DOI QR코드

DOI QR Code

UPQC-based effective mitigation of harmonics by signal processing approach

  • Nagarajan, Ananthan (Department of Electrical and Electronics Engineering, Vel Tech Multi Tech Dr. Rangarajan Dr. Sakunthala Engineering College) ;
  • Suganyadevi, M.V. (Department of Electrical and Electronics Engineering, Saranathan College of Engineering)
  • Received : 2021.08.21
  • Accepted : 2021.12.02
  • Published : 2022.03.20

Abstract

This paper introduces a solution for solving the harmonics problem in power distribution systems. The unified power quality conditioner (UPQC) is a combination of shunt and series converters linked by a common capacitor. Controlling the link voltage and generating the reference current are the two main objectives of this work. An adaptive PI controller is employed for regulating the link voltage. For reference current generation, the DDSRF (decoupled double synchronous reference frame) theory is employed, which assists in eliminating the harmonics that occur in the system. By the DDSRF theory, a THD of around 3.3% is accomplished, and to further minimize the harmonics, a signal processing approach is implemented. Pre-processing, segmentation and feature extraction are the three major steps used in this paper to accurately extract the reference current. Finally, the obtained test data is classified with the trained data by the DCNN (deep convolutional neural network). Thus, the reference current is extracted clearly by this technique, and the THD is minimized to 0.98%. This work is implemented in MATLAB, and the results are verified through hardware implementation.

Keywords

References

  1. Jian Han; Xing Li; Yan Jiang; Shaonan Gong: Three-Phase UPQC Topology Based on Quadruple-Active-Bridge. IEEE Access 9, 4049-4058 (2021) https://doi.org/10.1109/ACCESS.2020.3047961
  2. Nagarajan, A., Sivachandran, P., Suganyadevi, M.V., Muthukumar, P.: A study of UPQC: emerging mitigation techniques for the impact of recent power quality issues. Circuit World 47(1), 11-21 (2021) https://doi.org/10.1108/cw-09-2019-0125
  3. Kalair, A., Abas, N., Kalair, A.R., Saleem, Z., Khan, N.: Review of harmonic analysis, modeling and mitigation techniques. ELSEIVER Renew. Sustain. Energy Rev. 78, 1152-1187 (2017) https://doi.org/10.1016/j.rser.2017.04.121
  4. Choi, W., Lee, W., Han, Di., Sarlioglu, B.: New confguration of multifunctional grid-connected inverter to improve both currentbased and voltage-based power quality. IEEE Trans. Ind. Appl. 54(6), 6374-6382 (2018) https://doi.org/10.1109/tia.2018.2861737
  5. Liao, H., Abdelrahman, S., Milanovic, J.V.: Zonal mitigation of power quality using FACTS devices for provision of differentiated quality of electricity supply in networks with renewable generation. IEEE Trans. Power Deliv. 32(4), 1975-1985 (2017) https://doi.org/10.1109/TPWRD.2016.2585882
  6. Elmetwaly, A.H., Eldesouky, A.A., Sallam, A.A.: An adaptive D-FACTS for power quality enhancement in an isolated microgrid. IEEE Access 8, 5923-57942 (2020)
  7. Rajendran, M.: Comparison of various control strategies for UPQC to mitigate PQ issues. Springer-J. Inst Eng. (India): Series, B 102, 19-29 (2020) https://doi.org/10.1007/s40031-020-00502-4
  8. Nagarajan, A., Sivachandran, P., Suganyadevi, M.V.: Performance comparison of UPQC for improving the power quality with industrial controller techniques. J. Huazhong Univ. Sci.Technol. 50(4), 13 (2021)
  9. Nagarajan, A., Sivachandran, P., Suganyadevi, M.V.: Performance comparison of L-UPQC and R-UPQC with FUZZY logic controller for power quality improvement. Int. J. ChemTech Res. 11(4), 92-100 (2018)
  10. Ikramullah, Ashraf, M., Rehman, A.: Comparison of reference current generation techniques for shunt active power filter. In: 5th International Conference on Electrical and Electronic Engineering (ICEEE) (2018)
  11. Karbasforooshan, M.-S., Monfared, M.: An improved reference current generation and digital deadbeat controller for single-phase shunt active power filters. IEEE Trans. Power Deliv. 35(6), 2663- 2671 (2020) https://doi.org/10.1109/TPWRD.2020.2974155
  12. Dongre, G.A., Choudhari, V. V., Diwan, S. P.: A comparison and analysis of control algorithms for Shunt Active Power Filter. In: International Conference on Computation of Power, Energy, Information and Communication (ICCPEIC) (2015)
  13. Chen, D., Xiao, L.: A novel fundamental and harmonics detection method based on state-space model for power electronics system. IEEE Access 8, 170002-170012 (2020) https://doi.org/10.1109/access.2020.3024178
  14. Alam, S.J., Arya, S.R.: Control of UPQC based on steady state linear Kalman filter for compensation of power quality problems. Chin. J. Electr. Eng. 6(2), 52-65 (2020) https://doi.org/10.23919/cjee.2020.000011
  15. Axente, I., Basu, M., Conlon, M.F.: DC link voltage control of UPQC for better dynamic performance. Electr. Power Syst. Res. 81(9), 1815-1824 (2011) https://doi.org/10.1016/j.epsr.2011.05.005