초록

In this study, in order to understand the degradation characteristics of oil-paper insulation for power transformers and OF cables, tan delta was measured using cable model specimens with long-term accelerated thermal and electrical aging. In addition, to find out the degradation level due to the accelerated aging, tensile strengths of aged papers were measured. As a result, tan ${\delta}$ showed the characteristics of slight decrease at the first stage and then increase with the aging time, which could be analyzed due to the evaporation of remaining moisture and the change of aging rate with time. Also, the trend of tensile strengths with aging temperature and time was appeared to be exponentially decreased and by use of these data equivalent calculated lifetimes and accelerated aging factors were derived for each aging temperatures. After then, tan ${\delta}$ was analyzed with the equivalent operating years. For all different aging temperatures, the aged data were very well fit to the equivalent operating years and it is shown that tan ${\delta}$ was increased with the decrease of tensile strength.

키워드

참고문헌

  1. P. Thomas et al, "Ageing studies on paper and oil to assess the condition of solid insulation used in power transformers", 7th International Conference on Solid Dielectrics, pp.69-72, 2001
  2. Lukasz Chmura et al, "Use of Dissipation Factor for Life Consumption Assessment and Future Life Modeling of oil-Filled High-Voltage Power Cables", IEEE Electrical Insulation Magazine, Vol. 28, No. 1, pp. 27-37, 2012 https://doi.org/10.1109/MEI.2012.6130529
  3. A. J. Kachler, I. Hohlein, "Aging of Cellulose at Transformer Service Temperatures. Part 1: Influence of Type of Oil and Air on the Degree of Polymerization of Pressboard, Dissolved Gases, and Furanic Compounds in Oil", IEEE Electrical Insulation Magazine, Vol. 21, No. 2, pp. 15-21, 2005 https://doi.org/10.1109/MEI.2005.1412215
  4. KS M ISO 1924-2, Paper and board - Determination of tensile properties
  5. H. P. Gasser, "Determining the aging parameters of cellulosic insulation in a transformer", IEE, High Voltage Engineering Symposium, No. 467, 4.143-147.P1, 22-27 August 1999
  6. IEC 60076-7, "Loading guide for oil-immersed power transformers", 2009
  7. A. M. Emsley, "Degradation of cellulosic insulation in power transformers. Part 3: Effects of oxygen and water on ageing in oil", IEE Proc-Sci Meas. Technol. Vol. 147, No. 3, pp. 115-119, November 2000 https://doi.org/10.1049/ip-smt:20000021