Abstract
Currently, the number of a shopping center building is increasing because most people want to go a shopping center building easily for buying many things and eating some foods. That are a normal trend these days. However, the increasing number of shopping center buildings has been increasing the number of shopping center building fires which also have been making social problems. Therefore, this study was conducted for the fire department connection among other fire facilities because it is important for fire suppression. The research subject is on the fire department connections that are on 70 shopping center buildings of more than 5 years old constructed. Survey and analysis were conducted for 70 fire department connections. The result of this study is that all installed fire department connections have a type that includes one or two holes each at 65mm wide, and the average distance between fire department connections and access roads is 4.85m. The total average percentage of insufficiency conditions such as drive ways for fire trucks, visibility, accessibility, pressure range sign, installed height, cover of the hole, etc. is 45.3%. So improvement of law and systems, that are fire facility construction and maintenance implementations, will be needed in my opinion.