DOI QR코드

DOI QR Code

Analytical investigation on lateral load responses of self-centering walls with distributed vertical dampers

  • Huang, Xiaogang (Key Laboratory of Concrete and Prestressed Concrete Structures of the Ministry of Education, Southeast University) ;
  • Zhou, Zhen (Key Laboratory of Concrete and Prestressed Concrete Structures of the Ministry of Education, Southeast University) ;
  • Zhu, Dongping (Key Laboratory of Concrete and Prestressed Concrete Structures of the Ministry of Education, Southeast University)
  • Received : 2019.04.10
  • Accepted : 2019.06.12
  • Published : 2019.11.10

Abstract

Self-centering wall (SCW) is a resilient and sustainable structural system which incorporates unbonded posttensioning (PT) tendons to provide self-centering (SC) capacity along with supplementary dissipators to dissipate seismic energy. Hysteretic energy dissipators are usually placed at two sides of SCWs to facilitate ease of postearthquake examination and convenient replacement. To achieve a good prediction for the skeleton curve of the wall, this paper firstly developed an analytical investigation on lateral load responses of self-centering walls with distributed vertical dampers (VD-SCWs) using the concept of elastic theory. A simplified method for the calculation of limit state points is developed and validated by experimental results and can be used in the design of the system. Based on the analytical results, parametric analysis is conducted to investigate the influence of damper and tendon parameters on the performance of VD-SCWs. The results show that the proposed approach has a better prediction accuracy with less computational effects than the Perez method. As compared with previous experimental results, the proposed method achieves up to 60.1% additional accuracy at the effective linear limit (DLL) of SCWs. The base shear at point DLL is increased by 62.5% when the damper force is increased from 0kN to 80kN. The wall stiffness after point ELL is reduced by 69.5% when the tendon stiffness is reduced by 75.0%. The roof deformation at point LLP is reduced by 74.1% when the initial tendon stress is increased from $0.45f_{pu}$ to $0.65f_{pu}$.

