Seismic response evaluation of 154 kV transformer porcelain bushing by shaking table tests

  • Chun, Nakhyun (Structural and Seismic Tech. Group, KEPCO Research Institute) ;
  • Jeon, Bubgyu (Seismic Research and Test Center, Pusan National University) ;
  • Kim, Sungwan (Seismic Research and Test Center, Pusan National University) ;
  • Chang, Sungjin (Seismic Research and Test Center, Pusan National University) ;
  • Son, Suwon (Department of Architectural and Civil Engineering, Kyungil University)
  • Received : 2022.04.04
  • Accepted : 2022.07.28
  • Published : 2022.10.25

Abstract

The use of electricity and communication between electronic devices is increasing daily, which makes the stability of electrical power supply vital. Since the 1990s, large earthquakes have occurred frequently causing considerable direct damage to electrical power facilities as well as secondary damage, such as difficulty in restoring functions due to the interruption of electric power supply. Therefore, it is very important to establish measures to protect electrical power facilities, such as transformers and switchboards, from earthquakes. In this study, a 154 kV transformer whose service life had expired was installed on the base fabricated by simulating the field conditions and conducting the shaking table tests. The dynamic characteristics and seismic behavior of the 154 kV transformer were analyzed through the resonance frequency search test and seismic simulation test that considers the front, rear, left, and right directions. Since the purpose of this study is to analyze the acceleration amplification in the bushing due to the acceleration amplification, the experimental results were analyzed focusing on the acceleration response and the converted acceleration amplification ratio rather than the failure due to the displacement response of the transformer. The seismic force amplification at the transformer bushing was evaluated by simulating the characteristics of electrical power facilities in South Korea, and compared with the IEC TS 61463 acceleration amplification factor. Finally, the amplification factor at zero period acceleration (ZPA) modified for each return period was summarized. The results of this study can be used as data to define the amplification factor at ZPA of the transformer bushing, simulating the characteristics of electrical power facilities in Korea.

