초록

A ground air heat exchanger (GAHX), also called earth air heat exchanger is a useful technology to be integrated with other renewable energy technologies. In this study, ground-air heat exchanger system for the air source heat pump is introduced. The purpose of this study is to design the volumetric flow rate and the length of GAHX system. A GAHX length model equation has been developed and used for calculation. GAHX thermal efficiency are recommended as 75% and 85% in order to optimize pipe length. $2,750m^3/h$, $2,420m^3/h$ of volumetric flow rate on 88.3m, 111.7m length are suggested for providing 7.5kW thermal capacity. And the number of path is recommended more than two to minimize pressure drop. For future study, advanced model equation study with ground thermal behavior and a more efficient GAHX design will be considered.

키워드

참고문헌

  1. Rehau Ecoair Ground-Air Heat Exchange System, www.rehau.com.
  2. Kang, E. C., Lee, E. J., and Min, K. C., 2014, Two way set temperature control impact study on ground coupled heat pump system energy saving, Korea Society of Geothermal Energy Engineerings, Vol. 10, pp. 7-12.
  3. Muehleisen, R. T., 2012, Simple design tools for earthair heat exchangers, In Fifth National Conference of IBPSA-USA, SimBuild, pp. 723.
  4. Hollmuller, P. and Lachal, B. M., TRNSYS compatible moist air hypocaust model, Final report, Centre universitaire d'etudes des problemes de l'energie, Geneve.
  5. Lee, K. H. and Strand, R. K., 2008, The cooling and heating potential of an earth tube system in buildings, Energy and Buildings, Vol. 40, pp. 486-494. https://doi.org/10.1016/j.enbuild.2007.04.003
  6. Vlad, G. E. C., Necula, H., and Badea, A., 2011, Thermoeconomic design of an earth to air heat exchanger used to preheat ventilation air in low energy buildings, International Conference on Energy, Environment, Entrepreneurship, Innovation, Lanzarote, Spania, pp. 11-16.
  7. De Paepe, M. and Janssens, A., 2003, Thermal-hydraulic design of earth-air heat exchangers, Energy and Buildings, Vol. 35, pp. 389-397. https://doi.org/10.1016/S0378-7788(02)00113-5

피인용 문헌

  1. Model Verification and Justification Study of Spirally Corrugated Pipes in a Ground-Air Heat Exchanger Application vol.12, pp.21, 2019, https://doi.org/10.3390/en12214047