IT전력밀도에 따른 기축 데이터센터의 리모델링을 위한 설비시스템 계획방법에 관한 사례연구

A Case Study on Remodeling Strategies of Mission Critical Facility for Existing Data Centers Based on IT Power Density

  • 조진균 (국립한밭대 설비공학과) ;
  • 박우평 (강남대 부동산건설학부 건축공학전공 / 경기대학교 대학원 건축공학과)
  • Cho, Jinkyun (Dept. of Building and Plant Engineering, National Hanbat University) ;
  • Park, Woopyeng (Division of Real Estate and Construction Engineering, Kangnam University / Graduate School of Architecture, Kyonggi University)
  • 투고 : 2022.02.21
  • 심사 : 2022.04.22
  • 발행 : 2022.05.30

초록

Numerous data centers have been built and operated since 2000. Now that 20 years have passed, a growing need for remodeling that involves shifting to a new IT environment, upgrading IT equipment, and replacing outdated facility infrastructure is escalating. In this study, three basic independent non-IT system modules for a total IT load of 150 kW were derived to respond to low-density, medium-density, and high-density rack-server configurations according to the IT power density known as a key element of a data center. Additionally, a data center's cooling strategies were analyzed according to its IT power density. As of 2021, the average IT power density of global data centers was surveyed at the level of 7.8-8.4 kW/rack that involved more than 400 samples. Data center cooling was divided into a room-based cooling for low-density, row-based cooling for medium-density, and rack-based cooling for a high-density IT load. Compared to the ALT-1 of a low-density model, the required area was reduced by 30% for the medium-density model and 55% for the high-density model. As a result of the remodeling cost analysis, the cost increased to 105% for the ALT-2 and 119% for the ALT-3 based on the ALT-1 being 100%. The criterion for data center remodeling is to comprehensively consider the required space, cooling energy efficiency, and construction cost based on the IT power density.