Keywords

References

  1. Cao, M., Cheng, Y., Dai, Z., Zhou, F. and Tan, P. (2012), "Parameter analysis and shaking table test on seismic isolation system of transformer with bushings", Proceedings of the 15th World Conference on Earthquake Engineering, Lisboa, Portugal.
  2. Dinh, N.H., Lee, S.J., Kim, J.Y. and Choi, K.K. (2020), "Study on seismic performance of a mold transformer through shaking table tests", Appl. Sci., 10, 361. https://doi.org/10.3390/app10010361.
  3. Filiatrault, A. and Matt, H. (2005), "Experimental seismic response of high-voltage transformer-bushing systems", Earthq. Spectra, 21(4), 1009. http://doi.org/10.1193/1.2044820.
  4. Filiatrault, A. and Matt, H. (2006), "Seismic response of high voltage electrical transformer-bushing systems", J. Struct. Eng., 132(2), 287-295 https://doi.org/10.1061/(ASCE)0733-9445(2006)132:2(287).
  5. Fujisaki, E., Takhirov, S., Xie, Q. and Mosalam, M.K. (2014), "Seismic vulnerability of power supply: Lessons learned from recent earthquakes and future horizons of research", Proceedings of the 9th International Conference on Structural Dynamics, EURODYN 2014, Porto, Portugal, June-July.
  6. Gilani, A., Chavez, J., Fenves, G. and Whittaker, A. (1998) "Seismic evaluation of 196-kV porcelain transformer bushings", PEER Report 1998/02, University of California, Berkeley, CA, USA.
  7. Gilani, A., Chavez, J., Fenves, G. and Whittaker, A. (1999), "Seismic evaluation of 550kV porcelain transformer bushings", PEER, 1999.
  8. Gilani, A., Whittaker, A. and Fenves, G. (1999) "Seismic evaluation and retrofit of 230-kV porcelain transformer bushings", PEER Report 1999/14, University of California, Berkeley, CA, USA.
  9. Gilani, A., Whittaker, A. and Fenves, G. (1999), "Seismic evaluation of 550 kV porcelain transformer bushings", PEER Report 1999/05, University of California, Berkeley, CA, USA.
  10. Gilani, A., Whittaker, A. and Fenves, G. (2001), "Seismic evaluation and retrofit of 230-kV porcelain transformer bushings", Earthq. Spectra, 17(4), 597. http://doi.org/10.1193/1.1427316.
  11. He, C., Xie, Q. and Zhou, Y. (2018), "Influence of flange on seismic performance of 1100 kV UHV transformer bushing", Earthq. Spectra, 35(2), 611. http://doi.org/10.1193/012918EQS029M.
  12. Hwang, K.M., Ham, K.W. and Kim, G.H. (2018), "The experimental study on seismic capacity of 154 kV & 345 kV main transformer bushings", J. Earthq. Eng. Soc. Korea, 22(2), 87-94. (in Korean) https://doi.org/10.5000/EESK.2018.22.2.087
  13. Institute of Electrical and Electronics Engineers (2013), IEEE 344, Standard for Seismic Qualification of Equipment for Nuclear Power Generating Stations.
  14. Institute of Electrical and Electronics Engineers. (2005), IEEE Recommended Practice for Seismic Design of Substations, IEEE Std 693.
  15. International Code Council Evaluation Services Acceptance Criteria 156 (2010), ICC-ES AC156, Acceptance Criteria for Seismic Certification by Shake-table Testing of Nonstructural Components.
  16. International Electrotechnical Commission (IEC). (2016), Technical Specification: IEC TS 61463:2016-Bushing-Seismic Qualification, Section 7.
  17. Jang, J.B., Kim, J.K., Hwang, K.M., Ham, K.W., Park, J.W. and Lee, C.W. (2008), "Experimental study of friction pendulum system to improve the seismic capacity of transformer", J. Earthq. Eng. Soc. Korea, 12(2), 1-8. (in Korean)
  18. Joe, Y.H. and Cho, S.G. (2006) "Modal identification and seismic performance evaluation of 154 kV transformer porcelain bushing by vibration test", J. Earthq. Eng. Soc. Korea, 10(5), 107-115. (in Korean) https://doi.org/10.5000/EESK.2006.10.5.107
  19. KEPCO (Korea Electric Power Cooperation) (2021), Earthquake Resistant Design Guideleines of Transmission, Substation and Distribution Facilities, Korea. (in Korean)
  20. Lee, D. and Constantinou, M.C. (2018), "Combined horizontal-vertical seismic isolation system for high-voltage-power transformers: Development, testing and validation", Bull. Earthq. Eng., 16, 4273-4296. https://doi.org/10.1007/s10518-018-0311-2.
  21. Liu, R.S., Zhang, M.J. and Wu, Y.B. (2012), "Vulnerability study of electric power grid in different intensity area in wenchuan earthquake", Proceedings of the 15th World Conference on Earthquake Engineering, Lisboa, Portugal.
  22. Matt, H. and Filiatrault, A. (2004), "Seismic qualification requirements for transformer bushings", Research Project Report No. SSRP-2003-12, Department of Structural Engineering, University of California, San Diego, La Jolla, CA, USA.
  23. Murota, N., Feng, M.Q. and Liu, G.Y. (2006), "Earthquake simulator testing of base-isolated power transformers", IEEE Trans. Power Deliv., 21(3), 1291-1299. https://doi.org/10.1109/TPWRD.2006.874586.
  24. The Ministry of Interior & Safety (2017), Common Application of Seismic Design Criteria, April.
  25. UBC97 (1997), Uniform Building Code, International Code of Building Officials (ICBO), California, USA.
  26. Villaverde, R. and Pardoen, G. (1999), "Ground mtion amplication at base of bushings mounted on electric substation transformer", A Technical Report of Research Supported by PEER/PG&E Under Award No. PGE-09566, Department of Civil Engineering, University of California, Irvine, USA.
  27. Whittaker, A.S., Fenves, G.L. and Gilani, A.S.J. (2004), "Earthquake performance of porcelain transformer bushings", Earthq. Spectra, 20(1), 205-223 https://doi.org/10.1193/1.1647578.
  28. Wilcoski, J. (1997), "Demonstration of CERL equipment fragility and protection procedure by fragility testing of a power transformer bushing", ATC-29-1, Seminar Technical Papers.
  29. Xie, Q., He, C. and Zhou, Y. (2019), "Seismic evaluation of ultra-high voltage wall bushing", Earthq. Spectra, 35(2), 611. http://doi.org/10.1193/012918EQS029M.
  30. 日本電気協会(2010). 変電所等における電気設備の耐震設計指針, JEAG 5003-2010.