DOI QR코드

DOI QR Code

Comparison of Heat Pump Performance and Energy Consumption Patterns according to Heat Sources for Optimal Control of Multi-Source Heat Pumps

복합열원 히트펌프 최적 제어를 위한 열원에 따른 히트펌프 성능 및 에너지 소요량 패턴 비교

  • Ko, Yujin (Department of Mechanical Engineering, KyungHee University) ;
  • Park, Sihun (Lab. Thermal Environment Control, KyungHee University) ;
  • Min, Joonki (Department of Mechanical Engineering, KyungHee University)
  • 고유진 (경희대학교 기계공학과) ;
  • 박시훈 (경희대학교 열환경제어연구실) ;
  • 민준기 (경희대학교 기계공학과)
  • Received : 2020.11.06
  • Accepted : 2020.11.27
  • Published : 2020.12.01

Abstract

The investment in the technology of using a combined heat source is insufficient, which utilizes the advantages of various heat sources to maximize the potential energy and at the same time increases the performance of the heat pump. In this study, as basic data for the development of a high-efficiency hybrid heat pump system that actively connects and uses various heat sources, simulations were conducted for the heat pumps in two cases where geothermal and hydrothermal heat were applied respectively. In May, COP increased by about 27.3% compared to geothermal heat. In February, the COP percentage decrease of hydrothermal heat compared to geothermal heat is -6.9%. In May, total energy consumption can be reduced by 21.1% when hydrothermal is applied compared to geothermal heat. In February, the total energy consumption increases by 3.4%.

Keywords

Acknowledgement

이 논문은 2020년도 정부(환경부 환경기술개발사업)의 재원으로, 한국환경산업기술원의 지원을 받아 수행된 연구임. (No. 2020003160021, 수열에너지를 효과적으로 활용하기 위한 능동형 고효율 하이브리드 히트펌프 개발)

References

  1. Ministry of Trade, Industry and Energy, 2020, Energy Use Rationalization Act of Public Institutions, MOTIE criteria 2020-134.
  2. Bae, S., Jeong, Y., and Nam, Y., 2018, Performance Analysis of Hybrid System with PVT and GSHP for Zero Energy Building, J. Korea Inst. Ecol. Archit. And Environ., Vol. 18, No. 5, pp. 85-92.
  3. Bae, S., Kim, H., Jeon, J. Y., and Nam, Y., 2018, Sensitivity Analysis of the Design Factor for Vertical Closed-loop Geothermal System using Numerical Analysis, KIEAE Journal, Vol. 18, No. 5, pp. 55-61. https://doi.org/10.12813/kieae.2018.18.5.055
  4. Lee, D. Y., Choi, J. H., Min, K. C., and Sohn, B., 2016, Performance Simulation of Geothermal Heat Pump (GHP) System with Different Control Schedules, Trans. Korean Soc. Mech. Eng. C, Vol. 4, No. 1, pp. 35-41.
  5. Kang, E. C., Min, K. C., Lee, K. S., and Lee, E. J., 2016, Analysis Study of Seasonal Performance Factor for Residential Building Integrated Heat Pump System, Trans. Korean Soc. Mech. Eng. C, Vol. 4, No. 1, pp. 3-10.
  6. Ministry of Trade, Industry and Energy, 2019, Enforcement Decree of the Act on the Promotion of the Development, Use and Diffuse of New and Renewable Energy,
  7. Klein, S. A., 2019, TRNSYS18 Base Manual, KES Tech, Kocaeli, Turkey.
  8. Ministry of Land, Infrastructure and Transport, 2017, Standard of Building Saving, MLIT criteria 2017-881.
  9. Ministry of Land, Infrastructure and Transport, 2017, Standard of Building Saving, MLIT criteria 2017-881.
  10. Korea Energy Agency, 2020, Regulations on support for new and renewable energy facilities, etc., KEA criteria 2020-05.