키워드

참고문헌

  1. AFCOM (2021). The 2021 state of the data center report: A look at the evolution of our industry 5th edition, The Association for Computer Operations Management.
  2. ASHRAE TC 9.9. (2004). Thermal guidelines for data processing environments, American Society of Heating Refrigerating and Air-Conditioning Engineers.
  3. ASHRAE TC 9.9. (2021). Thermal guidelines for data processing environments 5th edition, American Society of Heating Refrigerating and Air-Conditioning Engineers.
  4. Bash, C.E., Patel, C.D. & Sharma, R.K. (2003). Efficient thermal management of data centers- Immediate and long-term research needs, HVAC&R Research, 9(2), 137-152. https://doi.org/10.1080/10789669.2003.10391061
  5. Beaty, D.L. (2013). Internal IT load profile variability, ASHRAE Journal, 55(2), 72-74.
  6. Cho, J. (2021a). An analysis of the data center energy consumption structure for efficient energy utilization, Journal of the Architectural Institute of Korea, 37(8), 153-164. https://doi.org/10.5659/JAIK.2021.37.8.153
  7. Cho, J. (2021b). Hot-aisle and cold-aisle containment - comparing thermal performance for data center cooling, ASHRAE Journal, 63(8), 44-56.
  8. Cho, J., Jeong, C., & Kim, B.S. (2006). A study on equipment power trends and heat loads for the optimal IT environment control in the (internet) data center, Journal of the Architectural Institute of Korea, Planning and Design Section, 22(9), 315-322.
  9. Cho, J., & Kim, B.S. (2011). Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers, Energy and Buildings, 43(9), 2145-2155. https://doi.org/10.1016/j.enbuild.2011.04.025
  10. Cho, J., Kim, S., Park, B., & Jeong, Y. (2020). A study on performance standard and test method of CRAC/H units for data centers, Korean Journal of Air-Conditioning and Refrigeration Engineering, 32(5), 235-248. https://doi.org/10.6110/kjacr.2020.32.5.235
  11. Cho, J., & Kim, Y. (2016). Improving energy efficiency of dedicated cooling system and its contribution towards meeting an energy-optimized data center, Applied Energy, 165, 967-982. https://doi.org/10.1016/j.apenergy.2015.12.099
  12. Cho, J., & Kim, Y. (2021). Development of modular air containment system: thermal performance optimization of row-based cooling for high-density data centers, Energy, 231, 120838. https://doi.org/10.1016/j.energy.2021.120838
  13. Cho, J., Park, B., Jeong, Y., & Go., M.G. (2021). An Empirical Study on Cooling Performance Evaluation of Independent Modular Air Containment and Row-based Cooling System for High-Density Data Centers, Korean Journal of Air-Conditioning and Refrigeration Engineering, 33(10), 494-505. https://doi.org/10.6110/KJACR.2021.33.10.494
  14. Cho, J., Park, C., & Choi, W. (2021). Numerical and experimental study of air containment systems in legacy data centers focusing on thermal performance and air leakage, Case Studies in Thermal Engineering, 26, 101084. https://doi.org/10.1016/j.csite.2021.101084
  15. Cho., J., & Shin, S. (2012). Power and heat load of IT equipment projections for new data center's HVAC system design, Korean Journal of Air-Conditioning and Refrigeration Engineering, 24(3), 212-217. https://doi.org/10.6110/KJACR.2012.24.3.212
  16. Cho, J., Suh, W., & Woo, J. (2020). CFD-based Comparison Study of Hot Aisle Containment and Cold Aisle Containment Solutions in High-density Data Centers, Korean Journal of Air-Conditioning and Refrigeration Engineering, 32(9), 419-434. https://doi.org/10.6110/kjacr.2020.32.9.419
  17. Cho, J., & Woo, J. (2020). Development and experimental study of an independent row-based cooling system for improving thermal performance of a data center, Applied Thermal Engineering, 169, 114857. https://doi.org/10.1016/j.applthermaleng.2019.114857
  18. Cisco public (2018), Cisco Visual Networking Index: Forecast and Trends, 2017-2022, White paper, Cisco.
  19. Cottuli, C. (2014). Comparison of static and rotary UPS, APC white paper 92 rev02, Schneider Electric-Data Center Science Center.
  20. Dunlap, K., & Rasmussen, N. (2012). Choosing between room, row, and rack-based cooling for data centers, APC white paper 130 rev02, Schneider Electric-Data Center Science Center.
  21. Ghatikar, G., Piette, M.A., Fujita, S., McKane, A., Dudley, J.H., Radspieler, A. Mares, K.C., & Shroyer, D. (2010). Demand Response and Open Automated Demand Response Opportunities for Data Centers, Ernest Orlando Lawrence Berkeley National Laboratory.
  22. Herrlin, M.K. (2005). Rack cooling effectiveness in data centers and telecom central offices: the rack cooling index (RCI), ASHRAE Transactions, 111(Part 2), 725-731.
  23. Herrlin, M.K. (2008). Airflow and cooling performance of data centers: two performance metrics, ASHRAE Transactions, 114(Part 2).
  24. Jiang, K., Kheradmandi, M., Hu, C., Pal, S., & Yan, F. (2021). Data-driven fault tolerant predictive control for temperature regulation in data center with rack-based cooling architecture, Mechatronics, 79, 102633. https://doi.org/10.1016/j.mechatronics.2021.102633
  25. KDCC. (2021). Korea data center market 2021-2024, Korea Data Center Council.
  26. Kim, J. (2021). Rapid growth of the data center market: main factors and prospects, Koscom news room (Updated December 21, 2021).
  27. Lin, P., & Avelar, V. (2014). How row-based data center cooling works, APC white paper 208, Schneider Electric-Data Center Science Center.
  28. Moreno-Munoz, A., Gonzalez de la Rosa, J.J., Pallares-Lopez, V., Real-Calvo, R.J., & Gil-de-Castro, A. (2011). Distributed DC-UPS for energy smart buildings, Energy and Buildings, 43(1), 93-100. https://doi.org/10.1016/j.enbuild.2010.08.018
  29. Niemann, J., Brown, K., & Avelar V. (2011). Hot-aisle vs. cold-aisle containment for data centers, APC White Paper 135 rev02, Schneider Electric-Data Center Science Center.
  30. Rasmussen, N., & Niles, S. (2012). Data center projects: standardized process, APC white paper 140 rev01, Schneider Electric-Data Center Science Center.
  31. Sharma R.K., Bash C.E., & Patel C.D. (2002). Dimensionless parameters for evaluation of thermal design and performance of large scale data centers, in American Institute of Aeronautics and Astronautics (AIAA), 3091-3100.
  32. Tao, D., Xiaoxuan C., Hanwen, C., Zhiguang, H., Jianmin, W., & Zhen, L. (2021). Principles of loop thermosyphon and its application in data center cooling systems: A review, Renewable and Sustainable Energy Reviews, 150, 111389. https://doi.org/10.1016/j.rser.2021.111389
  33. Uptime Institute (2021). the 10th annual Uptime Institute global survey of IT and data center managers.
  34. VanGilder, J., & Torell, W. (2019). Cooling entire data centers using only row cooling, APC white paper 139 rev01. Schneider Electric-Data Center Science Center.
  35. Xiaoqing, S., Zongwei H., & Xiuming, L. (2022). Simulation study on cooling effect of two-phase liquid-immersion cabinet in data center, Applied Thermal Engineering, 207, 118142. https://doi.org/10.1016/j.applthermaleng.2022.118142
  36. Xie, M., Wang, J., & Liu, J. (2019). Evaluation metrics of thermal management in data centers based on exergy analysis, Applied Thermal Engineering, 147, 1083-1095. https://doi.org/10.1016/j.applthermaleng.2018.10.137
  37. Zhan, B., Shao, S., Zhang, H., & Tian, C. (2020). Simulation on vertical microchannel evaporator for rack-backdoor cooling of data center, Applied Thermal Engineering, 164, 114550. https://doi.org/10.1016/j.applthermaleng.2019.114550