분산전원이 도입된 배전계통에 초전도한류기 적용에 따른 과전류계전기 동작향상 연구

Study on Improvement of Overcurernt Relay (OCR)'s Operation Due to Application of Superconducting Fault Current Limiter (SFCL) in Power Distribution System with a Dispersed Generation

  • Lim, Seung-Taek (Dept. of Electrical Engineering, Soongsil University) ;
  • Lim, Sung-Hun (Dept. of Electrical Engineering, Soongsil University)
  • 투고 : 2017.01.16
  • 심사 : 2017.01.30
  • 발행 : 2017.02.01

초록

Due to the introduction of various types of dispersed generations (DGs) with larger capacity in a power distribution system, the short-circuit current is expected to be increased, which more requires for the effective fault current limiting methods. As one of the promising countermeasures, the superconducting fault current limiter (SFCL) has been noticed. However, the decreased fault current by SFCL affects the operation of the overcurrent relay (OCR), representative protective device in a power distribution system. In this paper, the operation of the overcurrent relay due to the application of a SFCL in a power distribution system with DG linked by its bus line was analysed through the short-circuit tests. To analyze the effect of the SFCL application in a power distribution system with DG, the experimental simulated circuits were designed and the short-circuit tests for the power distributed system assembled with the DG, the OCR and the SFCL were carried out. Through the analysis on the short-circuit tests, the application of the SFCL in a power distribution system with DG could be confirmed to be contributed to the operational improvement of overcurrent relay.

키워드

참고문헌

  1. L. Ye, L. Lin, and K. P. Juengst, "Application studies of superconducting fault current limiters in electric power system," IEEE Trans. appl. Supercond., vol. 18, no. 2, pp. 624-627, Jun. 2008. https://doi.org/10.1109/TASC.2008.920785
  2. KEPCO, Long-Term Prospects for Transmission System (2002-2015) 2002.12.
  3. S. R. Lee, J. Y. Kim, and J. Y. Yoon, "A study on SFCL systems for korean power system application," in 2005/2006 IEEE PES T&D.
  4. I. K. You, S. H. Lim, J. C. Kim, and O. B. Hyun, "Study on Protection Coordination Between Protective Devices in a Power Distribution System with an SFCL," IEEE Trans. Appl. Supercond., vol. 20, no. 3, pp. 1168-1171, June 2010. https://doi.org/10.1109/TASC.2010.2040267
  5. J. Driesen, P. Vermeyen, and R. Belmans, "Protection issues in microgrids with multiple distributed generation units," in Power Conversion Conf., Nagoya, April 2007, pp. 646-653.
  6. A. Henning, A. Wehner, and M. Kurrat, "Feasibility study of superconducting current limiter application in a cogeneration plant," IEEE Trans. Appl. Supercond., vol. 19, no. 3, pp. 1908-1912, June 2009. https://doi.org/10.1109/TASC.2009.2017720
  7. T. Genji, K. Miyazato, H. Tsutsushio, and T. Nishiwaki, "Study on required performance of fault current limiter for dispersed generator," Trans. IEE Japan, vol. 124-B, no. 1, pp. 15-21, Jan. 2004.
  8. T. Sato, M. Yamaguchi, T. Terashima, S. Fukui, J. Ogawa, H. Shimizu, and T. Sato, "Study on the Effect of Fault Current Limiter in Power System With Dispersed Generators," IEEE Trans. Appl. Supercond., vol. 17, no. 2, pp. 2331-2334, June 2007. https://doi.org/10.1109/TASC.2007.899884

피인용 문헌

  1. Analysis on Operational Improvement of OCR Using Voltage Component in a Power Distribution System for Application of SFCL pp.2093-7423, 2019, https://doi.org/10.1007/s42835-019-00089-x
  2. Study on Operational Characteristics of OCR with Voltage Component in a Power Distribution System with SFCL pp.2092-7592, 2019, https://doi.org/10.1007/s42341-019-00101-1