References
- IEEE (2006), Recommended Practice for Seismic Design of Substations, The Institute of Electrical and Electronics Engineers, New York, USA.
- AASHTO (2003), Guide Specifications for Horizontally Curved Steel Girder Highway Bridges with Design Examples for I-girder and Box-girder Bridges, Washington, DC., USA.
- Akiyama, H. (1985), Earthquake-Resistant Limit-State Design for Buildings, University of Tokyo Press, Tokyo, Japan.
- ASCE (2005), Minimum Design Loads for Buildings and Other Structures, American Society of Civil Engineers, VA, Reston, USA.
- Anagnos, T. (2001), "Development of an electrical substation equipment performance database for evaluation of equipment fragilities", Pacific Earthquake Engineering Research Center.
- ANSI (American National Standards Institute) (1996), "American National Standard High-Voltage Air Disconnect Switches Interrupter Switches, Fault Initiating Switches, Grounding Switches, Bus Supports and Accessories Control Voltage Ranges-Schedules of Preferred Ratings Construction Guidelines and Specification", Institute of Electrical and Electronics Engineers, https://doi.org/10.1109/IEEESTD.1996.95627.
- Applied Technology Council (ATC) (2007), Guidelines for Seismic Performance: Assessment of Buildings. Washington D.C., USA.
- Asgarian, B., Khazaee, H. and Mirtaheri, M. (2012), "Performance evaluation of different types of steel moment resisting frames subjected to strong ground motion through incremental dynamic analysis", J. Steel Struct., 12(3), 363-379, https://doi.org/10.1007/s13296-012-3006-6.
- Ashrafi, S.A.H.N. (2003), "Issues of seismic response and retrofit for critical substation equipment", M.Sc. Dissertation, New Jersey Institute of Technology, USA.
- Bai, W., Dal, J., Zhou, H., Yang, Y. and Ning, X. (2017), "Experimental and analytical studies on multiple tuned mass dampers for seismic protection of porcelain electrical equipment", Earthq. Eng. Eng. Vib., 16(4), 803-813. https://doi.org/10.1007/s11803-017-0416-7.
- Buckle, I.G., Constantinou, M.C., Diceli, M. and Ghasemi, H. (2006), "Seismic Isolation of Highway Bridges", MCEER-06-SP07, Federal Highway Administration, Multidisciplinary Center for Earthquake Engineering Research, State University of New York; USA.
- Cheng, Y., Li, S., Lu, Z., Liu, Z. and Zhu, Z. (2018), "Seismic risk mitigation of cylindrical electrical equipment with a novel isolation device", Soil Dynam. Earthq. Eng., 111, 41-52. https://doi.org/10.1016/j.soildyn.2018.04.001
- Dastous, J.B. and Der Kiureghian, A. (2010), Application guide for the design of flexible and rigid bus connections between substation equipment subjected to earthquakes, Pacific Earthquake Engineering Research Center, USA.
- Dastous, J.B. and Pierre, J.H. (1996), "Experimental investigation on the dynamic behavior of flexible conductors between substation equipment during an earthquake", IEEE Transactions on Power Delivery, 11(2), 801-807, https://doi.org/10.1109/61.489337.
- Davani, M., Hatami, S. and Zare, A. (2016), "Performance-based evaluation of strap-braced cold-fonned steel frames using incremental dynamic analysis", Steel Compos. Struct., 21(6), 1369-1388, https://doi.org/10.12989/SCS.2016.21.6.1369.
- Erdik, M. (2000), "Report on 1999 Kocaeli and Duzce (Turkey) earthquakes", Bogazici University, Kandilli Observatory and Earthquake Research Institute; Turkey.
- Ghalibafian, H. (2001), "An experimental study on the seismic interaction of flexible conductors with electrical substation equipment", M.Sc. Dissertation, Department of Civil Engineering, The University of British Columbia (UBC), USA.
- Gokce, T., Yuksel, E. and Orakdogen, E. (2019), "Seismic performance enhancement of high-voltage post insulators by a polyurethane spring isolation device", Bullet. Earthq. Eng., 17(3), 1739-1762. https://doi.org/10.1007/s10518-018-0494-6.
- IEC 60672-3 (1997), Ceramic and Glass-Insulating Materials-Part 3: Specifications for Individual Materials, International Standards and Conformity Assessment for all electrical, electronic and related technologies, Switzerland.
- IEEE Standard 1527 (2006), IEEE Recommended Practice for the DeSign of Flexible Buswork Located in Seismically Active Areas, Institute of Electrical and Electronics Engineers, New York, USA.
- Jeon, B., Chang, S., Kim, S. and Kim, N. (2015), "Base isolation performance of a cone-type friction pendulum bearing system", Struct. Eng. Mech., 53(2), 227-248, http://ds.doi.org/10.12989/sero.2015.53.2.227.
- Karabork, T. (2011), "Performance of multi-storey structures with high dsmping rubber bearing base isolation systems", Struct. Eng. Mech., 39(3), 399-410. https://doi.org/10.12989/sem.2011.39.3.399.
- Karami-Mohammadi, R., Mirtaheri, M., Salkhordeh, M. and Hariri-Ardebili, M.A. (2019), "A cost-effective neural network-based damage detection procedure for cylindrical equipment", Adv. Mech. Eng., 11(7), https://doi.org/10.1177/1687814019866942.
- Khorami, M., Khorami, M., Motahar, H, Alvansazyazdi, M, Shariati, M. and Jalali, A. (2017), "Evaluation of the seismic performance of special moment frames using incremental nonlinear dynamic analysis", Struct. Eng. Mech., 63(2), 259-268. https://doi.org/10.12989/sem.2017.63.2.259.
