DOI QR코드

DOI QR Code

Study on the performance characteristics of a new CO2 auto-cascade heat pump system

새로운 CO2 오토 캐스케이드 열펌프 시스템의 성능특성 연구

  • Yun, Sang-Kook (Division of Mechanical and Energy Systems Engineering, Korea Maritime and Ocean University)
  • Received : 2017.01.06
  • Accepted : 2017.03.06
  • Published : 2017.03.31

Abstract

Owing to the harmful environmental effects of HCFC and CFC refrigerants discovered in the late 20th century, the need for environmentally friendly refrigerants such as $CO_2$ in cooling systems has increased. Air-source $CO_2$ heat pumps that utilize ambient heat in cold winter are less efficient because of a higher evaporation temperature, and it is difficult to manufacture the components of the heat pump owing to a super critical pressure of over 130 bar. This research aims to overcome these disadvantages and improve energy efficiency by introducing a new lower-pressure $CO_2$ auto-cascade heat pump system. $CO_2$-R32 zeotropic refrigerants were considered for two-stage expansion and effective cooling heat exchanging system configurations of the new auto-cascade heat pump. The results indicated that the efficiency of the two-stage expansion system was higher than that of the original one-stage expansion system. Furthermore, the two-stage expansion system showed significant performance improvements when the two-stage expansion stage from highest pressure of 70bar, intermediate expansion pressure of 25bar, and final low pressure of 10bar is applied. The COP of the new two-stage auto-cascade system (2.332) was 43.15% higher than that of the present simple auto-cascade system (1.629). Refrigerants having an evaporation temperature of $-10^{\circ}C$ or lower can be obtained that can be easily evaporated in an evaporator even at a low temperature.

20세기에 대두된 HCFC나 CFC계의 냉매들의 환경에의 악영향을 극복하기 위하여 보다 환경 친화적인 이산화탄소와 같은 자연냉매에 대한 관심이 커지고 있다. 겨울철 대기의 열원을 이용하여 증발을 유도하는 이산화탄소 열펌프는 증발기의 온도가 높아 효율이 상대적으로 낮아지고, 130bar가 넘는 고압으로 인하여 열펌프 설비 부품들의 제작의 어려움이 따르게 된다. 본 연구는 보다 낮은 압력의 새로운 2단 팽창식 $CO_2$ 오토 캐스케이드 열펌프를 고안하여 이러한 단점들을 해소하고 보다 효율을 증가시키고자 하였다. 새로운 오토 캐스케이드 열펌프에 2단 팽창방식과 효과적인 냉각방식의 시스템 구성을 하여 혼합냉매인 $CO_2$ 와 R32를 적용하였다. 공정에 고압 70bar, 중간 팽창압은 25bar, 최종 저압은 10bar를 적용하여 해석한 결과, 현재의 오토 캐스케이드 열펌프 공정의 COP는 1.629이었으나, 개선된 중간 압력 25bar의 2단 팽창 오토 캐스케이드 공정은 2.332로 현재의 공정보다 43.15% 향상되었다. 또한 저압측 증발기의 온도도 $-10^{\circ}C$ 이하가 되어 찬 외기에도 증발이 용이하게 발생되는 공정이 되었다. 본 공정이 향후 $CO_2$ 열펌프의 성능계수를 보다 향상시키고 고압에 따른 부품 문제들의 해소에 기여할 수 있는 공정으로 분석되었다.

Keywords

References

  1. G. Lorentzen, "Revival of carbon dioxide as a refrigerant," International Journal of Refrigeration, vol. 17, no. 5, pp. 292-301, 1994. https://doi.org/10.1016/0140-7007(94)90059-0
  2. P. Neksa, "CO2 heat pump systems," International Journal of Refrigeration, vol. 25, no. 4, pp. 421-427, 2002. https://doi.org/10.1016/S0140-7007(01)00033-0
  3. H. Tian, Z. Yang, M. Li, and Y. Ma, "Research and application of CO2 refrigeration and heat pump cycle," Science in China Series E: Technological Sciences, vol. 52, no. 6, pp. 1563-1575, 2009. https://doi.org/10.1007/s11431-009-0175-4
  4. T. Tsuruha, Y. Yamagami, and T. Matsubara, "Heat pump vending machine equipped with CO2 ejector refrigerating cycle," FUJI Electric Review, vol. 61, no. 3, pp. 158-162, 2015.
  5. P. Domanski and M. McLinden, "A simplified cycle simulation model for the performance rating of refrigerants and refrigerant mixtures," International Journal of Refrigeration, vol. 15, no. 2, pp. 81-88, 1992. https://doi.org/10.1016/0140-7007(92)90031-O
  6. S. G. Kim and M. S. Kim, "Experiment and simulation on the performance of an autocascade refrigeration system using carbon dioxide as a refrigerant," International Journal of Refrigeration, vol. 25, no. 8, pp. 1093-1101, 2002. https://doi.org/10.1016/S0140-7007(01)00110-4
  7. D. Kai, Z. Shaoqian, X. Weirong, and N. Xiaofeng, "A study on the cycle characteristics of an auto-cascade refrigeration system," Experimental Thermal and Fluid Science, vol. 33, no. 2, pp. 240-245, 2009. https://doi.org/10.1016/j.expthermflusci.2008.08.006
  8. M. Sivakumar and P. Somasudaram, "Exergy and performance analysis of three stage auto refrigerating cascade (3 stage ARC) system using Zeotropic mixture of eco-friendly refrigerants," International Review of Mechanical Engineering. vol. 8, no. 1, pp. 124-134, 2014.
  9. Y. Jianlin, Z. Hua, and L. Yanzhong, "Application of an ejector in autocascade refrigeration cycle for the performance improvement," International Journal of Refrigeration, vol. 31, no. 2, pp. 279-286, 2008. https://doi.org/10.1016/j.ijrefrig.2007.05.008
  10. S. N, Park and M. S. Kim, "Performance of autocascade refrigeration system using carbon dioxide and R134a, In: natural working fluids," 98 Proceedings of the IIR-Gustav Lorentzen Conference, Oslo, Norway, pp. 311-320, 1998.

Cited by

  1. Performance and Exergy Transfer Analysis of Heat Exchangers with Graphene Nanofluids in Seawater Source Marine Heat Pump System vol.13, pp.7, 2017, https://doi.org/10.3390/en13071762