DOI QR코드

DOI QR Code

태양광 발전 PCS 구성부품에 대한 열적특성 및 고장모드영향분석

Thermal Characteristic and Failure Modes and Effects Analysis for Components of Photovoltaic PCS

  • Kim, Doo-Hyun (Department of Safety Engineering, Chungbuk National University) ;
  • Kim, Sung-Chul (Department of Safety Engineering, Chungbuk National University) ;
  • Kim, Yoon-Bok (Korea Polytechnics College Cheongju Campus)
  • 투고 : 2018.05.30
  • 심사 : 2018.08.06
  • 발행 : 2018.08.31

초록

This paper is analyzed for the thermal characteristics(1 year) of the 6 components(DC breaker, DC filter(including capacitor and discharge resistance), IGBT(Insulated gate bipolar mode transistor), AC filter, AC breaker, etc.) of a photovoltaic power generation-based PCS(Power conditioning system) below 20 kW. Among the modules, the discharge resistance included in the DC filter indicated the highest heat at $125^{\circ}C$, and such heat resulting from the discharge resistance had an influence on the IGBT installed on the rear side the board. Therefore, risk priority through risk priority number(RPN) of FMEA(Failure modes and effects analysis) sheet is conducted for classification into top 10 %. According to thermal characteristics and FMEA, it is necessary to pay attention to not only the in-house defects found in the IGBT, but also the conductive heat caused by the discharge resistance. Since it is possible that animal, dust and others can be accumulated within the PCS, it is possible that the heat resulting from the discharge resistance may cause fire. Accordingly, there are two options that can be used: installing a heat sink while designing the discharge resistance, and designing the discharge resistance in a structure capable of avoiding heat conduction through setting a separation distance between discharge resistance and IGBT. This data can be used as the data for conducting a comparative analysis of abnormal signals in the process of developing a safety device for solar electricity-based photovoltaic power generation systems, as the data for examining the fire accidents caused by each module, and as the field data for setting component management priorities.

키워드

참고문헌

  1. Ministry of Trade, Industry and Energy, "The 8th Framework Plan for Power Supply", pp.48-55, 2017.
  2. D. H. Kim, S. C. Kim, J. S. Park, E. J. Kim and E. S. Kim, "Analysis of Risk Priority Number for Grid-connected Energy Storage System", J. Korean Soc. Saf., Vol. 31, No. 2, pp.1-8, 2016.
  3. D. S. Park, Reduction Plan of Electrical Fire through Analysis of the Electric Failure and Accident Cases and Application of ETA in PV System, Graduate School, Chungbuk National University, pp.28-29, 2016.
  4. D. H. Kim, S. C. Kim, E. S. Kim and Y. H. Park, "Risk Assessment of Energy Storage System Using Event Tree Analysis", J. Korean Soc. Saf., Vol. 31, No. 3, pp.34-41, 2016. https://doi.org/10.14346/JKOSOS.2016.31.3.34
  5. A. Colli, "Extending Performance and Evaluation Risks of PV Systems Failure Using a Fault Tree and Event Tree Approach: Analysis of the Possible Application", presented at the 38th IEEE Photovoltaic Specialist Conference, 2012.
  6. R. Freancis and A. Colli, "Information-Based Reliability Weighting for Failure Mode Prioritization in Photovoltaic (PV) Module Design, Probabilistic Safety Assessment and Management PSAM 12, 2014.
  7. M, Catelni, L. Ciani and E. Simoni, "Thermal Analysis of Critical Components in Photovoltaic Inverter", IEEE International Instrumentation and Measurement Technology Conference Proceedings, pp.1891-1595, 2012.
  8. D. H. Kim, S. C. Kim, J. S. Park, E. J. Kim and E. S. Kim, "Analysis of Risk Priority Number for Grid-connected Energy Storage System", J. Korean Soc. Saf., Vol. 31, No. 2, pp.10-17, 2016. https://doi.org/10.14346/JKOSOS.2016.31.2.10
  9. I. S. Song, Quality Bible ; FMEA, pp.96-99, 2014.
  10. INTERNATIONAL SEMATECH, Failure Mode and Effects Analysis(FMEA): A Guide for Continuous Improvement for the Semiconductor Equipment Industry, 1992.
  11. Z. J. Ma and S. Thomas, "Reliability and Maintainability in Photovoltaic Inverter Design", Reliability and Maintainability Symposium, 2011.
  12. KOSHA, "A Study on Development of Evaluation Model for Reliability and Safety of Temporary Electric Power Installations" pp.31-32, 2003.