Keywords

Acknowledgement

Supported by : Central Universities

References

  1. Aaleti, S. and Sritharan, S. (2009), "A simplified analysis method for characterizing unbonded post-tensioned precast wall systems", Eng. Struct., 31(12), 2966-2975. https://doi.org/10.1016/j.engstruct.2009.07.024.
  2. Abdalla, J. A., Saqan, E. I. and Hawileh, R. A. (2014), "Optimum seismic design of unbonded post-tensioned precast concrete walls using ANN", Comput. Concrete, 13(4), 547-567. http://dx.doi.org/10.12989/cac.2014.13.4.547.
  3. Armouti, N. S. (1993), "Seismic performance of precast concrete structural walls", Ph.D. Dissertation, Lehigh University, Bethlehem, PA.
  4. Bai Y., Lin X. (2015), "Numerical simulation on seismic collapse of thin-walled steel moment frames considering post local buckling behavior", Thin Wall. Struct., 94, 424-434. https://doi.org/10.1016/j.tws.2015.04.033.
  5. Bayat M., Abdollahzadeh G. (2011), "On the effect of the near field records on the steel braced frames equipped with energy dissipating devices", Latin American J. Solids Struct., 8(4), 429-443. http://dx.doi.org/10.1590/S1679-78252011000400004.
  6. Bayat M., Abdollahzade G. (2011), "Analysis of the steel braced frames equipped with ADAS devices under the far field records", Latin American J. Solids Struct., 8(2), 163-181. http://dx.doi.org/10.1590/S1679-78252011000200004.
  7. Bayat M., Bayat M. (2014), "Seismic behavior of special moment-resisting frames with energy dissipating devices under near source ground motions", Steel Compos. Struct., 16(5), 533-557. https://doi.org/10.12989/scs.2014.16.5.533.
  8. Eatherton, M. R., Ma, X., Krawinkler, H., Mar, D., Billington, S., Hajjar, J. F. and Deierlein, G. G. (2014), "Design concepts for controlled rocking of self-centering steel-braced frames", J. Struct. Eng., 140(11), https://doi.org/10.1061/(ASCE)ST.1943-541X.0001047.
  9. Erkmen, B. and Schultz, A. E. (2009), "Self-centering behavior of unbonded post-tensioned precast concrete shear walls", J. Earthq. Eng., 13(7), 1047-1064. https://doi.org/10.1080/13632460902859136.
  10. Garlock, M. M., Ricles, J. M. and Sause, R. (2005), "Experimental studies of full-scale posttensioned steel connections", J. Struct. Eng., 131(3), 438-448. https://doi.org/10.1061/(ASCE)0733-9445(2005)131:3(438).
  11. Guo, T., Xu, Z., Song, L., Wang, L. and Zhang, Z. (2017), "Seismic resilience upgrade of RC frame building using self-centering concrete walls with distributed friction devices", J. Struct. Eng., 143(12), https://doi.org/10.1061/(ASCE)ST.1943-541X.0001901
  12. Guo, T., Zhang, G. and Chen, C. (2014), "Experimental study on self-centering concrete wall with distributed friction devices", J. Earthq. Eng., 18(2), 214-230. https://doi.org/10.1080/13632469.2013.844211.
  13. Huang, X., Zhou, Z., Xie, Q., Xue, R. and Zhu, D. (2017), "Force distribution analysis of self-centering coupled-beams for moment-resisting-frames without floor elongation", Eng. Struct., 147, 328-344. https://doi.org/10.1016/j.engstruct.2017.05.055.
  14. Hu, X., Zhang, Y. and Moghaddasi B, N. S. (2012), "Seismic performance of reinforced concrete frames retrofitted with self-centering hybrid wall", Adv. Struct. Eng., 15(12), 2131-2143. https://doi.org/10.1260/1369-4332.15.12.2131
  15. Kim, H. J. and Christopoulos, C. (2008), "Friction damped posttensioned self-centering steel moment-resisting frames", J. Struct. Eng., 134(11), 1768-1779. https://doi.org/10.1061/(ASCE)0733-9445(2008)134:11(1768).
  16. Kurama, Y.C. (2000) "Seismic design of unbonded post-tensioned precast concrete walls with supplemental viscous damping", ACI Struct. J., 97(4), 648-658.
  17. Kurama, Y.C. (2001), "Simplified seismic design approach for friction-damped unbonded post-tensioned precast concrete walls", ACI Struct. J., 98(5), 705-716.
  18. Kurama Y.C. (1997), "Seismic analysis, behavior and design of unbonded post-tensioned precast concrete walls", Ph.D. Dissertation, Lehigh University, Bethlehem, PA.
  19. Kurama, Y., Sause, R., Pessiki, S. and Lu, L. W. (1999), "Lateral load behavior and seismic design of unbonded post-tensioned precast concrete walls", ACI Struct. J., 96(4), 622-632.
  20. Kurama, Y.C., Sause, R., Pessiki, S. and Lu, L. W. (2002), "Seismic response evaluation of unbonded post-tensioned precast walls", ACI Struct. J., 99(5), 641-651.
  21. Maurya A., Eatherton M.R. (2016), "Experimental study of the restoring force mechanism in the self-centering beam (SCB)", Frontier. Struct. Civil Eng., 10(3), 272-282. https://doi.org/10.1007/s11709-016-0346-x.
  22. Priestley, M. N. and Tao, J. R. (1993), "Seismic response of precast prestressed concrete frames with partially debonded tendons", PCI J., 38(1), 58-69. https://doi.org/10.15554/pcij.01011993.58.69
  23. Perez FJ, Pessiki S, Sause R. (2004a) "Experimental and analytical lateral load response of unbonded post-tensioned precast concrete walls", ATLSS Report No. 04-11; Department of Civil Engineering, Lehigh University.
  24. Perez, F. J., Pessiki, S. and Sause, R. (2004b), "Seismic design of unbonded post-tensioned precast concrete walls with vertical joint connectors", PCI J., 49(1), 58-79.
  25. Perez, F. J., Pessiki, S. and Sause, R. (2004c), "Lateral load behavior of unbonded post-tensioned precast concrete walls with vertical joints", PCI J., 49(2), 48-64. https://doi.org/10.15554/pcij.03012004.48.64
  26. Perez, F. J., Pessiki, S. and Sause, R. (2013), "Experimental lateral load response of unbonded post-tensioned precast concrete walls", ACI Struct. J., 110(6), 1045-1055.
  27. Perez, F. J., Sause, R. and Pessiki, S. (2007), "Analytical and experimental lateral load behavior of unbonded posttensioned precast concrete walls", J. Struct. Eng., 133(11), 1531-1540. https://doi.org/10.1061/(ASCE)0733-9445(2007)133:11(1531).
  28. Qiu, C. and Zhu, S. (2017), "Shake table test and numerical study of self-centering steel frame with SMA braces", Earthq. Eng. Struct. Dynam., 46(1), 117-137. https://doi.org/10.1002/eqe.2777.
  29. Restrepo, J. I. and Rahman, A. (2007), "Seismic performance of self-centering structural walls incorporating energy dissipators", J. Struct. Eng., 133(11), 1560-1570. https://doi.org/10.1061/(ASCE)0733-9445(2007)133:11(1560).
  30. Sritharan S, Aaleti S, Thomas D (2007) "Seismic analysis and design of precast concrete jointed wall systems", ISU-ERI-Ames report, Ames (Iowa), Department of Civil, Construction and Environmental Engineering, Iowa State University.
  31. Thomas DJ, Sritharan S. (2004), "An evaluation of seismic design guidelines proposed precast jointed wall systems", ISU-ERI-Ames report ERI-04643, Ames (Iowa), Department of Civil and Construction and Environmental Engineering, Iowa State University.
  32. Xue, J., Qi, L., Yang, K. and Wu, Z. (2017), "Dynamic experimental study on single and double beam-column joints in steel traditional-style buildings", Struct. Eng. Mech., 63(5), 617-628. https://doi.org/10.12989/sem.2017.63.5.617.
  33. Xue, J., Bai, F., Qi, L., Sui, Y. and Zhou, C. (2018), "Research on damage and identification of mortise-tenon joints stiffness in ancient wooden buildings based on shaking table test", Struct. Eng. Mech., 65(5), 547-556. https://doi.org/10.12989/sem.2018.65.5.547
  34. Zhou, Z., Xie, Q., Lei, X.C., He, X.T. and Meng, S.P. (2015), "Experimental investigation of the hysteretic performance of dual-tube self-centering buckling-restrained braces with composite tendons", J. Compos. Construct., 19(6), https://doi.org/10.1061/(ASCE)CC.1943-5614.0000565.