Experimental studies on the behaviour of headed shear studs for composite beams in fire

  • Lim, Ohk Kun (R&D Laboratory, Korea Fire Institute) ;
  • Choi, Sengkwan (School of the Built Environment, Ulster University) ;
  • Kang, Sungwook (Fire Safety Centre, Korea Conformity Laboratories) ;
  • Kwon, Minjae (Fire Safety Centre, Korea Conformity Laboratories) ;
  • Choi, J. Yoon (Fire Safety Centre, Korea Conformity Laboratories)
  • Received : 2019.03.04
  • Accepted : 2019.08.27
  • Published : 2019.09.25

Abstract

Steel and concrete composite structures are commonly applied in multi-story buildings as they maximise the material strength through composite action. Despite the popularity of employing a trapezoidal deck slab, limited experimental data are available under elevated temperatures. The behaviour of the headed shear stud embedded in a transverse trapezoidal deck and solid slab was investigated at both ambient and fire conditions. Twelve push-out tests were conducted according to the ISO 834 standard fire utilising a customised electric furnace. A stud shearing failure was observed in the solid slab specimen, whereas the failure mode was changed from a concrete-dominated failure to the stud shearing in the transverse deck specimen with an increase in temperature. Comparisons between the experimental observations and design requirements are presented. The Eurocode design guidance on the transverse deck slab gives a highly conservative estimate for shear resistance. A new design formula was proposed to determine the capacity of the shear connection regardless of the slab type when the stud shearing occurs at high temperatures.

