There is a growing concern on the improvement of water distribution pipeline for multi-regional water supply system in Korea along with its aging infrastructure. Rehabilitation of large diameter pipeline is more efficient in cost and time compared to replacement with trenching. The procedure for rehabilitation are diagnosis, cleaning, spraying coating material, and final inspection. The internal state of pipeline was carefully diagnosed and got C grade, which required rehabilitation. We found that 17,274,787,000 Korean won could be saved after pipe surface coating because of increased C coefficient of Hazen-Williams equation. Optimal coating material was D polyurea. We also found optimal distance between spraying nozzle and pipe wall to be 70 - 80 cm, which were critical factors for coating quality. This study also illustrated the time for spray drying to be more than 30 min. These results could be used in the quality control process during rehabilitation of aged pipelines.

Keywords

References

  1. AWWA (2008), C222-08 Polyurethane Coatings for the Interior and Exterior of Steel Water Pipe and Fittings
  2. Bae, C. H., Choi, D. Y., Kim, J. H., Kim, D. H. (2014), The assessment of self cleaning velocity and optimal flushing velocity in water distribution system, 28(4), pp. 441-451, Journal of Korean Society of Water and Wastewater https://doi.org/10.11001/jksww.2014.28.4.441
  3. Boxall, J. B., Skipworth, P. J., and Saul, A. J. (2003), Aggressive flushing for discolouration event mitigation in water distribution networks. 3(1/2), pp. 179-186, Water Sci. and Technol. : Water Supply
  4. Dandy, G. and Engelhardt, M. (2001), Optimal scheduling of water pipe replacement using genetic algorithms., 127:4(214), pp. 214-223, J. Water Resources Planning Manage https://doi.org/10.1061/(ASCE)0733-9496(2001)127:4(214)
  5. Kim, J. and Mays, L. (1994), Optimal rehabilitation model for water distribution systems., 120(5), pp. 674-692, J. Water Resources Planning Manage https://doi.org/10.1061/(ASCE)0733-9496(1994)120:5(674)
  6. Herz, R. K. (1998), Exploring rehabilitation needs and strategies for water distribution networks, 47(6), pp. 275-283, Journal of Water Supply: Research and Technology - AQUA https://doi.org/10.2166/aqua.1998.33
  7. Hyun, I. H. and Lee, C. K. (1999), Effect of C factor on the analysis of water distribution system, 13(2), pp. 23-32, Journal of Korean Society of Water and Wastewater
  8. Korean ministry of environment (MOE) (2015), Statistics on Korean water supply in 2014
  9. KWWA (2010), The Korean guidance manual for water supply system
  10. KWWA (2011), The Korean guidance manual for wastewater system
  11. Ministry of Environment (MOE) (2015), Korean national statistics for water supply system.
  12. Rogers, P. and Grigg, N. (2009), Failure assessment modeling to prioritize water pipe renewal: Two case studies, 15:3(162), pp. 162-171, Journal of Infrastructure System https://doi.org/10.1061/(ASCE)1076-0342(2009)15:3(162)
  13. Rajani, B., Kleiner, Y., (2001a), Comprehensive review of structural deterioration of water mains: physically based models, 3(3), pp. 151-164, Urban Water https://doi.org/10.1016/S1462-0758(01)00032-2
  14. Rajani, B., Kleiner, Y., (2001b), Comprehensive review of structural deterioration of water mains: statistical models, 3(3), pp. 131-150, Urban Water https://doi.org/10.1016/S1462-0758(01)00033-4

Cited by

  1. Pipe Bursting 공법의 적용성 검토를 위한 주요 성능평가 항목의 기초실험연구 vol.32, pp.5, 2016, https://doi.org/10.11001/jksww.2018.32.5.435