초록
The purpose of this paper is to conduct ETA on six items of ESS: the whole system, battery, BMS, PCS, ESS and cable. To achieve that, ESS work flow and its components are categorized. Based on performance, human, environmental, management, and safety, this paper drew initiation events (IE) and end states (ES). ETA is applied to the main functions of each item, and the end states that may occur in one initiation event are suggested. In addition, detailed classification was performed to induce various end states on the basis of the suggested initiation events ; loss of grid electricity of ESS, loss of battery electricity(DC) of battery, impairment of electric function of BMS, loss of grid electricity(AC) of PCS, loss of data of EMS, Mechanical damage of cable, event sequence analysis conducted on the basis of event trees. If the suggested IEs and ESs are applied on the basis of ESS event cases, it is expected to prevent the same kinds of accident and operate ESS safely.