DOI QR코드

DOI QR Code

Experimental research on design wind loads of a large air-cooling structure

  • Yazhou, Xu (School of Civil Engineering, Xi'an University of Architecture and Technology) ;
  • Qianqian, Ren (School of Civil Engineering, Xi'an University of Architecture and Technology) ;
  • Guoliang, Bai (School of Civil Engineering, Xi'an University of Architecture and Technology) ;
  • Hongxing, Li (Northwest Electric Power Design Institute)
  • 투고 : 2018.02.08
  • 심사 : 2018.11.03
  • 발행 : 2019.04.25

초록

Because of the particularity and complexity of direct air-cooling structures (ACS), wind parameters given in the general load codes are not suitable for the wind-resistant design. In order to investigate the wind loads of ACS, two 1/150 scaled three-span models were designed and fabricated, corresponding to a rigid model and an aero-elastic model, and wind tunnel tests were then carried out. The model used for testing the wind pressure distribution of the ACS was defined as the rigid model in this paper, and the stiffness of which was higher than that of the aero-elastic model. By testing the rigid model, the wind pressure distribution of the ACS model was studied, the shape coefficients of "A" shaped frame and windbreak walls, and the gust factor of the windbreak walls were determined. Through testing the aero-elastic model, the wind-induced dynamic responses of the ACS model was studied, and the wind vibration coefficients of ACS were determined based on the experimental displacement responses. The factors including wind direction angle and rotation of fan were taken into account in this test. The results indicated that the influence of running fans could be ignored in the structural design of ACS, and the wind direction angle had a certain effect on the parameters. Moreover, the shielding effect of windbreak walls induced that wind loads of the "A" shaped frame were all suction. Subsequently, based on the design formula of wind loads in accordance with the Chinese load code, the corresponding parameters were presented as a reference for wind-resistant design and wind load calculation of air-cooling structures.

키워드

과제정보

연구 과제 주관 기관 : National Natural Science Foundation of China, Ministry of Education of China

참고문헌

  1. Badri, A.A., Hussein, M.M. and Attia, W.A. (2015), "Study of wind tunnel test results of high-rise buildings compared to different design codes", Wind Struct., 20(5), 623-642. https://doi.org/10.12989/was.2015.20.5.623
  2. Butler, C. and Grimes, R. (2014), "The effect of wind on the optimal design and performance of a modular air-cooled condenser for a concentrated solar power plant", Energy, 68, 886-895. https://doi.org/10.1016/j.energy.2014.01.086
  3. Chen, L., Yang, L.J., Du, X.Z. and Yang, Y.P. (2016), "A novel layout of air-cooled condensers to improve thermo-flow performances", Appl. Energy., 165, 244-259. https://doi.org/10.1016/j.apenergy.2015.11.062
  4. Duvenhage, K. and Kroger, D.G. (1996), "The influence of wind on the performance of forced draught air-cooled heat exchangers", J. Wind Eng. Ind. Aerod., 62(2-3), 259-277. https://doi.org/10.1016/S0167-6105(96)00082-7
  5. Du, N.J., Bai, G.L., Xu, Y.Z. and Qin, C.G. (2017), "Experimental and numerical researches on the seismic behavior of tubular reinforced concrete columns of air-cooling structures", Int. J. Concr. Struct. Mater., 11(3), 459-475. https://doi.org/10.1007/s40069-017-0207-6
  6. Edgar, T.H. and Sordo, E. (2017), "Structural behaviour of lattice transmission towers subjected to wind load", Struct. Infrastruct. Eng., 13(11), 1462-1475. https://doi.org/10.1080/15732479.2017.1290120
  7. GB 50009-2012 (2012), Load code for the design of building structures, China Architecture and Building Press; Beijing, China.
  8. Gu, H.F., Qiu, F.Q. and Wang, H.J. (2011), "Structure optimization of an air-cooling system platform at a large power plant", Heat Transf. Eng., 32(11-12), 1069-1074. https://doi.org/10.1080/01457632.2011.556503
  9. Gu, Z.F., Chen, X.R. and William, L. (2007), "Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant", Int. J. Thermal Sci., 46(3), 308-317. https://doi.org/10.1016/j.ijthermalsci.2006.04.007
  10. He, W.F., Dai, Y.P., Wang, J.F., Li, M.Q. and Ma, Q.Z. (2013), "Performance prediction of an air-cooled steam condenser using UDF method", Appl. Therm. Eng., 50(1), 1339-1350. https://doi.org/10.1016/j.applthermaleng.2012.06.020
  11. Ke, S.T., Wang, H. and Ge, Y.J. (2016), "Wind load effects and equivalent static wind loads of three-tower connected tall buildings based on wind tunnel tests", Struct. Eng. Mech., 58(6), 967-988. https://doi.org/10.12989/sem.2016.58.6.967
  12. Li, B., Liu, J. and Gao, J.M. (2015), "Surface wind pressure tests on buildings with various non-uniformity morphological parameters", J. Wind Eng. Ind. Aerod., 137, 14-24. https://doi.org/10.1016/j.jweia.2014.11.015
  13. Li, X.E., Wang, N.L., Wang L.G., Yang, Y.P. and Marechal, F. (2018), "Identification of optimal operating strategy of direct air-cooling condenser for Rankine cycle based power plants", Appl. Energy, 209, 153-166. https://doi.org/10.1016/j.apenergy.2017.10.081
  14. Maniscalco, N. (2014), "Design and performance characterization of high power density air-cooled compact condenser heat exchangers", Ph.D. Dissertation, University of Illinois at Urbana-Champaign, Urbana, Illinois.
  15. Moore, J., Grimes, R., Walsh, E. and O'Donovana, A. (2014). "Modelling the thermodynamic performance of a concentrated solar power plant with a novel modular air-cooled condenser." Energy, 69, 378-391. https://doi.org/10.1016/j.energy.2014.03.028
  16. Owen, M.T.F. and Kroger, D.G. (2011), "An investigation of aircooled steam condenser performance under windy conditions using computational fluid dynamics", J. Eng. Gas Turbine Power., 133(6), 831-844.
  17. Rodrigues, A.M., Tome, A. and Gomes, M.G. (2017), "Computational study of the wind load on a free-form complex thin shell structure", Wind Struct., 25(2), 177-193. https://doi.org/10.12989/WAS.2017.25.2.177
  18. Rooyen, J.A.V. (2008), "Performance trends of an air-cooled steam condenser under windy conditions", J. Eng. Gas Turbine Power., 130(2), 277-285.
  19. Xu, Y.Z., Bai G.L. and Zhu, J.N. (2015), "Pseudo-dynamic test and numerical simulation of a large direct air-cooling structure", Struct. Des. Tall Spec. Build., 24(4), 280-299. https://doi.org/10.1002/tal.1166
  20. Yang, F.L., Dang, H.X., Niu, H.W., Zhang, H.J. and Zhu, B.R. (2016), "Wind tunnel tests on wind loads acting on an angled steel triangular transmission tower", J. Wind Eng. Ind. Aerod., 156, 93-103. https://doi.org/10.1016/j.jweia.2016.07.016
  21. Yang, L.J., Wang, M.H., Du, X.Z. and Yang, Y.P. (2012), "Trapezoidal array of air-cooled condensers to restrain the adverse impacts of ambient winds in a power plant", Appl. Energy, 99(6), 402-413. https://doi.org/10.1016/j.apenergy.2012.06.006