DOI QR코드

DOI QR Code

An Experimental Study on Evaluation of Bond Strength of Arc Thermal Metal Spaying According to Treatment Method of Water Facilities Concrete Surface

수처리 시설물 콘크리트 표면처리 방법에 따른 금속용사 피막의 부착성능 평가에 관한 실험적 연구

  • Park, Jin-Ho (Department of Architectural Engineering, Han Yang University) ;
  • Lee, Han-Seung (School of Architecture, Hanyang University) ;
  • Shin, Jun-Ho (Department of Sustainable Architectural Engineering, Hanyang University)
  • Received : 2015.12.18
  • Accepted : 2016.01.28
  • Published : 2016.04.20

Abstract

In this study, the bond strength of metal spraying system by surface treatment of concrete (waterproof/corrosion method) in water treatment facilities was evaluated. The results showed that the system with Sa-P-R-(S) (sanding-perviousness surface hardener-surface roughness agent-metal spraying-sealing) led to the desirable performance. The bond strength, the coefficient of water permeability and air permeability were 3.7MPa, $0.68{\ast}10^{-8}cm/sec$, and $0.45{\ast}10^{-16}m^2$, respectively. In scanning electron microscope analysis, the microstructure of specimen coated with perviousness surface hardener was much denser than that without it. Therefore, the specimen coated with sanding-perviousness surface hardener-surface roughness agent-metal spraying-sealing had the best bond performance and was the most suitable system to concrete surface in water treatment facilities.

본 연구에서는 금속용사 시스템을 수처리 시설 콘크리트 구조물의 방수/방식 공법으로 사용하기 위하여 콘크리트 표면처리 방법에 따른 기초적 성능 평가 실험을 진행하였다. 실험결과 Sa-P-R-(S)(샌딩-침투성표면강화제-조면형성제-봉공처리)의 경우가 3.57MPa로 가장 높은 부착성능을 나타냈다. 부착성능이 확보된 면처리 방법을 기반으로 투수성, 투기계수 측정실험을 진행하였다. 실험 결과 Sa-P-R-(S)의 경우가 각각 $0.68{\times}10^{-8}cm/sec$, $0.45{\times}10^{-16}m^2$로 가장 우수한 성능을 나타내었다. 또한 SEM분석 결과 침투성 표면강화제를 도포한 실험체가 그렇지 않은 경우에 비해 콘크리트의 미세 구조가 더 치밀한 것을 확인 할 수 있었으며, 이러한 구조로 인해 침투제를 도포한 경우의 실험체에서 가장 높은 부착성능이 나타난 것으로 판단된다. 따라서 콘크리트의 표면 처리 방법은 금속용사 시스템을 적용하는데 있어, 매우 중요한 영향을 미치는 것으로 판단되며, 본 연구를 통하여 Sa-P-R-(S)의 경우가 수처리 시설 콘크리트 구조물의 적용하기에는 가장 적합한 면처리 방법이라 판단된다.

Keywords

References

  1. Choi SM. Techniques for Characterizing Surface Deterioration of Epoxy Exposed to Ozone Damage. Journal of the Korea Institute for Structural Maintenance and Inspection. 2014 May;18(3):167-77 https://doi.org/10.11112/jksmi.2014.18.3.167
  2. Kwk KS. Seo HJ, Miyauchi H, Kim GY, Oh SK. A Study on Suggestion of the Evaluation Method of O3 Deterioration of Waterproofing and Corrosion Prevention Materials in Concrete Facility for Advanced Water Treatment Using Ozone(O3) Sterilization. Journal of the Architecture Institute of Korea Structure & Construction. 2010 Sep;26(9):79-86
  3. Kim SR. Bond strength characteristics of Water Proofing and Corrosion Prevention Materials inside Ozone Contactor. In: Noh SK, Shin, HC, Kim TS, Cho BY, Kim YG, editors. Proceeding of Fall Annual Conference of the Korea Concrete Institute; 2011 Nov 9-11; Pyeong Chang Alpensia Convention Center Pyeong Chang Korea; Korea Concrete Institute. 2011. p.759-60
  4. Seo HJ. A Study on Suggestion of the Evaluation Method of O3 Deterioration of Waterproofing and Corrosion Prevention Materials in Concrete Facility for Advanced Water Treatment. In: Oh SK. editors Proceeding of Fall Annual Conference of the Korea Concrete Institute; 2010 Nov 5-6; Elysian Resort. ChunCheon Korea; Korea Concrete Institute. 2010. p. 149-50
  5. Chung MJ. A study on the Evaluation of Field Application for the Waterproofing or Corrosion Proof Construction Method, as Coating High Quality Filtration plant with Ozone Resistance Paints of Phenol Degeneration Polyamine [Master's thesis]. [Korea]: Seoul Nation University. 2006. 74 p.
  6. Noh SK. A Status Investigation of Waterproofing and Corrosion Prevention Materils in Advanced Water Tretment in domestic. Shin HC, Kim SR, Park HI, Cho BY, Kim YG, editors. Proceeding of Spring Annual Conference of the Korea Concrete Institute; 2011 May 11-13 Ramada Plaza Hotel, Jeju, Korea: Korea Concrete Institute. 2011. p. 609-10.
  7. Choi WC, Hong YG, Hong GS. Characteristics of FRP System for Strengthening Concrete Structures. Journal of the Korea Concrete Institute. 2000 Nov;12(6):63-9
  8. Jung SH, Lee MS. Experimental study on the Corrosion Protection Properties and Anticorrosive life of the Zn/Al Metal Spray Method according to the Contents Ratio of Zn and Al. Journal of the Architecture Institute of Korea Structure & Construction. 2003 Oct;19(10):59-66
  9. Guenbour A, Benbachir A, Kacemi A. Evaluation of the corrosion performance of zinc-phosphate-painted carbon steel. Surface and Coating Technology. 1999 Mar 12;113(1-2):36-43 https://doi.org/10.1016/S0257-8972(98)00816-0
  10. Cinca N, Lima CRC, Guilemany JM. An overview of intermetallics research and application: Status of thermal spray coatings. Journal of Materials Research and Technology. 2013 Mar 13;2(1):75-86 https://doi.org/10.1016/j.jmrt.2013.03.013
  11. Baek IY. An Experimental Study on the Electromagnetic Shielding Performance of Arc Thermal Metal Spraying Film as Shielding Material for High-altitude Electromagnetic Pulse(HEMP) [Master's thesis]. [Korea]: Hanyang University. 2015. 52 p.

Cited by

  1. Ozone Resistance, Water Permeability, and Concrete Adhesion of Metallic Films Sprayed on a Concrete Structure for Advanced Water Purification vol.7, pp.3, 2017, https://doi.org/10.3390/coatings7030041