Analysis of Heating and Domestic Hot Water Load for Adjusting the Output Range of Individual Gas-fired Boilers for Low-Energy Apartment Buildings

저에너지 공동주택 개별보일러의 출력범위 조절을 위한 난방 및 급탕부하 분석

  • 김상엽 (부경대학교 대학원 건축소방공학부) ;
  • 장형문 (부경대학교 융복합인프라기술연구소) ;
  • 김찬희 (부경대학교 건축공학과) ;
  • 최지수 (부경대학교 대학원 건축소방공학부) ;
  • 이규남 (부경대학교 건축공학과) ;
  • 정근주 (부경대학교 건축공학과)
  • Received : 2021.07.01
  • Accepted : 2021.11.08
  • Published : 2021.11.30

Abstract

In Korea, it is common to determine the capacity of individual gas-fired boilers based on the floor area or unit heating load of residential buildings. With this approach, the current tendency of heating load reduction can not be taken into account when sizing the individual gas-fired boilers for low-energy apartment buildings. Most of the low-energy apartment buildings might be equipped with over-sized boilers, which would cause the boiler to operate with low efficiency particularly under part load conditions. As the over-sized boilers can deteriorate the energy saving performance of low-energy apartment buildings, this study was conducted to suggest the necessity of adjusting the output range of individual gas-fired boilers. For this purpose, heating and domestic hot water load of apartment buildings were analyzed considering the historical change of energy saving design standards. The analyzed loads were compared with the output range of household gas-fired boilers currently available on the market. The results showed that the heating output of the boilers is over-sized, even though the heating load has been reduced by 53%. It was found that the part-load output of boilers was significantly higher than the heating load, which would lead to the reduced efficiency during the part load conditions. It was also found that the individual room control can increase the difference between the boiler part-load output and heating load. Therefore, it is necessary to adjust the output range of boilers by lowering the part-load output and to increase the turn-down ratio of boilers in order to improve the energy efficiency of low-energy apartment buildings.

Keywords

Acknowledgement

이 연구는 2019년도 한국연구재단 연구비 지원에 의한 결과의 일부임. 과제번호:NRF-2019R1A2C1010515

References

  1. Hong, H., & Kim, Y. (2011). Control and Thermal Comfort by Low Temperature Ondol Heating. Korean Journal of Air-Conditioning and Refrigerating Engineers, 62-65.
  2. KEEI, Energy Consumption Survey (2017), Korea Energy Economics Institute.
  3. Kim, J. (2013). Architectural Equipments, 2nd ed., Seowoo Books, Seoul, Korea, 106-107
  4. Lee, C., Kum, S., Jeong, Y., & Lee, G. (2001). A study on the Development of Low NOx Condensing Gas Boiler (I) -Design of Cylindrical Multi-Hole Premixed Burner-. The Korean Society of Mechanical Engineers-B, 25(2), 235-243.
  5. LH, Design Criteria for Heating Facility (2018). Land and Housing Corporation.
  6. Li, L. (2016). Analysis on the Operation Characteristics and Heating Energy Consumption of Individual Boiler According to Heating Capacity of Radiant Floor Heating System, (Doctoral dissertation, Graduate School Seoul National University).
  7. MOLIT, Standard for green building certification (2013). Ministry of Land, Infrastructure and Transport Notice No.2013-383.
  8. MOLIT, Building Energy Saving Design Standards (2018). Ministry of Land, Infrastructure and Transport.
  9. MOLIT Statistics System, APT House Living Condition Statistics (2018). Ministry of Land, Infrastructure and Transport, Statistics System, available at "http://stat.molit.go.kr", accessed on 20th September, 2021.
  10. MOLIT, Enforcement rule of the regulation for equipment in building (2020). Ministry of Land, Infrastructure and Transport Decree No.715.
  11. Osman, K., & Lane, N. (2020). Five Design Factors To Help Optimize A Boiler Plant. ASHRAE Journal, 62(9), 14-19.
  12. Rhee, K., & Jung, G. (2020). Improvement Methods of Individual Boiler Heat Source considering Reduced Heating Load of Low-Energy Apartment Buildings, Journal of Korean Institute of Architectural Sustainable Environment and Building Systems, 14(1), 124-135.
  13. Yang, K., Rhee, K., Ryu, S., Yeo, M., & Kim, K. (2008). A Study on the Thermal Performance Simulation Considering Hydronic Analysis for Radiant Floor Heating System. Journal of the Architectural Institute of Korea, Planning and Design Section, 24(12), 321-328.
  14. Yu, B., Seo, B., Moon, J., & Lee, K. (2015). Analysis of the Part Load Ratio Characteristics and Gas Energy Consumption of a Hot Water Boiler in a Residential Building under Korean Climatic Conditions. Korean Journal of Air-Conditioning and Refrigerating Engineers, 27(9), 455-462. https://doi.org/10.6110/KJACR.2015.27.9.455
  15. Yu, J., Shin, S., & Cho, D. (2015). An Analysis on Heating Energy Use and Economic Evaluation of Passive Apartments Compared to Existing Apartments -Focused on the Zero Carbon Green Home-. Journal of Real Estate Analysis, 1(1), 111-132. https://doi.org/10.30902/jrea.2015.1.1k.111