DOI QR코드

DOI QR Code

According to PCM Application in Radiant Floor Heating System Temperature Change and Energy Consumption Comparison Mock-up Experiment

바닥복사난방시스템에서 PCM 적용에 따른 온도 변화 및 에너지 사용량 비교 Mock-up 실험

  • 정용기 (중앙대학교 건축공학과) ;
  • 김성은 (중앙대학교 건축공학과) ;
  • 유민상 (중앙대학교 건축공학과) ;
  • 박진철 (중앙대학교 건축공학과)
  • Received : 2021.12.07
  • Accepted : 2022.01.14
  • Published : 2022.01.30

Abstract

In this study, as a method to reduce the energy consumption of the radiant floor heating system, the heating energy reduction was studied using PCM, a latent heat storage device. A 44℃ PCM was installed under the heating pipe of the mock-up laboratory with the standard floor structure applied, and the temperature change and energy consumption according to the PCM application were compared through the experiment. For the experiment, two mock-up laboratories of the same standard were established outdoors. A general radiant floor heating system and a PCM system were applied to each laboratory, and the indoor air temperature, floor surface temperature, heating hot water temperature, and heating energy consumption were measured to compare the temperature change and energy consumption of each room. As a result of the experiment, when PCM was applied, both the time to reach the maximum temperature from the start of heating operation decreased in the case of indoor air temperature and floor surface temperature. As a result of comparison of hot water temperature, it was confirmed that when PCM was applied, heating was operated for a shorter time, and heating energy consumption was also reduced.

Keywords

Acknowledgement

이 연구는 2021년도 한국연구재단 연구비 지원에 의한 결과의 일부임. 과제번호:NRF-2016R1D1A1B01015616

References

  1. Akihiro, T. Yoon, C. S. Kazuo, F., & Chung, Y. S. (1999). A comparative study on thermal responses of male and female in thermal environmental conditions in floor heating system. Journal of the Architectural Institute of Korea Planning & Design, 15(5), 127-134.
  2. Belen, Z., Jose, M. M., Luisa, F. C., & Harald, M. (2003). Review on thermal energy storage with phase change: materials, heat transfer analysis and applications. Applied Thermal Engineering, 23(3), 251-283. https://doi.org/10.1016/S1359-4311(02)00192-8
  3. Cho, S., & Sohn, J. Y. (1992). Indoor air temperature distribution in a floor heating space with PCM panels. Journal of the Korea Solar Energy Society, 12(1), 59-71.
  4. Choi, S. H., Kim, S. E., Song, Y. W., & Park, J. C. (2020). Mock-up experiment on temperature variation according to PCM position in radiant floor heating system. Journal of the Architectural Institute of Korea, 36(10), 127-132. https://doi.org/10.5659/JAIK.2020.36.10.127
  5. Jeon, J. S., Lee, J. H., Seo, J. K., Jeong, S. G., & Kim, S. M. (2012). Application of PCM thermal energy storage system to reduce building energy consumption. Journal of Thermal Analysis and Calorimetry, 111, 279-288. https://doi.org/10.1007/s10973-012-2291-9
  6. KICT, (1996). Thermal performance improvement of floor heating system in apartment housing, 1-213.
  7. Kim, T. W. (2019). A Mock-up Test of Thermal Storage Performance for PCM Radiant Floor Heating System, Thesis, Chung-Ang University Graduate School.
  8. Kum, J. S., & Kim, K. C. (1993). A study on performance evaluation of floor heating system using phase change material and night time electricity. Journal of the Architectural Institute of Korea, 9(3), 113-122.
  9. Lin, K., Zhang, Y., Xu, X., Di, H. Yang, R., & Qin, P. (2005). Experimental study of under-floor electric heating system with shape-stabilized PCM plates. Energy and Building, 37(3), 215-220. https://doi.org/10.1016/j.enbuild.2004.06.017
  10. Ministry of Environment. (2010). The 2030 National Greenhouse Gas Reduction Target (NDC) is raised, 1-37
  11. Ministry of Health and Welfare. (2018). Korea Centers for Disease Control and Prevention, Health Tips for cold Weather- Have a Healthy Winter.
  12. Ministry of Trade, Industry and Energy. (2019). Energy Efficiency Innovation Strategy, 1-29.
  13. Roberta, A. Larghtti, R., Giretti, A., & Lemma, M. (2011). Radiant floors integrated with PCM for indoor temperature control. Energy and Building, 45(11), 3019-3026.
  14. Soares, N., Costa, J. J., Gaspar, A. R., & Santos, P. (2013). Review of passive PCM latent heat thermal energy storage systems towards buildings' energy efficiency. Energy and Buildings, 59, 82-103. https://doi.org/10.1016/j.enbuild.2012.12.042
  15. Yiping, Z., Guobing, Z., Kunping, L., Qunli, Z., & Hongfa, D. (2007) Application of latent heat thermal energy storage in buildings: State-of-the-art and outlook. Building and Environment, 42(6), 2197-2209. https://doi.org/10.1016/j.buildenv.2006.07.023