DOI QR코드

DOI QR Code

Performance Characteristics of Refrigerant R170(Ethane) Refrigeration System Using Liquid-gas Heat Exchanger

액-가스 열교환기를 이용한 R170(에탄)용 냉동시스템의 성능 특성

  • Ku, Hak-Keun (Department of Refrigeration and Air-conditioning Engineering, TongMyong University)
  • 구학근 (동명대학교 냉동공조공학과)
  • Received : 2016.08.04
  • Accepted : 2016.09.19
  • Published : 2016.10.31

Abstract

This paper considers the influence of internal heat exchangers to the efficiency of a refrigerating system using R170. These liquid-gas heat exchangers(internal or suction-line heat exchangers) can, in some cases, yield improved system performance while in other cases they degrade system performance. A steady state mathematical model is used to analysis the performance characteristics of refrigeration system with internal heat exchanger. The influence of operating conditions, such as the mass flowrate of R170, inner diameter tube and length of internal heat exchanger, to optimal dimensions of the heat exchanger is also analyzed in the paper. The main results were summarized as follows : the mass flowrate of R170, inner diameter tube and length of internal heat exchanger, and effectiveness have an effect on the cooling capacity, compressor work and RCI(Relative Capacity Index) of this system. Exception for the effect of inner diameter, the RCI of R170 with respect to refrigerant mass flowrate, the length and effectiveness of internal heat exchanger is about 2.1~3.3% higher than that of R13 at the same experimental conditions. With a thorough grasp of these effect, it is necessary to design the R170 compression refrigeration cycle using internal heat exchanger.

Keywords

References

  1. M. Y. Wen and C. Y. Ho, 2005, "Evaporation heat transfer and pressure drop characteristics of R-290(propane), R-600(butane), and a mixture of R-290/R-600 in the three-lines serpentine small-tube bank", Applied Thermal Engineering, Vol. 25, pp. 921-936.
  2. R. N. Richardson and J. S. Butterworth, 1995, "The performance of propane/isobutane mixtures in a vapour compression refrigeration system", Int. J. Refrigeration, Vol. 18, No. 1, pp. 58-62. https://doi.org/10.1016/0140-7007(94)P3712-A
  3. J. H. Hwang, I. C. Baek, D. S. Jung, 2006, "Performance of HCFC22 alternatives R1270, R290, R1270/R290, R290/HFC152a, R1270/R290 /RE170 refrigerants for air-conditioning and heat pump applications", SAREK, Vol. 18, No. 4, pp. 312-319.
  4. H. K. Oh and C. H. Son, 2012, "Performance analysis of a R744 and R404A cascade refrigeration system with internal heat exchanger", Journal of the Korean for Power System Engineering, Vol. 16, No. 1, pp. 38-43.
  5. H. K. Ku, 2009, "Performance Analysis of Refrigeration Cycle of Hydrocarbon Refrigerants using Suction-Line Heat Exchanger", Journal of the Korean-Academia Industrial Cooperation Society, Vol. 10, No. 9, pp. 2195-2201. https://doi.org/10.5762/KAIS.2009.10.9.2195
  6. W. F. Stoecker and D. J. Walukas, 1981, "Conserving energy in domestic refrigerators through the use of refrigerant mixture", ASHRAE Transactions, Vol. 87, No. 1, pp. 279-281.
  7. M. O. McLinden, 1990, "Optimum refrigerants for non-ideal cycles: an analysis employing corresponding states", In Proceedings ASHRAEPurdue CFC and IIR-Purdue Refrigeration Conferences, W. Lafayette (IN), pp. 17-20.
  8. D. A. Didion and P. A. Domanski, 1993, "Thermodynamic evaluation of R22 alternative refrigerants and refrigerant mixtures", ASHRAE Transactions, Vol. 99, No. 2, pp. 636-648.
  9. P. A. Domanski, D. A. Didion and J. P. Doyle, 1994, "Evaluation of suction-line/liquid-line heat exchange in the refrigeration cycle", Rev. Int. Froid, Vol. 7, pp. 487-493.
  10. H. Kruse, 2000, "Refrigerant Use in Europe", ASHRAE J., Vol. 42, pp. 16-25.
  11. C. H. Son et al., 2015, "Performance Analysis of Two-stage Compression Refrigeration System with Internal Heat Exchanger Applied Various Refrigerants", Journal of the Korean for Power System Engineering, Vol. 19, No. 6, pp. 82-88.
  12. J. I. Yoon and C. H. Son et al., 2014, "Heat Transfer and Pump Consumption Power of Indirect Refrigeration System Using as a Secondary Refrigerants", Journal of the Korean for Power System Engineering, Vol. 18, No. 2, pp. 25-30. https://doi.org/10.9726/kspse.2014.18.2.025
  13. EES : Engineering Equation Solver, 2010, fChart Software Inc.
  14. F. W. Dittus and L. M. K. Boelter, 1930, University of California, Berkeley, Publications Engineering, Vol. 2, pp. 443-448.