DOI QR코드

DOI QR Code

Experimental and numerical study on the collapse failure of long-span transmission tower-line systems subjected to extremely severe earthquakes

  • Tian, Li (School of Civil Engineering, Shandong University) ;
  • Fu, Zhaoyang (School of Civil Engineering, Shandong University) ;
  • Pan, Haiyang (School of Civil Engineering, Shandong University) ;
  • Ma, Ruisheng (School of Civil Engineering, Shandong University) ;
  • Liu, Yuping (School of Civil Engineering, Shandong University)
  • Received : 2019.03.09
  • Accepted : 2019.03.25
  • Published : 2019.05.25

Abstract

A long-span transmission tower-line system is indispensable for long-distance electricity transmission across a large river or valley; hence, the failure of this system, especially the collapse of the supporting towers, has serious impacts on power grids. To ensure the safety and reliability of transmission systems, this study experimentally and numerically investigates the collapse failure of a 220 kV long-span transmission tower-line system subjected to severe earthquakes. A 1:20 scale model of a transmission tower-line system is constructed in this research, and shaking table tests are carried out. Furthermore, numerical studies are conducted in ABAQUS by using the Tian-Ma-Qu material model, the results of which are compared with the experimental findings. Good agreement is found between the experimental and numerical results, showing that the numerical simulation based on the Tian-Ma-Qu material model is able to predict the weak points and collapse process of the long-span transmission tower-line system. The failure of diagonal members at weak points constitutes the collapse-inducing factor, and the ultimate capacity and weakest segment vary with different seismic wave excitations. This research can further enrich the database for the seismic performance of long-span transmission tower-line systems.

Keywords

Acknowledgement

Supported by : National Natural Science Foundation of China, Shandong University

References

  1. Albermani, F., Kitipornchai, S. and Chan, R.W.K. (2009), "Failure analysis of transmission towers", Eng. Fail. Anal., 16(6), 1922-1928. https://doi.org/10.1016/j.engfailanal.2008.10.001.
  2. Bai, F.L., Hao, H., Bi, K.M. and Li, H.N. (2011), "Seismic response analysis of transmission tower-line system on a heterogeneous site to multi-component spatial ground motions", Adv. Struct. Eng., 286(3), 565-585. https://doi.org/10.1260/1369-4332.14.3.457.
  3. Eslamlou, S.D. and Asgarian, B. (2017), "Determining critical areas of transmission towers due to sudden removal of members", Case Stud. Eng. Fail. Anal., 9, 138-147. https://doi.org/10.1016/j.csefa.2015.09.005.
  4. GB 50260-2013 (2013), Code for Seismic Design of Electrical Installations, China Architecture & Building Press, Beijing, China.
  5. Ghobarah, A., Aziz, T.S. and El-Attar, M. (1996), "Response of transmission lines to multiple support excitation", Eng. Struct., 18(12), 936-946. https://doi.org/10.1016/S0141-0296(96)00020-X.
  6. Hall, J.F., Holmes, W. and Somers, P. (1994), "Northridge Earthquake, January 17, 1994", Preliminary Reconnaissance Report.
  7. Kempner, L.J. and Smith, S. (1984), "Cross-rope transmission tower-line dynamic analysis", J. Struct. Eng., ASCE, 110(6), 1321-1335. https://doi.org/10.1061/(ASCE)0733-9445(1984)110:6(1321).
  8. Kotsubo, S., Takanishi, T., Uno, K. and Sonoda, T. (1985), "Dynamic tests and seismic analysis of high towers of electrical transmission line", Tran. JPN Soc. Civil Eng., 15, 72-75.
  9. Li, H.N., Shi, W.L., Wang, G.X. and Jia, L.G. (2005), "Simplified models and experimental verification for coupled transmission tower-line system to seismic excitations", J. Sound Vib., 286(3), 565-585. https://doi.org/10.1016/j.jsv.2004.10.009.
  10. NCREE (1999), "Investigation report of Chi-Chi Earthquake", National Center for Research on Earthquake Engineering.
  11. Park, H.S., Choi, B.H., Kim, J.J. and Lee, T.H. (2016), "Seismic performance evaluation of high voltage transmission towers in South Korea", KSCE J. Civil Eng., 20(6), 2499-2505. https://doi.org/10.1007/s12205-015-0723-3.
  12. Sedov, L. (1959), Similarity and Dimensional Methods in Mechanics, CRC Press.
  13. Shinozuka, M. (1995), "The Hanshin-Awaji Earthquake of January 17", 1995 Performance of Lifelines, Technical Report NCEER, 95 US National Center for Earthquake Engineering Research.
  14. Tian L., Ma, R.S. and Qu, B. (2018a), "Influence of different criteria for selecting ground motions compatible with IEEE 693 required response spectrum on seismic performance assessment of electricity transmission towers", Eng. Struct., 156, 337-350. https://doi.org/10.1016/j.engstruct.2017.11.046.
  15. Tian, L., Gai, X. and Qu, B. (2017a), "Shake table tests of steel towers supporting extremely long span electricity transmission lines under spatially correlated ground motions", Eng. Struct., 132, 791-807. https://doi.org/10.1016/j.engstruct.2016.11.068.
  16. Tian, L., Gai, X., Qu, B., Li, H. and Zhang, P. (2016a), "Influence of spatial variation of ground motions on dynamic responses of supporting towers of overhead electricity transmission systems: An experimental study", Eng. Struct., 128, 67-81. https://doi.org/10.1016/j.engstruct.2016.09.010.
  17. Tian, L., Ma, R.S., Li, H.N. and Wang, Y. (2016b), "Progressive collapse of power transmission tower-line system under extremely strong earthquake excitations", Int. J. Struct. Stab. Dyn., 16(7), 1550030. https://doi.org/10.1142/S0219455415500303.
  18. Tian, L., Ma, R.S., Qiu, C.X., Xin, A.Q., Pan, H.Y. and Guo, W. (2018b), "Influence of multi-component ground motions on seismic responses of long-span transmission tower-line system: An experimental study", Earthq. Struct., 15(6), 583-593. https://doi.org/10.12989/eas.2018.15.6.583.
  19. Tian, L., Pan, H.Y. and Ma, R.S. (2019), "Probabilistic seismic demand model and fragility analysis of transmission tower subjected to near-field ground motions", J. Constr. Steel Res., 156, 266-275. https://doi.org/10.1016/j.jcsr.2019.02.011.
  20. Tian, L., Pan, H.Y., Ma, R.S. and Qiu, C.X. (2017b), "Collapse simulations of a long span transmission tower-line system subjected to near-fault ground motions", Earthq. Struct., 13(2), 211-220. https://doi.org/10.12989/eas.2017.13.2.211.
  21. Wang, W.M., Li, H.N. and Tian, L. (2013), "Progressive collapse analysis of transmission tower-line system under earthquake", Adv. Steel Constr., 9(2), 161-172.
  22. Zhang, M.Z. (1997), "Study on similitude laws for shaking table tests", Earthq. Eng. Eng. Vib., 17(2), 52-58.
  23. Zheng, H.D. and Fan, J. (2018), "Analysis of the progressive collapse of space truss structures during earthquakes based on a physical theory hysteretic model", Thin Wall. Struct., 123, 70-81. https://doi.org/10.1016/j.tws.2017.10.051.
  24. Zheng, H.D., Fang, J. and Long, X.H. (2017), "Analysis of the seismic collapse of a high-rise power transmission tower structure", J. Constr. Steel. Res., 134, 180-193. https://doi.org/10.1016/j.jcsr.2017.03.005.