DOI QR코드

DOI QR Code

Analysis on magnetizing characteristics of current limiting reactor using HTSC module

  • Received : 2018.02.08
  • Accepted : 2018.03.18
  • Published : 2018.03.31

Abstract

In this paper, the magnetizing characteristics of the current limiting reactor (CLR) using $high-T_C$ superconducting (HTSC) module were analyzed. Since the saturation of iron core comprising the CLR using HTSC module deteriorates its current limiting operation, the design of the CLR using HTSC module considering the magnetizing characteristics is needed. For the analysis on the magnetizing characteristics, the flux linkage and the magnetizing current of this CLR using HTSC module were derived from its electrical equivalent circuit. Through the analysis on the linkage flux versus the magnetizing current, obtained from the short-circuit tests, the suppressing effect of the iron core's saturation was discussed.

Keywords

References

  1. H. Yamaguchi, T. Kataoka, K. Yaguchi, S. Fujita, K. Yoshikawa, and K. Kaiho, "Characteristics analysis of transformer type superconducting fault current limiter," IEEE. Trans. Appl. Supercond., vol. 14, no. 2, pp. 815-818, 2004. https://doi.org/10.1109/TASC.2004.830284
  2. H. M. Kim, K. B. Park, B. W. Lee, I. S. Oh, H. G. Lee, and Y. Iwasa, "Current limiting characteristics of transformer type superconducting fault current limiter," IEEE. Trans. Appl. Supercond., vol. 15, no. 2, pp. 2106-2109, 2005. https://doi.org/10.1109/TASC.2005.849463
  3. T. Janowski, S. Kozak, B. Kondratowicz-Kucewicz, G. Wojtasiewicz, and J, Kozak, "Analysis of Transformer Type Superconducting Fault Current Limiters," IEEE Trans. Appl. Supercond. vol. 17, no. 2, pp. 1788-1790, 2007. https://doi.org/10.1109/TASC.2007.898134
  4. T. Kataoka, and H. Yamaguchi, "Comparative Study of Transformer-Type Superconducting Fault Current Limiters Considering Magnetic Saturation of Iron Core," IEEE Trans. Appl. Supercond., vol. 42, no. 10, pp. 3386-3388, 2006.
  5. Sung-Hun Lim, Tae-Hee Han, Seong-Woo. Yim, Hyo-Sang Choi and Byoung-Sung Han, "Current limiting characteristics of a flux-lock type SFCL dependent on fault angles and core saturation," IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 1827-1830, 2007. https://doi.org/10.1109/TASC.2007.899868