DOI QR코드

DOI QR Code

An Experimental Study on Improvement of Fire Extinguishing Performance of Basic Sprinkler System

간이스프링클러 설비의 소화성능 향상에 관한 실험적 연구

  • Received : 2017.11.27
  • Accepted : 2018.05.29
  • Published : 2018.06.30

Abstract

A basic sprinkler system is a fire extinguishing system that can be easily installed in a fire-vulnerable place such as a publicly used establishments. However, the publicly used establishments are not only complicated in structure, but also have a large amount of flammable interior materials, and the users are not normally in a normal state, which is a very dangerous fire-fighting object. Therefore, due to the low fire extinguishing performance of the basic sprinkler system installed in the publicly used establishments, the fire suppression control can not be performed quickly in case of fire, which may increase the life and property damage. In this study, the cases of quantitative changes of extinguishing water used in basic sprinkler system and the cases of addition of additives such as wetting agents, reinforced agents to improve extinguishing performance were compared. Experimental results showed that the extinguishing performance was improved as the quantity of extinguishing water increase and the reinforced agents showed similar performance to that of 60% increase in the amount of extinguishing water. The cooling time to $200^{\circ}C$ and oxygen concentration were improved up to 14.3% and 34.5%, respectively. In the case of using the wetting agent, the cooling time to $200^{\circ}C$ and oxygen concentration did not show any significant improvement, but showed the effect of preventing deep seated fire. In order to prevent loss of life and property, it is necessary to improve the performance of the basic sprinkler system by increasing amount of extinguishing water or using additives like reinforced agents.

Keywords

References

  1. NFA(National Fire Agency), http://www.nfds.go.kr
  2. NFA(National Fire Agency), "National Fire Safety Codes of Basic Sprinkler Systems (NFSC 103A)", 2016.
  3. D. J. Kim, S. S. Oh, J. K. Lee and S. W. Kim, "Developing Sprinklers on Space Characteristic Fit of Multiplex Use Facility", Autumn Conference of Korean Institute of Fire Science and Engineering, pp. 437-440, 2012.
  4. NFA(National Fire Agency), "Standard of Model Approval and Inspection Technology for Sprinkler Head", 2016.
  5. M. H. Kim and C. S. Shin, "Efficiency of Water Mist Suppression System Containing Viscosity Agent to Extinguish Wood Cribs Fire", J. Korean Soc. Saf., Vol. 29, No. 4, 2014.
  6. NFA(National Fire Agency), "Performance-oriented Design Methods and Standards for Fire-fighting Systems", 2016.
  7. H. J. Kim, W. K. Kim, H. J. Park, S. H. Choi and J. H. Chun, "A Study on the Performance Criteria for Performance-Based Design", Summer Conference of Korea Institute of Fire Science & Engineering, 2004.
  8. W. D. Walton, "SFPE Handbook of Fire Protection Engineering", Section 3, National Fire Protection Association, 2008.
  9. Korea Occupational Safety & Health Agency, http://www.kosha.or.kr
  10. Y. J. Yeo, "Water-Based Fire Protection Systems Engineering", pp. 19, Korea Fire Safety Lavoratory, 2006.