- Der Kiureghian, A., Sackman, J.L. and Hong, K.J. (1999), Interaction in Interconnected Electrical Substation Equipment Subjected to Earthquake Ground Motions, Pacific Earthquake Engineering Research Center (PEER), CA, USA.
- Liu, R., Zhang, M. and Wu, Y. (2012) "Vulnerability Study of Electric Power Grid in Different Intensity Area in Wenchuan Earthquake", 15th World Conference of Earthquake Engineering (WCEE), Lisboa, Portugal. Septernber.
- Lopez Garcia, D. and Soong, T. (2003), "Sliding fragility of block-type non-structural components. Part 1: Unrestrained components", Earthq. Eng. Struct. Dynam., 32(1), 111-129. https://doi.org/10.1002/eqe.217.
- Ma, G.L. and Xie, Q. (2018), "Seismic analysis of a 500-kV power transformer of the type damaged in the 2008 Wenchuan earthquake", J. Performance Construct. Facilities, 32(2), https://doi.org/10.10611(ASCE)CF.1943-5509.0001145.
- Mohammadi, R.K. and Mosaffa, E. (2018), "Seismic Rehabilitation of Substation Equipment by Friction Pendulum Systems", The 2018 Structures Congress, Incheon, Korea, August
- FEMA P-751, (2009), "Seismically Isolated Structures, FEMA P-751", NEHRP Recommended Provisions: Design Examples, National Institute of Building Sciences, USA.
- Porter, K.A., Kiremidjian, A.S. and LeGrue, J.S. (2001), "Assembly-based vulnerability of buildings and its use in performance evaluation", Earthq. Spectra, 17(2), 291-312. https://doi.org/10.1193/1.1586176.
- Tokyo Electric Power (2011), Report Regarding Collection of Reports pursuant to the Provisions of Article 106, Paragraph 3 of the Electricity Business Act, Tokyo Electric Power, Tokyo, Japan.
- Priestley, M.N. (1997), "Myths and fallacies in Earthquake Engineering", Concrete International, 19(2), 54-63, https://doi.org/10.14359/983.
- Richins, B.D. (2011), "Evaluation and seismically isolated substructure redesign of a typical multi-span pre-stressed concrete girder highway hridge", M.Sc. Dissertation, Utah State University, Utah, USA.
- Roussis, P.C. (2009), "Study on the effect of uplift-restraint on the seismic response of base-isolated structures", J. Struct. Eng., 135(12), 1462-1471. https://doi.org/10.10611(ASCE)ST.1943-541X.0000070. https://doi.org/10.1061/(ASCE)ST.1943-541X.0000070
- Ala Saadeghvaziri, M, Feizi, B., Keropner Jr., L. and Alston, D. (2009), "On seismic response of substation equipment and application of base isolation to transformers". IEEE Transactions on Power Delivery, 25(1), 177-186, https://doi.org/10.1109/TPWRD.2009.2033971.
- Schiff, A.J. (1998), Guide to Improved Earthquake Performance of Electric Power Systems, American Society of Civil Engineers, VA, Reston, USA.
- Stearns, C.C. and Filiatrault, A. (2005), Electrical Substation Equipment Interaction: Experimental Rigid Conductor Studies, Pacific Earthquake Engineering Research Center, USA.
- Tavanir (1990), "Damage report of Shahid Beheshti power plant in 1990 earthquake", Tavanir, Tehran, Iran.
- Varnvatsikos, D. and Cornell, C.A. (2002), "Incremental dynaroic analysis", Earthq. Eng. Struct. Dynam., 31(3), 491-514, https://doi.org/10.100/leqe.141.
- Wang, L., Ona, Jin, Liu, Weiqing and Wang, Shuguang (2013), "Full-scale tests and analytical model of the Teflon-based lead rubber isolation bearings", Struct. Eng. Mech., 48(6), 809-822. https://doi.org/10.12989/SEM.2013.48.6.809.
- Warn, G.P. and Ryan, K.L. (2012), "A review of seismic isolation for buildings: historical development and research needs", Buildings, 2(3), 300-325, https://doi.org/10.3390/buildings2030300.
- Waseern, M. and Spacone, E. (2017), "Fragility curves for the typical multi-span simply supported bridges in northern Pakistao ", Struct. Eng. Mech., 64(2), 213-223, https://doi.org/10.12989/sero.2017.64.2.213.
- Wen, B., Zhang, J. and Niu, D. (2004), "Application of isolation technology in high-voltage electrical equipments", The 14th World Conference on Earthquake Engineering, Beijing, China
- Yang, Z. and Lam, E.S. (2015), "Seismic mitigation of an existing building by connecting to a base-isolated building with viscoelastic dampers", Struct. Eng. Mech., 53(1), 57-71. https://doi.org/10.12989/SEM.2015.53.1.057.
- Yue, H., Chen, J. and Xu, Q. (2019), "Optimal design of multiple annular tuned liquid dampers for seismic reduction of 1,100-kV composite bushing", Struct. Control Health Monitor., 26(4), e2316, https://doi.org/10.1002/stc.2316.
- Zayas, V.A., Low, S.S and Mabin, S.A. (1990), "A simple pendulum technique for achieving seismic isolation", Earthq. Spectra, 6(2), 317-333, https://doi.org/10.1193/l.l585573.
- ASCE 7-05, (2005), Minimum Design Loads for Buildings and Orher Structures, American Society of Civil Engineers, VA, Reston, USA.
Cited by
- Comparing Hysteretic Energy and Ductility Uniform Annual Failure Rate Spectra for Traditional and a Spectral Shape-Based Intensity Measure vol.2021, 2019, https://doi.org/10.1155/2021/2601087
- Seismic progressive collapse mitigation of buildings using cylindrical friction damper vol.20, pp.1, 2021, https://doi.org/10.12989/eas.2021.20.1.001