tan, J., Michael Ho, S. C., Zhang, P., & Jiang, J., "Experimental study on vibration control of suspended piping system by single-sided pounding tuned mass damper", Applied Sciences, Vol.9, No.2, 285, 2019. DOI:https://doi.org/10.3390/app9020285
  6. Ministry of Land, Infrastructure and Transport (MOLIT), "Seismic Building Design Code (KDS 41 17 00)", MOLIT, 2022.
  7. Perrone, D., Brunesi, E., Filiatrault, A., Peloso, S., Nascimbene, R., Beiter, C., & Piccinin, R., "Seismic numerical modelling of suspended piping trapeze restraint installations based on component testing", Bulletin of earthquake engineering, Vol.18, pp.3247~3283, 2020. DOI:https://doi.org/10.1007/s10518-020-00832-0
  8. Filiatrault, A., Perrone, D., Brunesi, E., Beiter, C., & Piccinin, R., "Effect of cyclic loading protocols on the experimental seismic performance evaluation of suspended piping restraint installations", International Journal of Pressure Vessels and Piping, Vol.166, pp.61~71, 2018. DOI:https://doi.org/10.1016/j.ijpvp.2018.08.004
  9. Wood, R. L., Hutchinson, T. C., Hoehler, M. S., & Kreidl, B., "Experimental characterization of trapeze assemblies supporting suspended nonstructural systems", In Proceedings of Tenth U.S. National Conference on Earthquake Engineering, Anchorage, Alaska, July 2014. DOI:https://doi.org/10.4231/D3D21RJ9J
  10. ASHRAE Standard Committee 2016-2017, "ANSI/ASHRAE Standard 171: Method of Testing for Rating Seismic and Wind Restraints", ANSI, 2017.
  11. Korea Agency for Technology and Standards (KATS), "KS B ISO 898-1: Mechanical properties of fasteners made of carbon steel and alloy steel-Part 1: Bolts, screws and studs", Seoul (Korea), Korean Standards Association, 2023.
  12. Korea Agency for Technology and Standards (KATS), "KS D 3503: Rolled steels for general structure", Seoul (Korea), Korean Standards Association, 2023.
  13. Jeon, J. S., Kim, J. H., Oh, C. S., & Lee, C. H., "Tensile and Shear Strengths of New Type of Cast-in-Place Concrete Insert Anchors Under Monotonic Loading", Journal of Korean Association for Spatial Structures, Vol.21, No.2, pp.49~56, 2021. DOI:https://doi.org/10.9712/KASS.2021.21.2.49
  14. Jeong, S. D., Oh, C. S., & Lee, C. H., "Experimental evaluation of tension and shear capacities of new headed cast-in specialty inserts in cracked concrete", International Journal of Concrete Structures and Materials, Vol.17, 40, 2023. DOI:https://doi.org/10.1186/s40069-023-00605-4
  15. Jeong, S. D., Oh, C. S., & Lee, C. H., "Shear performance evaluation of cast-in specialty inserts in cracked concrete according to cyclic loading patterns", Journal of Korean Association for Spatial Structures, Vol.23, No.2, pp.53~60, 2023. DOI:https://doi.org/10.9712/KASS.2023.23.2.53
  16. CSI (Computers & Structures, Inc.), "CSI Analysis Reference Manual", ETABS version 17, CSI, 2017.
  17. Ministry of Land, Infrastructure and Transport (MOLIT), "Design Standard of Structural Steel Members (LRFD) (KDS 14 31 10)", MOLIT, 2017.
  18. Chen, Y. Z., Cheung, Y. K., & Xie, J. R., "Buckling loads of columns with varying cross sections", Journal of engineering mechanics, Vol.115, No.3, pp.662~667, 1989. DOI:https://doi.org/10.1061/(ASCE)0733-9399(1989)115:3(662)
  19. Arbabi, F., & Li, F., "Buckling of variable cross-section columns: integral-equation approach", Journal of Structural Engineering, Vol.117, No.8, pp.2426~2441, 1991. DOI:https://doi.org/10.1061/(ASCE)0733-9445(1991)117:8(2426)