Corrosion Behavior of Boiler Tube under Circulation Water Conditions in District Heating System

지역난방 시스템의 순환수에 따른 보일러 튜브의 부식 특성

  • Hong, Minki (Department of Materials Science and Engineering, Chungnam National University) ;
  • Cho, Jeongmin (Department of Materials Science and Engineering, Chungnam National University) ;
  • Song, Min Ji (Department of Materials Science and Engineering, Chungnam National University) ;
  • Kim, Woo Cheol (Frontier Research & Training Institute, Korea District Heating Corp.) ;
  • Ha, Tae Baek (Frontier Research & Training Institute, Korea District Heating Corp.) ;
  • Lee, Soo Yeol (Department of Materials Science and Engineering, Chungnam National University)
  • 홍민기 (충남대학교 신소재공학과) ;
  • 조정민 (충남대학교 신소재공학과) ;
  • 송민지 (충남대학교 신소재공학과) ;
  • 김우철 (한국지역난방공사 미래개발원) ;
  • 하태백 (한국지역난방공사 미래개발원) ;
  • 이수열 (충남대학교 신소재공학과)
  • Received : 2018.11.20
  • Accepted : 2018.12.05
  • Published : 2018.12.31

Abstract

In this study, corrosion behavior of a SA178-A alloy used in the boiler tube of a district heating system was investigated in different environments where it was exposed to pure water, district heating (DH) water, and filtered district heating (FDH) water. After the corrosion test, the surface morphology was examined for observation of the number of pitting sites and pitting area fraction, using a scanning electron microscope. The DH water and FDH water conditions resulted in a lower corrosion potential and pitting potential, and revealed a significantly higher corrosion rate than the pure water condition. The pitting sites in the DH water (pH 9.6) were approximately eighteen times larger than those in the pure water (pH 9.6). Compared to the DH water, the corrosion potential became more noble in the FDH water condition, where iron ions were reduced through filtration. However, the corrosion rate increased in the FDH water due to an increased concentration of chloride ions, which deteriorated the stability of passive film.

Keywords

E1COB2_2018_v17n6_287_f0001.png 이미지

Fig. 1 Schematic view of the direct supply and recovery district heating system.

E1COB2_2018_v17n6_287_f0002.png 이미지

Fig. 2 Specimen preparation for the corrosion test.

E1COB2_2018_v17n6_287_f0003.png 이미지

Fig. 3 Potentiodynamic polarization behavior in pure water and district heating water conditions.

E1COB2_2018_v17n6_287_f0004.png 이미지

Fig. 4 Surface morphology of the tested samples: (a) before electrochemical test, (b) pure water at pH 9.6, (c) pure water at pH 10.5, (d) district heating (DH) water at pH 9.6, (e) filtered district heating (FDH) water at pH 9.6, (f) filtered district heating (FDH) water at pH 10.5.

Table 1 Chemical composition of SA178-A (wt%)

E1COB2_2018_v17n6_287_t0001.png 이미지

Table 2 Water conditions for potentiodynamic polarization

E1COB2_2018_v17n6_287_t0002.png 이미지

Table 3 Potentiodynamic polarization results using Tafel extrapolation

E1COB2_2018_v17n6_287_t0003.png 이미지

Table 4 Pitting sites and pitting area fraction for the tested samples after potentiodynamic polarization

E1COB2_2018_v17n6_287_t0004.png 이미지

References

  1. H. Lund, B. Moller, B. V. Mathiesen, and A. Dyrelund, Energy, 35, 1381 (2010). https://doi.org/10.1016/j.energy.2009.11.023
  2. Y. S. Chang, S. W. Jung, S. M. Lee, J. B. Choi, and Y. J. Kim, Appl. Therm. Eng., 27, 2524 (2007). https://doi.org/10.1016/j.applthermaleng.2007.02.001
  3. P. A. Ostergaard and H. Lund, Appl. Energ., 88, 479 (2011). https://doi.org/10.1016/j.apenergy.2010.03.018
  4. H. Gadd and S. Werner, Appl. Energ., 106, 47 (2013). https://doi.org/10.1016/j.apenergy.2013.01.030
  5. D. Connolly, H. Lund, B. V. Mathiesen, S. Werner, B. Moller, U. Persson, T. Boermans, D. Trier, P. A. Ostergaard, and S. Nielsen, Energ. Policy, 65, 475 (2014). https://doi.org/10.1016/j.enpol.2013.10.035
  6. H. Lund, S. Werner, R. Wiltshire, S. Svendsen, J. E. Thorsen, F. Hvelplund, and B. V. Mathiesen, Energy, 68, 1 (2014). https://doi.org/10.1016/j.energy.2014.02.089
  7. Y. S. Kim and J. G. Kim, Eng. Fail. Anal., 83, 193 (2018). https://doi.org/10.1016/j.engfailanal.2017.09.014
  8. F. D. Fatah, A. Mostafaei, R. H. Taghani, and F. Nasirpouri, Eng. Fail. Anal., 28, 69 (2013). https://doi.org/10.1016/j.engfailanal.2012.09.010
  9. KS B 6209, Water conditioning for boiler feed water and boiler water (2017).

Cited by

  1. 지역난방 냉각수 배관의 용접부 파손 분석 vol.19, pp.6, 2018, https://doi.org/10.14773/cst.2020.19.6.296