Keywords

References

  1. ANSI/AISC 360-10 (2010), Specification for Structural Steel Buildings; American Institute of Steel Construction (AISC), Chicago, IL, USA.
  2. CEN (2009), EN 1994-1-1:2004, Eurocode 4 - design of composite steel and concrete structures - Part 1-1: General rules and rules for buildings, European Committee for standardization, Brussel, Belgium.
  3. CEN (2014a), EN 1992-1-1: 2004, Eurocode 2 - Design of concrete structures - Part 1-1: General rules for buildings, European Committee for standardization, Brussel, Belgium.
  4. CEN (2014b), EN 1994-1-2, Eurocode 4 - design of composite steel and concrete structures - Part 1-2: General rules - Structural fire design, European Committee for standardization, Brussel, Belgium.
  5. Chen, L.Z., Li, G.Q. and Jiang, S.C. (2012), "Experimental studies on the behavior of headed stud shear connectors at elevated temperatures", Proceedings of the 7th International Conference on Structures in Fire, Zurich, Switzerland, June.
  6. Chen, L.-Z., Ranzi, G., Jiand, S.-C., Tahmaseninia, F. and Li, G.-Q. (2015), "Behaviour and design of shear connectors in composite slabs at elevated temperatures", J. Constr. Steel Res., 115, 387-397. https://doi.org/10.1016/j.jcsr.2015.08.025
  7. Dara, S. (2015), "Behavior of the Shear Studs in Composite Beams at Elevated Temperatures", Ph.D. Dissertation; University of Texas at Austin, TX, USA.
  8. Davoodnabi, S.M., Mirhosseini, S.M. and Shariati, M. (2019), "Behavior of steel-concrete composite beam using angle shear connectors at fire condition", Steel Compos. Struct., Int. J., 30(2), 141-147. https://doi.org/10.12989/scs.2019.30.2.141
  9. Ellobody, E. and Young, B. (2006), "Performance of shear connection in composite beams with profiled steel sheeting", J. Constr. Steel Res., 62(7), 682-694. https://doi.org/10.1016/j.jcsr.2005.11.004
  10. He, Y.-L., Wu, X.-D., Xiang, Y.-Q., Wang, Y.-H., Liu, L.-S. and He, Z.-H. (2017), "Mechanical behavior of stud shear connectors embedded in HFRC", Steel Compos. Struct., Int. J., 24(2), 177-189. https://doi.org/10.12989/scs.2017.24.2.177
  11. Hicks, S. (2009), "Strength and Ductility of Headed Stud Connectors Welded in Modern Profiled Steel Sheeting", Struct. Eng. Int., 19(4), 415-419. https://doi.org/10.2749/101686609789846975
  12. ICC (2017), 2018 International Building Code (IBC), International Code Council, Inc., Washington DC, USA.
  13. ISO (2016), ISO 6892-1, Metallic materials - Tensile testing - Part 1: Method of test at room temperature, International Organization for Standardization, Geneva, Switzerland.
  14. Kumar, P. and Chaudhary, S. (2019), "Effect of reinforcement detailing on performance of composite connections with headed studs", Eng. Struct., 179, 476-492. https://doi.org/10.1016/j.engstruct.2018.05.069
  15. Luo, Y., Hoki, K., Hayashi, K. and Nakashima, M. (2016), "Behavior and Strength of Headed Stud-SFRCC Shear Connection. I: Experimental Study", J. Struct. Eng., 142(2). https://doi.org/10.1061/(ASCE)ST.1943-541X.0001363
  16. Mashiri, F.R., Mirza, O., Canuto, C. and Lam, D. (2017), "Postfire Behaviour of Innovative Shear Connection for Steel-Concrete Composite Structures", Structures, 9, 147-156. https://doi.org/10.1016/j.istruc.2016.12.001
  17. McCam-Bartlett, S. (2019), Steel Construction Cost, Report of the British Constructional Steelwork Association and Steel for Life.
  18. Nellinger, S., Odenbreit, C., Obiala, R. and Lawson, M. (2017), "Influence of transverse loading onto push-out tests with deep steel decking", J. Constr. Steel Res., 128, 335-353. https://doi.org/10.1016/j.jcsr.2016.08.021
  19. Qi, J., Wang, J., Li, M. and Chen, L. (2017), "Shear capacity of stud shear connectors with initial damage: Experiment, FEM model and theoretical formulation", Steel Compos. Struct., Int. J., 25(1), 79-92. https://doi.org/10.12989/scs.2017.25.1.079
  20. Qureshi, J., Lam, D. and Ye, J. (2011), "The influence of profiled sheeting thickness and shear connector's position on strength and ductility of headed shear connector", Eng. Struct., 33(5), 1643-1656. https://doi.org/10.1016/j.engstruct.2011.01.035
  21. Rodrigues, J.P.C. and Laim, L. (2014), "Experimental investigation on the structural response of T, T-block and TPerfobond shear connectors at elevated temperatures", Eng. Struct., 75, 299-314. https://doi.org/10.1016/j.engstruct.2014.06.016
  22. Shahabi, S.E.M., Ramli Sulong, N.H., Shariati, M. and Shah, S. (2016), "Performance of shear connectors at elevated temperatures - A review", Steel Compos. Struct., Int. J., 20(1), 185-203. https://doi.org/10.12989/scs.2016.20.1.185
  23. Sun, Q., Nie, X., Denavit, M.D., Fan, J. and Liu, W. (2019), "Monotonic and cyclic behavior of headed steel stud anchors welded through profiled steel deck", J. Constr. Steel Res., 157, 121-131. https://doi.org/10.1016/j.jcsr.2019.01.022
  24. Wang, A.J. (2012), "Numerical investigation into headed shear connectors under fire", J. Struct. Eng., 138(1), 118-122. https://doi.org/10.1061/(ASCE)ST.1943-541X.0000428
  25. Xu, C. and Sugiura, K. (2014), "Analytical investigation on failure development of group studs shear connector in push-out specimen under biaxial load action", Eng. Fail. Anal., 37, 75-85. https://doi.org/10.1016/j.engfailanal.2013.11.010
  26. Yasuda, S., Michikoshi, S., Kobayashi, Y. and Narihara, H. (2008), "Experimental study on shear strength of headed stud shear connectors at high temperature", J. Struct. Constr. Eng. (Trans. of AIJ), 73(630), 1417-1423. https://doi.org/10.3130/aijs.73.1417
  27. Zhao, B. and Kruppa, J. (1996), "Experimental and numerical investigation of fire behavior of steel and concrete composite beams", Proceedings of Engineering Foundation Conference, ASCE, New York, NY, USA, June.

Cited by

  1. The bearing capacity of monolithic composite beams with laminated slab throughout fire process vol.38, pp.1, 2019, https://doi.org/10.12989/scs.2021.38.1.087
  2. Structural performance of steel-concrete composite bridges utilising innovative blind bolt shear connectors vol.40, pp.4, 2019, https://doi.org/10.12989/scs.2021.40.4.581