Abstract
Shunt reactor, a facility for reactive power compensation, is switched several times a day depending on the load pattern. When the circuitbreaker opens the shunt reactor over-voltage is generated by several factors which degrade the insulating performance of internal parts of the circuit-breaker and cause severe voltage stress on the equipment in the power system. Transient phenomenon occurring during the switching of shunt reactor are available in laboratories that verify the performance of the circuit-breaker by simulating the power system. However, it is difficult to measure the transient phenomenon that occurs during actual operation in actual power system due to many limitations. Therefore, this paper deals with the modeling using EMTP to analyze the reignition and current chopping which causes more severe transient recovery voltage in the small inductive current breaking in actual power systems. In addition, this paper analyzes the main phenomenon that cause circuit-breaker failure in opening shunt reactor using EMTP model.
무효전력 보상설비인 분로리액터는 전력계통의 부하 패턴에 따라서 하루에도 수 회 정도 차단기에 의해 운전되거나 정지된다. 분로리액터개폐 시 몇 가지 요인에 의해 발생하는 과전압은 차단기의 절연 성능을 저하시키며, 계통을 구성하는 전력기기에 심각한 전압 스트레스를 유발한다. 분로리액터 개폐 과정에서 발생하는 과도현상을 측정하는 것은 계통을 모의하여 차단기 성능을 검증하는 시험소 수준에서는 가능하나, 실제 계통 운전 중에 발생하는 과도현상을 측정하는 것은 여러 가지 제약으로 어려움이 있다. 따라서 본 논문에서는 실 계통에서 지상 소전류 차단과정에서 가혹한 과도회복전압(TRV: Transient Recovery Voltage)을 유발하는 재발호(reignition)나 전류재단(current chopping) 현상에 대한 해석을 위해 전자계과도해석프로그램(EMTP: Electro-magnetic Transients Program)을 활용한 모델링 과정과 이를 토대로 분로리액터 개폐 과정에서 차단기의 고장을 유발하는 주된 현상에 대해 해석하고자 한다.