Monotonic Loading Tests on Seismic Stiffeners for Vertical Hangers

수직 행거 내진설계용 스티프너의 단조 압축 실험

  • Chang-Soo Oh (Fire Protection and Safety Engineering, Woosuk University) ;
  • Ha-Sung Kong (Fire and Disaster Prevention, Woosuk University)
  • 오창수 (우석대학교 일반대학원 소방.안전공학과) ;
  • 공하성 (우석대학교 일반대학원 소방방재학과)
  • Received : 2023.05.23
  • Accepted : 2023.06.11
  • Published : 2023.06.30

Abstract

In piping systems, trapeze hangers are subjected to vertical and horizontal seismic loads and stiffeners are used. In this study, monotonic compression tests were conducted with the removable stiffeners using three variables: stiffener clamp fixing position, section length, and installation direction. The maximum load reinforced with stiffeners could withstand a compressive load of 11kN by applying a safety factor of 10%. It could be estimated that the fixing clamp spacing or the length of shape and load had a proportional relationship. And the stiffener must be fixed in the direction of the strong axis on hinge parts. Also the stiffener buckiling load design proposes to use a method of calculate the flexural buckling compressive strength of and unreinforced full threaded bolt.

Keywords

References

  1. B. T. Park, S. J. Lee, J. H. Lee(2022), "A study on the hysteresis characteristics of stiffener-integrated buckling restrained brace." Journal of Korean Society of Steel Construction, 34(3):161-172. https://doi.org/10.7781/kjoss.2022.34.3.161
  2. S. C. Chen, Y. H. Kim, J. Y. Kim, B. S. Han(2013), "Monotonic loading tests on removable stiffener." Spring Conference of AIK, 33(1):421-422.
  3. J. R. Tauby, R. Lloyd(2011), Practical guide to seismic restraint (2nd ed.). ASHRAE, pp. 88-89.
  4. Hilti Corporation(2014), "Earthquake resistant design of installation. p. I.09.
  5. Nvent Caddy, Instruction sheet; Vertical Rod Stiffener. www.nvent.com
  6. KDS 14 31 10 Korean Building Code(2017).
  7. ANSI/AISC 360(2016), Specification for structural steel buildings.