DOI QR코드

DOI QR Code

기능성 필름의 열처리 온도에 따른 특성 분석

Characteristic Analysis of Functional Films according to the Annealing Temperature

  • 투고 : 2016.01.25
  • 심사 : 2016.02.29
  • 발행 : 2016.03.01

초록

Because of the low pollution resistance of the porcelain electrical insulator itself, in this work the anti-pollution performance of insulator was improved by using the functional coating. The ceramic substrates that components were same as the porcelain electrical insulator were used in this experiment. The functional films were coated on the ceramic substrate by using a spray coating method, and then the coated substrate were annealed under different coating condition such as natural curing and annealing temperature of $200^{\circ}C$, $300^{\circ}C$ and $400^{\circ}C$. Then, the contact angles of the coated surfaces were measured and the minimum angle ($8.3^{\circ}$) was obtained at $400^{\circ}C$. The anti-contamination properties were measured, revealing that as the contact angle decreased, the anti-contamination properties improved. The hardness and adhesion were small at the natural curing condition however the excellent mechanical properties were obtained under higher temperature annealing.

키워드

참고문헌

  1. X. Jiang, J. Hu, Z. Zhang, and J. Yuan, "Switching impulse flashover performance of different types of insulators at high altitude sites of above 2800 m," IEEE Trans. Dielectr. Electr. Insul., Vol.15, pp.1340-1345, 2008. https://doi.org/10.1109/TDEI.2008.4656242
  2. J. Sun, G. Gao, L. Zhou and G. Wu, "Pollution Accumulation on Rail Insulator in High-speed Aerosol," IEEE Trans. Dielectr. Electr. Insul., Vol.20, No.3, pp.731-738, 2013. https://doi.org/10.1109/TDEI.2013.6518942
  3. C.-B. Park, S.-N. Chun, B.-S. Lee, and C.-M. Chu, "Analysis of Contaminants Adhered and Insulation Characteristics on Polymeric Insulators," KIEE Conference, Vol.2008, No9, pp.56-57, 2008.
  4. Y.-J. Jeon, T.-H. Lee, K.-I. Choi, S.-B. Lee, and S.-G. Han, "A research on the tunnel insulator pollution characteristic in Korea Railroad," KIEE Conference, Vol.2009, No.7, pp.1169-1170, 2009.
  5. Y. S. Kim, K. M. Shong, and M. I. Choi, "A Study on Selection of Cleaning Period and Pollution Analysis of Insulators in Tunnel," Journal of KIIEE, Vol.24, No.4, pp.149-155, 2010.
  6. A. Fujishima and X. Zhang, "Titanium dioxide photocatalysis: present situation and future approaches," Comptes Rendus Chimie Vol.9, pp.750-760, 2006. https://doi.org/10.1016/j.crci.2005.02.055
  7. G. Bracco and B. Holst, "Surface Science Techniques," Springer-Verlag, Heidelberg, Vol.51, Ch.1, p.3, 2013.
  8. A. K. Tiwari, H. Kumar, R. Bajpai, and S. K. Tripathi, "Preparation of blends of epoxidised novolac resin and carboxylic terminated polybutadiene (CTPB) liquid rubber and evaluation of their physico-chemical characteristics," J. Chem. Pharm. Res., Vol.2, pp.172-178, 2010.
  9. M. E. McKnight, J. F. Seiler, T. Nguyen, and W. J. Rossiter, "Measuring Peel Adhesion of Coatings," J. Prot. Coat. Linings, Vol.12, pp.82-89, 1995.

피인용 문헌

  1. Development of Coating Process Technique for Anti-Fouling Electric Insulator vol.904, 2017, https://doi.org/10.4028/www.scientific.net/MSF.904.75