DOI QR코드

DOI QR Code

Fabrication and Evaluation of Digital Signal Processor for Multi-Lane Energy Measurement System

개별 전로 전력 계측을 위한 디지털 신호처리 프로세서 기반 전력 관제 시스템의 제작 및 평가

  • Received : 2018.08.27
  • Accepted : 2018.09.19
  • Published : 2018.09.30

Abstract

Due to the development of society, the demand for electric power has increased and the quality control of electric power has become an important issue. In order to efficiently perform such power management, we propose a DSP based power measurement system for multi-wire power measurement. Since the conventional power measurement system can measure only the power of one line, a power quality measurement device is required for each line in order to measure the power quality of the individual line. Respectively. The system proposed in this paper proposes a system capable of real-time measurement of power quality at up to 12 points using digital signal processing algorithm, and the prototype based on this system was evaluated through the official test report of Korea Electrotechnology Research Institute. As a result of the performance test, it was evaluated that the error range is excellent at ${\pm}0.3%$.

사회의 발달로 인하여 전력에 대한 수요가 증가함과 동시에 전력의 품질 관리가 중요한 문제로 부상하였다. 이러한 전력관리를 효율적으로 수행하기 위하여 본 논문에서는 다선로 전력 계측을 위한 DSP 기반 전력 측정 시스템을 제안한다. 종래의 전력 계측 시스템이 하나의 선로의 전력만을 측정 할 수 있었기 때문에, 개별 선로에 대한 전력 품질 측정을 위해서는 선로마다 전력 품질 측정 장치가 필요로 하였으며 이는 비용적인 문제로 인하여 시스템의 실제 구현이 불가능한 구조였다. 본 논문에서 제안하는 시스템은 디지털 신호 처리 알고리즘을 이용하여 최대 12개소의 전력 품질을 실시간 계측 할 수 있는 시스템을 제안하며, 이를 토대로 한 시제품을 한국전기연구원의 공인시험 성적서를 통하여 그 성능을 평가 받았다. 성능 시험결과 정밀 계측의 오차 범위 ${\pm}0.3%$의 우수한 성능임을 평가 받았다.

Keywords

References

  1. J. Lee, "Current Status and Expected Effect of EMS localization," Journal of Korea Electric Association, vol.457, pp. 26-29, Jan. 2015.
  2. D. Minoli, K. Sohraby, and B. Occhiogrosso, "IoT Considerations, Requirements, and Architectures for Smart Buildings-Energy Optimization and Next-Generation Building Management Systems," IEEE Internet of Things Journal, vol.4, no.1, pp. 269-283, Feb. 2017. https://doi.org/10.1109/JIOT.2017.2647881
  3. F. Farmani et al, "A conceptual model of a smart energy management system for a residential building equipped with CCHP system," International Journal of Electrical Power & Energy Systems, vol.95, pp. 523-536, Feb. 2018. https://doi.org/10.1016/j.ijepes.2017.09.016
  4. IEC Standard, IEC60255: Measuring relays and protection equipment, part 27: product safety requirements 10.6.4.4, 2013.
  5. IEC Standard, IEC60255: Measuring relays and protection equipment, part 27: product safety requirements 10.6.4.3, 2013.
  6. IEC Standard, IEC60255: Measuring relays and protection equipment, part 27: product safety requirements 10.6.4.2, 2013.
  7. G.J. Kim and Bongsoon Kang, "System Design for Real-Time Measuring of Power Quality and Harmonics Distortion using Digital Signal Processor," Journal of the Korea Institute of Information and Communication Enginnering, vol.20, no.7, pp. 1283-1289, Jul. 2016. https://doi.org/10.6109/jkiice.2016.20.7.1283
  8. Korea Electrotechnology Research Institute Certification No. :2017-TRD16S01672